| Plan Review Stops For Permit 02120897 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-20 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-03-20 |
Time |
08:08 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-03-20 00:00:00 | **************PROVISO************* | | | | | | 1. SUBMIT CURRECT COPIES OF PRODUCTT | | | APPROVALS FOR THE ROOF TILE & EXTERIOR | | | OUTSWING DOORS.(SUBMITTED COPIES ARE | | | EXPIRED. | | | 2. MECHANICAL CONTRACTOR TO APPLY FOR | | | PERMIT SEPARATELY WITH DRAWINGS. | | | | | | | | | ANY QUSTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2003-01-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-03-19 |
Time |
07:08 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-10-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-08 |
Time |
19:25 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-10-08 |
Time |
19:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-07 |
Time |
10:52 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-09-26 |
Time |
05:57 |
Sent To |
P |
|
| Notes |
| 2003-09-26 00:00:00 | ************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE THAT ALL SEALS BY AN | | | ARCH/ENGINEER MUST BE A RAISED SEALED | | | AND MUST BE CLEAR AND VISABLE. | | | FS. 471.025/481.221 | | | | | | 2)NOTE: PLEASE ALSO NOTE,IF HAND WRITTEN | | | CHANGES ARE DRAWN ON PLANS, EACH CHANGE/ | | | LOCATION MUST BE INITIALED AND DATED | | | BY THE ENGINEER/OR ARCH OF RECORD. | | | | | | | | | PLEASE NOTE: DUE TO THE DELETION OF DOOR | | | PLANS ARE BEING SENT TO BLDG REVIEW. | | | BLDG SHEET MAY ALSO NEED TO BE CHANGED | | | TO REFLECT CHANGE? | | | | | | PLEASE SEEE THAT IT APPEARS THAT KITCHEN | | | SINK IS CROSSED OUT? IS THERE ARE NEW | | | LOCATION? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-03-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-23 |
Time |
16:13 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-03-19 |
Time |
07:08 |
Sent To |
B |
|
| Notes |
| 2003-03-19 00:00:00 | | | | PLANS SENT TO L MARTINEZ. | | | TWO SETS OF PRODUCT APPROVALS ARE | | | EXPIRED. 12/2/02 | | | PLANS NEED TO HAVE RADON FEES FIGURED | | | AND ATTACHED. | | | PLANS NEED TO GO TO PALM BEACH COUNTY | | | FOR IMPACT FEES TO BE PAID. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-01-06 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-17 |
Time |
11:11 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-01-06 |
Time |
17:59 |
Sent To |
M |
|
| Notes |
| 2003-01-06 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLANS MENTION NEW ELECTRICAL | | | PANEL IN GARAGE, PLEASE CLARIFY SIZE, | | | CONDUCTOR CONDUITS ETC. PLEASE SUBMIT | | | A RISER DIAGRAM. PLEASE ALSO IF CONDUCT- | | | -ORS ARE OVERHEAD, THEN NO MORETHAN 8' | | | OF UNPROTECTED CONDUCTORS ARE PERMITTED | | | "INSIDE" BLDG. PLEASE NOTE, A MAIN WOULD | | | BE REQ`D OUTSIDE. PLEASE SHOW GROUNDING | | | ELECTRODE SYSTEM BONDING OF NEW FOOTER | | | STEEL. ABOVE PER 250-50/215-5/210-70, | | | 225-31 | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ANY NEW SERVICE EQUIPMENT BEING INSTALL- | | | -ED PER 110-9. | | | | | | 3)NOTE: PLEASE CLARIFY NEW OR EXSITING | | | REQ`D EGRESS LIGHTING FROM KITCHEN TO | | | REAR OF HOUSE. PER 210-70 | | | | | | 4)NOTE:PLEASE CLARFIY NEW OR EXISTING | | | WASHER/DRYER/WATERHEATER IN GARAGE? | | | ELECTRIC OR GAS? | | | | | | 5)NOTE: PLEASE NOTE, ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE ARE TO BE SHOWN AS | | | GFI/GFI PROTECTED PER 210-8-A-6. | | | | | | 6)NOTE: PLEASE LIST NEW CIRCUITS ON | | | SUBMITTED PANEL SCHEDULE AND NOTE | | | 210-52D/210-11-C-3 FOR REQ`D BATH #12, | | | 20A CIRCUIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-10-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-07 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-07 |
Time |
10:31 |
Sent To |
P |
|
| Notes |
| 2003-10-07 00:00:00 | TO KS DESK/2ND REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-09-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-23 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-23 |
Time |
16:13 |
Sent To |
E |
|
| Notes |
| 2003-09-23 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-03-17 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-17 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-17 |
Time |
11:11 |
Sent To |
E |
|
| Notes |
| 2003-03-17 00:00:00 | TO DP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-01-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-06 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-01-06 |
Time |
17:44 |
Sent To |
E |
|
| Notes |
| 2003-01-06 00:00:00 | RECEIVED FROM DEAN RUNNELS TO DV PALMER` | | | S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-31 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-12-31 |
Time |
11:31 |
Sent To |
E |
|
| Notes |
| 2002-12-31 00:00:00 | TO DV P'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-13 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-13 |
Time |
18:22 |
Sent To |
P |
|
| Notes |
| 2002-12-13 00:00:00 | TO"P" IN BOX./WRT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-01-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-06 |
Time |
17:59 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2003-01-07 |
Time |
08:47 |
Sent To |
B |
|
| Notes |
| 2003-01-07 00:00:00 | NO MECHANICAL INFORMATION SUBMITTED. | | | PLANS DO NOT INDICATE THAT THE REMODEL | | | WILL HAVE ANY IMPACT ON THE EXISTING | | | A/C SYSTEM.NO ADDITIONAL SQUARE | | | FOOTAGE ADDED TO THE CONDITIONED SPACE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-10-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-07 |
Time |
10:52 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-10-07 |
Time |
10:52 |
Sent To |
E |
|
| Notes |
| 2003-10-07 00:00:00 | NO PLUMBING ISOMETRIC SUBMITTED. - MOVED | | | KIT SINK AND W/M- OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-07 |
Time |
10:32 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-10-02 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2003-10-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA STATUTES. | | | | | | 1) SHEETS E-1 AND 4, IT APPEARS THAT | | | THE KITCHEN SINK IS BEING DELETED. KIT. | | | SINK REQUIRED PER TABLE 403.1. PLEASE | | | SHOW WHERE KITCHEN SINK WILL BE IF MOVED | | | 2) SHEET 4 INDICATES THAT THE WASH MACH- | | | INE AND SINK IN LAUNDRY ROOM WILL BE | | | MOVED. PLEASE SHOW WHERE THESE WILL BE | | | MOVED TO. | | | 3) ALL CHANGES TO A SIGNED AND SEALED | | | SET OF PLANS SHALL BE SIGNED AND DATED | | | BY THE ARCHITECT OF RECORD. | | | 4) PER FS ALL SEALS BY AN ARCHICTECT | | | SHALL BE RAISED AND MUST BE CLEAR AND | | | VISABLE. FS 481.221 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-12-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-09-26 |
Time |
05:57 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-12-21 |
Time |
05:05 |
Sent To |
Z |
|
| Notes |
| 2002-12-21 00:00:00 | PASSED/PROVISO | | | | | | MINIMUM 2" PIPE UNDERGROUND (710.3) - NO | | | RISER FOR KITCHEN |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-12-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-21 |
Time |
05:06 |
Rev Time |
5.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|