Plan Review Details - Permit 02120927
Plan Review Stops For Permit 02120927
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By jwitmer Date 2003-02-13 Time 11:06 Rev Time 0.75
Received By jwitmer Date 2003-02-13 Time 10:09 Sent To  
Notes
2003-02-13 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02120927
 ADDRESS: 121 LINDA LANE
 CONT: JAMES COLE
 TELL # (561) 833-8401
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 ******PROVISO******
 1) SHEET A-2 BUCKET FOR GIRDERS NOT
 IDENTIFIED! THIS INFORMATION TO BE
 RECEIVED, AFTER ARCHITECT REVIEWS THE
 TRUSS ENGINEERING AND LOADS ARE IDENTIFI
 ED. ARCHITECT WILL SPECIFY BUCKET BEFORE
 FRAMING INSPECTION.
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-01-31 Cont ID  
Sent By pschmitz Date 2003-02-13 Time 08:49 Rev Time 1.25
Received By jwitmer Date 2003-01-31 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-10 Cont ID  
Sent By jwitmer Date 2003-01-10 Time 07:03 Rev Time 2.25
Received By jwitmer Date 2003-01-10 Time 07:03 Sent To  
Notes
2003-01-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120927
 ADD: 121 LINDA LANE
 CONT: JAMES C. COLE
 TEL: (561)833-8401
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)1804.1.3 THE BOTTOM OF THE FOUNDA-
 TION SHALL EXTEND NO LESS THAN 12"
 BELOW FINISH GRADE. THE GARAGE SLAB AND
 FOUNDATION INDICATES OVERALL 12" NOT 16"
  
 2) GARAGE COLUMNS MISSING INFO, NO "C-1"
 INFORMATION, WHAT SIZE DOWELS LENGHT OR
 LAP? TIE TO EXISTING BUILDING?
  
 3) GARAGE MISSING BEAM SCHEDULE, MASAON-
 ARY WALLS & BEAM SIZE OVER GARAGE DOOR.
 TIE TO EXISTING BUILDING?
  
 4) THE DESIGN OF THE GARAGE ROOF TRUSSES
 DOES NOT INDICATE 7'-0" SETBACK FOR GIR-
 DERS, LAYOUT INCORRECT, GIVE UPLIFT IN
 LBS. & REQUIRED ANCHORS.1606.2.4.
 MAIN FORCE RESISTING SYSTEM
  
 5) 1606.2.5 COMPOANTS & CLADDING, INDI-
 CATE WALL PRESSURE ZONES POS & NEG OPEN-
 ING PRESSURES, ELEVATION SECTIOIN PLEASE
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) SINGLE HUNG WINDOWS
 B) MULLIONS
 C) LAUNDRY WINDOW- NOT LISTED IN
 SCHEDULE?
  
 7) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 7)1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
  
 8)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11) ADDITIONAL INFORMATION, NEW STAIRS,
 MISSING BEARING WALL- CUT CEILING JOIST
 OR TRUSSES NO DETAILS!!!!!SHEET A-6 WALL
 SECTION FOR 2 STORY INCORRECT, PLAN INDI
 CATES 2ND STORY CANTILEVERED OVER 8"
 CMU WALL APPROX. 30". SHEET A-3 EXTEND
 8" CMU WALL TO BE INLINE WITH STAIRWELL
 THE DIMENSION REQUIRED FOR 2ND STORY
 FRAME WALL TO EXT. OF EXISTING BLOCK
 WALL IS APPROX 5'-0"? THIS SAME DETAIL
 SHOWS FLOOR LOADING 2ND FLOOR WITH A
 8'-6" CASEMENT WINDOW. WILL THE ADDITION
 AL LOADING OF THE EXISTING BEAM FIRST
 FLOOR TAKE THE ADDITIONAL LOADING? THIS
 BEAM WAS DESIGNED FOR THE LOADING OF THE
 CEILING JOIST AND ROOF FRAMING WITH
 LIMITATIONS (12'-0" OPENING FIRST FLOOR)
  
 12) SECOND STORY ROOF FRAMING DETAIL,
 INCORRECT LAYOUT, NOT INDICATING GIRDERS
 NOR UPLIFT LOADS? PLANS INDICATE "NEW"
 AWNING WINDOWS TO MATCH EXISTING 1ST FL.
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY. REVIEW TIE DOWN CONNECTION
 PLANS INDICATE USAGE OF SIMPSON SP22 THE
 CATOLOG DOESN'T INDICATE THIS AS A
 CURRENT PRODUCT. SHOW CONTINOUS PATH OF
 RESITANCE FROM EXISTING BEAM. SHOW
 CONTINIOUS PATH ON NEW BEARING WALL @
 STAIRWELL. ALSO NEW FOOTER FOR BEARING
 WALL?
  
