Plan Review Details - Permit 02120892
Plan Review Stops For Permit 02120892
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-01-09 Cont ID  
Sent By rbrown Date 2004-01-09 Time 16:02 Rev Time 0.00
Received By rbrown Date 2004-01-09 Time 16:02 Sent To  
Notes
2004-01-09 00:00:00BUILDING PLAN REVIEW
 **REVISION DENIED**
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 11-4.1.3(11)SHOWER.ADDRESS
 PLUMBING PLAN REVIEW (12/13/02) COMMENT
 ABOUT ACCESSIBLE SHOWER PROVISION.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-12-03 Cont ID  
Sent By rbrown Date 2003-12-03 Time 15:58 Rev Time 0.00
Received By rbrown Date 2003-12-03 Time 15:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-08-08 Cont ID  
Sent By rbrown Date 2003-08-08 Time 12:16 Rev Time 0.00
Received By rbrown Date 2003-08-08 Time 12:16 Sent To  
Notes
2003-08-08 00:00:00REVISION SUBMITTED 8/7/03 FOR ADDITIONAL
 WINDOWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-07-10 Cont ID  
Sent By alange Date 2003-08-07 Time 15:04 Rev Time 0.00
Received By rbrown Date 2003-07-10 Time 19:12 Sent To  
Notes
2003-07-10 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED 6/27/03
  
 --PROVISO--
 FBC 1606.1.7THE WIND LOAD DESIGN
 PARAMETERS HAVE BEEN UNINTENTIALLY
 OMITTED FROM THIS 6/20/03 REVISION OF
 SHEET 5.FOR THIS INFORMATION REFER TO
 THE 1/30/03 REVISION.DO NOT DISCARD
 THE 1/30/03 REVISION OF SHEET 5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-05-01 Cont ID  
Sent By rbrown Date 2003-04-14 Time 16:58 Rev Time 0.00
Received By rbrown Date 2003-04-14 Time 16:58 Sent To  
Notes
2003-05-01 00:00:00PROVISO HAS BEEN MET:
 APPLICATION FOR UNDERGROUND UTILITIES
 AND CIVIL/SITE WORKS PERMIT NOW RECEIVED
 (PERMIT #03042760)
2003-04-14 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 NOTE: SEE ATTACHED ENGINEERING REVIEW
 COMMENT SHEET.THE BUILDING PERMIT CAN
 BE ISSUED ONLY AFTER THE REQUIRED
 SEPARATE PERMIT APPLICATION FOR
 UNDERGROUND UTILITIES AND CIVIL/SITE
 WORKS IS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-02-21 Cont ID  
Sent By rbrown Date 2003-02-20 Time 17:18 Rev Time 0.00
Received By rbrown Date 2003-02-20 Time 17:18 Sent To  
Notes
2003-02-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/23/03:
  
 4) FBC TABLE 500FROM THE AREAS GIVEN
 ON SHEET 1, THE PRINCIPLE INTENDED USE
 (REF: FBC 303.2) IS WAREHOUSE.SHEET 1
 DECLARES THE BUILDING AS TYPE IV
 UNPROTECTED WITH NO SPRINKLERS. FOR THIS
 CONSTRUCTION TYPE AND BUILDING OCCUPANCY
 TABLE 500 LIMITS THE ALLOWABLE AREA TO
 16000 SQFT.THE PROPOSED AREA EXCEEDS
 THIS AMOUNT.AMEND THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 6) FBC 1004.2.1TWO INDEPENDENT EXITS
 REQUIRED. THE ADDITION OF A SECOND STAIR
 FROM THE 'STORAGE LOFT', AS REQUIRED BY
 THE PREVIOUS REVIEW, IS NOTED.BOTH
 STAIRS DISCHARGE INTO THE WAREHOUSE
 FLOOR AREA AND CANNOT THEREFOR BE
 CONSIDERED INDEPENDENT EXITS.EXIT IS
 DEFINED IN FBC 202 AS BEING 'SEPARATED
 FROM ALL OTHER SPACES'.A SECOND
 INDEPENDENT MEANS OF EGRESS IS REQUIRED
 FROM THE 'STORAGE LOFT'. AMEND THE
 PLANS.PLEASE NOTE THAT 553.80(2)(B) FS
 (FLORIDA STATUTES) REQUIRES THAT LOCAL
 GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE PERMIT FEE IF PLANS ARE
 REJECTED THREE OR MORE TIMES FOR FAILURE
 TO CORRECT A CODE VIOLATION.THIS IS
 THE SECOND SUCH REVIEW.
  
 8) PROVISO:
 SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED ROOFING.
  
 9) PROVISO:
 ROLL-UP DOOR PRODUCT APPROVAL.SUBMIT
 A PRODUCT APPROVAL APPLICABLE TO THE
 SIZE OF THE PROPOSED ROLL-UP DOOR.THE
 SUBMITTED PRODUCT APPROVAL
 NOA# 00-0508.1 DOES NOT COVER THE DOOR
 WIDTH SHOWN ON THE PLANS.
  
 10) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-23 Cont ID  
Sent By sgraham Date 2003-01-02 Time 14:19 Rev Time 0.00
Received By rbrown Date 2003-01-23 Time 08:54 Sent To  
Notes
2003-01-23 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES.)
  
 2) FBC* 104.1.1DUMPSTER.A SEPARATE
 PERMIT APPLICATION WILL BE REQUIRED FOR
 THE DETACHED DUMPSTER ENCLOSURE.
  
 3) FBC* 104.1.1AWNINGS.A SEPARATE
 PERMIT APPLICATION WILL BE REQUIRED FOR
 THE INSTALLATION OF THE VINYL AWNINGS.
  
 4) FBC T500 AND T600THE PLANS SHALL
 STATE WHETHER THE BUILDING IS
 SPRINKLERED OR UNSPRINKLERED.
  
 5) FBC 704.3TENANT SEPARATION WALLS.
 THE PLANS SHALL BE AMENDED TO STATE THE
 1-HOUR FIRE RATING REQUIREMENT FOR THE
 TENANT FIRE SEPARATION WALLS AT THE
 TOILETS AND 'FUTURE PARTITION' LOCATIONS
  
 6) FBC 1027.1.1NUMBER OF EXITS FROM
 THE STORAGE LOFT.THE 'LOFT' DOES NOT
 MEET THE FBC 503.2.3.2 REQUIREMENTS FOR
 A MEZZANINE, AND SO MUST BE CONSIDERED
 AS A SECOND STORY.A SINGLE EXIT IS
 ONLY PERMITTED IN A STORAGE OCCUPANCY
 WITH A MAXIMUM OF ONE STORY.A SECOND
 MEANS OF EGRESS IS REQUIRED FROM THE
 STORAGE LOFT.
  
 7) SHEET 8, SECTION 1.STORAGE LOFT
 FLOOR.THE STATED LISTING NUMBER
 'UL 501' DOES NOT APPEAR TO BE A VALID
 LISTING.SHOULD THIS BE 'UL# L501'?
 AMEND THE PLANS AS NECESSARY.
  
 8) SUBMIT A PRODUCT APPROVAL FOR THE
 PROPOSED ROOFING.
  
 9) ROLL-UP DOOR PRODUCT APPROVAL.THE
 DOOR ELEVATIONS ON PLAN SHEET #2,
 SPECIFY A 16'-0" WIDE DOOR.THIS WIDTH
 APPEARS TO BE OUTSIDE THE SCOPE OF THE
 SUBMITTED ROLL-UP DOOR PRODUCT APPROVAL
 NOA# 00-0508.1.THE PRODUCT APPROVAL
 DRAWING SHEETS ARE NOT COMPLETELY
 LEGIBLE BUT THE PLAN VIEW ON SHEET 1
 SHOWS A MAXIMUM DOOR WIDTH WHICH IS LESS
 THAN 16'-0".SUBMIT AN APPROPRIATE
 PRODUCT APPROVAL OR REVISE THE PLANS
 ACCORDINGLY.
  