 13) SHOW STAIRWELL CONSTRUCTION, RISE &
 RUN 1007.3.
  
 14)1007.8.1 WINDERS SHALL HAVE A
 MINIMUM TREAD DEPTH OF 6" AT THE NARROW-
 EST EDGE & SHALL HAVE A MINIMUM TREAD
 DEPTH OF 11" AT A POINT 12" FROM THE
 NARROW EDGE. WINDERS SHALL BE PERMITTED
 TO BE USED AS A COMPONENT IN MEANS OF
 EGRESS WITHIN A DWELLING UNIT.
  
 15)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 16) 2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS. IN FLOOR/CEIL/
 ING ASSEMBLIES SEPERATING USEABLE SPACE
 INTO 2 OR MORE APPROXIMATE AREAS WITH NO
 AREA GREATER THAN 500 SQ FT. DRAFTSTOP-
 PING SHALL BE PROVIDED PARALLEL TO THE
 MAIN FRAMING MEMBERS.
  
 17)TABLE 2306.1 PALM BEACH COUNTY
 AMENDMENTS
 ROOF SHEATHING NAILING REQUIREMENTS
  
 ZONE 1 & 28D COMMON
 6" EDGES & 6" INTERMEDIATES
  
 ZONE 38DCOMMON
 4" EDGES & 6" INTERMEDIATES
  
 18)FL BLD CODE 2309.6 ATTIC ACCESS, PRO-
 VIDE ATTIC ACCESS 20"X36".
  
 19)FL BLD CODE 2405.2 HAZARDOUS LOCATION
 PROVIDE SAFETY GLASS FOR THIS LOCATION:
 MASTER BATH TUB.
  
 20)2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR. INDICATE WHICH WINDOWS
 SHALL BE EGRESS WINDOWS.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-30 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 13:19 Rev Time 0.50
Received By btrobaug Date 2002-12-30 Time 18:06 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-22 Cont ID  
Sent By btrobaug Date 2003-01-22 Time 18:03 Rev Time 0.00
Received By btrobaug Date 2003-01-21 Time 18:03 Sent To P
Notes
2003-01-22 00:00:00"P" IN BOX./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-23 Cont ID  
Sent By dpalmer Date 2002-12-23 Time 13:18 Rev Time 0.00
Received By dpalmer Date 2002-12-23 Time 13:18 Sent To E
Notes
2002-12-23 00:00:00TO ELE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-16 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 17:02 Rev Time 0.00
Received By btrobaug Date 2002-12-16 Time 17:02 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-31 Cont ID  
Sent By pkrauss Date 2003-01-31 Time 09:40 Rev Time 0.30
Received By pkrauss Date 2003-01-31 Time 09:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-04 Cont ID  
Sent By kstevens Date 2003-01-23 Time 13:10 Rev Time 0.50
Received By hmoser Date 2003-01-04 Time 07:08 Sent To P
Notes
2003-01-04 00:00:00PLAN DENIED
 1) NO DUCT SIZE ON PLAN
 2) NO DUCT TO RETURN AIR GRILL ON PLAN
 3) NEED EXHAUST FAN IN NEW MASTER BATH
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By pschmitz Date 2003-02-13 Time 08:49 Rev Time 0.50
Received By pschmitz Date   Time   Sent To B
Notes
2003-02-13 00:00:00REVISION, APPR. PES

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-01-23 Cont ID  
Sent By kstevens Date 2003-01-23 Time 12:10 Rev Time 0.25
Received By kstevens Date 2003-01-23 Time 12:09 Sent To M
Notes
2003-01-23 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SHT M-1 SANITARY RISER DOES NOT MEET
 CODE. BATHROOM FROM SECOND FLOOR SHALL
 NOT DRAIN PAST VENT FOR BATHROOM ON
 FIRST FLOOR. SEPARATE SOIL STACK IS RE-
 QUIRED FOR SECOND FLOOR RESTROOM, AND
 SHALL TIE IN DOWNSTREAM OF FIRST FLOOR
 BATHROOM. SEE ATTACHED SHEET FOR EXAMPLE
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-01-07 Cont ID  
Sent By btrobaug Date 2003-01-22 Time 18:03 Rev Time 0.25
Received By kstevens Date 2003-01-07 Time 17:42 Sent To R
Notes
2003-01-07 00:00:00NO PLUMBING PLAN SUBMITTED - SEPARATE
 PERMIT REQUIRED FOR IRRIGATION.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2003-01-10 Cont ID  
Sent By kstevens Date 2003-01-07 Time 17:43 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 17:03 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
***NONE***