 10) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2003-12-22 Cont ID  
Sent By dpalmer Date 2003-12-22 Time 07:46 Rev Time 0.50
Received By dpalmer Date 2003-12-22 Time 07:46 Sent To  
Notes
2003-12-22 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SEE COMMENTS FROM
 PREVIOUS REVIEW.
 SAME COMMENTS.
  
 2)NOTE: PLEASE SEE ATTACHED COPY OF FS
 553.80(2)(B). PLANS COMING BACK W/ SAME
 COMMENTS.NEXT REVIEW WILL BE THIRD
 REVIEW W/ SAME COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-11-04 Cont ID  
Sent By dpalmer Date 2003-11-04 Time 07:23 Rev Time 0.50
Received By dpalmer Date 2003-11-04 Time 07:23 Sent To  
Notes
2003-11-04 00:00:00************* UNSAT *******************
  
 PLEASE SEE THE FOLLOWING STATEMENT FOR
 EXPLANATION OF "F" STATUS.
  
 1)NOTE: PLANS/REVISION DATED 6/20/03
 CAME IN FOR REVIEW. PLANS CONTAINED THE
 TITLE BLOCK FOR THE ENGINEER OF RECORD,
 HOWEVER THEY WERE NOT SIGNED, DATED AND
 SEALED BY THE ENGINEER. PER FS 471.025,
 AND FAC 61G15-23.002
 REVISED ELECTRICAL PLAN IS NOW COMING
 IN DATED 10/15/03. PLEASE SEE THAT
 THE ORIGINAL REVOF 6/20/03 IS NOW SIGNED
 AND SEALED, HOWEVER THIS REV DOES NOT
 CORRELATE WITH NEW REV OF 10/15/03.
 PANEL "P" ETC.
  
 PLEASE TAKE OUT ALL OLD/VOIDED SHEETS,
 SUBMIT COMPLETE ELECTRICAL REVISIONS TO
 LAST REVISED SET, HAVE PLANS SIGNED,DATE
 -D AND SEALED BY THE ORIGINAL ENGINEER
 OF RECORD(CHANE ENG) AND SUBMIT FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-07-17 Cont ID  
Sent By dpalmer Date 2003-07-17 Time 15:19 Rev Time 0.50
Received By dpalmer Date 2003-07-17 Time 15:19 Sent To  
Notes
2003-07-17 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE HAVEPLANS SIGNED,DATED
 AND SEALED BY ENGINEER OF RECORD.
 REQ'D UNDER FS 471
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-03-27 Cont ID  
Sent By shernand Date 2003-07-16 Time 16:42 Rev Time 0.33
Received By dpalmer Date 2003-03-27 Time 05:54 Sent To  
Notes
2003-03-27 00:00:00REVISED ELEC SHEET.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-24 Cont ID  
Sent By dpalmer Date 2003-02-24 Time 06:08 Rev Time 0.25
Received By dpalmer Date 2003-02-24 Time 06:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By dpalmer Date 2003-01-13 Time 10:12 Rev Time 1.00
Received By dpalmer Date 2003-01-13 Time 10:12 Sent To  
Notes
2003-01-13 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, PER FS/FAC 61G15-23
 .002. PLANS THAT ARE SIGNED AND SEALED
 BY AN ENGINEER MUST HAVE A TITLE BLOCK
 CONTAINING ALL INFORMATION AS SET FORTH
 IN FS.
  
 2)NOTE: PLEASE SEE FIRE REVIEW NOTES FOR
 EMERGENCY LIGHTING. PLEASE ALSO SEE
 700-12E FOR CIRCUTING OF EXT AND EM LTS.
  
 3)NOTE: PLEASE SEE 600-5 FOR REQ`D SIGN
 CIRCUIT.
  
 4)NOTE: PLEASE CLARFIY EGRESS LIGHTING
 FOR STAIRWAY.
  
 5)NOTE: PLEASE CLARIFY VOLTAGE, PANELS
 SHOW 120/208V AND YET RISER SHOWS A
 HIGH LEG? Y OR DELTA SYSTEM?
  
 6)NOTE: PLEASE CLARIFY EQUIPMENT GROUND-
 ING METHOD BETWEEN MAIN DISC/GUTTER AND
 PANELS P/T. SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2003-05-01 Cont ID  
Sent By mamini Date 2003-05-01 Time 10:13 Rev Time 1.00
Received By mamini Date 2003-05-01 Time 10:12 Sent To  
Notes
2003-05-01 00:00:00PASSED:
 1. SEE PERMIT # 03042760 FOR UNDERGROUND
 UTILITIES AND SITE WORK .
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2003-03-24 Cont ID  
Sent By mamini Date 2003-03-24 Time 10:59 Rev Time 1.00
Received By mamini Date 2003-03-24 Time 10:59 Sent To  
Notes
2003-03-24 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND CIVIL/ SITE WORKS WILL BE
 REQUIRED.PLEASE SUBMIT TWO SETS OF
 CIVIL PLANS ONLY, SIGNED & SEALED.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-02-24 Cont ID  
Sent By mamini Date 2003-02-24 Time 09:40 Rev Time 1.00
Received By mamini Date 2003-02-24 Time 09:40 Sent To  
Notes
2003-02-24 00:00:00FAILED:
 1. CIVIL SITE PLANS PD-1 AND PD-2 BY
 WALLACE CIVIL ENGINEERS, NOT INCLUDED
 IN 2ND SUBMITTAL.
 2. PLEASE REFER TO THE PREVIOUS PLAN
 REVIEW COMMENTS DATED 01-07-03.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-01-07 Cont ID  
Sent By mamini Date 2003-01-07 Time 13:47 Rev Time 2.00
Received By mamini Date 2003-01-07 Time 13:47 Sent To  
Notes
2003-01-07 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPICATION AND FEES FOR UNDERGROUND
 UTILITIES AND CIVIL SITE WORKS WIIL BE
 REQUIRED.
 2. SIDEWALK, CURB AND GUTTERS AS
 REQUIRED BY THE PLANNING DEPARTMENT (SEE
 ATTACHED LETTER) AROUND THE PROPERTY,
 MUST BE SHOWN, PLEASE COORDINATE WITH
 CITY ENGINEER'S OFFICE FOR THE
 REQUIREMENTS. 659-8040 MR. RICHARD
 PITTMAN.
 3. ALL DRIVEWAYS MUST BE CONSTRUCTED PER
 CITY' STANDARDS AND RQUIREMENTS.
 4. A CLEAN OUT MUST BE INSTALLED IN
 SEWER LATERALS IF ONE IS NOT THERE, IT
 SHALL BE THE RESPONSIBILITY OF THE
 DEVELOPER/ENGINEER/DEVELOPER TO DESIGN
 AND INSTALL THE NEW INVERT ELEVATION FOR
 THE BUILDING LATERAL TO MACH OR BE
 HIGHER THAN THE EXISTING WHILE MAINTAIN-
 ING THE PLUMBING CODE REQUIREMENT FOR
 EFFLUENT PIPE FALL WITH MINIMUM OF THREE
 FEET COVER. IF THESE REQUIREMENTS CAN NO
 T BE MET, THE CITY MUST BE NOTIFIED
 PRIOR TO INSTALLATION.659-8040, 659-8079
 5. ALL BACKFLOW PREVENTERS AND
 CONNECTIONS TO CITY SERVICES MUST BE
 APPROVED BY PUBLIC UTILITIES ENGINEERING
 SERVICES DEPT. 659-8040 MR. MANNY
 GONZALEZ.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-11-13 Cont ID  
Sent By mcarsill Date 2003-11-13 Time 07:05 Rev Time 0.00
Received By mcarsill Date 2003-11-13 Time 07:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-07-15 Cont ID  
Sent By nmccray Date 2003-07-15 Time 15:16 Rev Time 0.00
Received By nmccray Date 2003-07-15 Time 15:16 Sent To  
Notes
2003-07-15 00:00:00REVISION 6-27-03 NAM

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-03-28 Cont ID  
Sent By mcarsill Date 2003-03-28 Time 10:33 Rev Time 0.00
Received By mcarsill Date 2003-03-28 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-02-21 Cont ID  
Sent By mcarsill Date 2003-02-13 Time 13:35 Rev Time 0.00
Received By mcarsill Date 2003-02-13 Time 13:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-01-03 Cont ID  
Sent By mcarsill Date 2003-01-03 Time 15:28 Rev Time 0.00
Received By mcarsill Date 2003-01-03 Time 15:28 Sent To  
Notes
2003-01-03 00:00:001) PLEASE INDICATE LOCATIONS OF ANY
 EXISTING FIRE HYDRANTS IN THE VICINITY
 OF THE BUILDING.
  
 2) HOW IS FIRE AND PARAMEDICAL EQUIPMENT
 EXPECTED TO USE THE NEW GATES. ARE THE
 NEW GATES ELECTRIC OR MANUAL.
  
 3) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION.
  
 4) PLEASE INDICATE LOCATIONS OF
 EMERGENCY LIGHTING EQUIPMENT WITHIN
 TENANT SPACE.
  
 5) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 6) WHAT IS THE SEPARATION BETWEEN THE
 WAREHOUSE AND OFFICE AREA.
  
 7) PLEASE EXPLAIN SINGLE EXIT THEORY
 FROM SECOND LEVEL STORAGE AREA.
  
 8) WHAT WILL THE PRINCIPAL USE OF THE
 SEVEN RENTAL UNITS.
  
 9) PLEASE INDICATE CONSTRUCTION TYPE
 FOR THE BUILDING.
  
 10) PLEASE EXPLAIN HOW THE GLASS
 SPECIALITIES AREA BE USED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2003-12-09 Cont ID  
Sent By csiegber Date 2003-12-09 Time 15:15 Rev Time 0.00
Received By csiegber Date 2003-12-09 Time 15:15 Sent To  
Notes
2003-12-09 00:00:00TO COMM BD#23

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-11-03 Cont ID  
Sent By csiegber Date 2003-11-03 Time 12:56 Rev Time 0.00
Received By csiegber Date 2003-11-03 Time 12:56 Sent To  
Notes
2003-11-03 00:00:00TO COMM BD#33

Review Stop I INCOMING/PROCESSING
Rev No 8 Status   Date 2003-10-31 Cont ID  
Sent By lsmith Date 2003-10-31 Time 09:52 Rev Time 0.00
Received By lsmith Date 2003-10-31 Time 09:52 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-08-07 Cont ID  
Sent By alange Date 2003-08-07 Time 15:01 Rev Time 0.00
Received By alange Date 2003-08-07 Time 15:01 Sent To B
Notes
2003-08-07 00:00:00TO RBROWN DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-16 Cont ID  
Sent By shernand Date 2003-07-16 Time 16:41 Rev Time 0.00
Received By shernand Date 2003-07-16 Time 16:41 Sent To E
Notes
2003-07-16 00:00:00GAVE REVISION TO DP.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-07-08 Cont ID  
Sent By shernand Date 2003-07-08 Time 12:08 Rev Time 0.00
Received By shernand Date 2003-07-08 Time 12:08 Sent To  
Notes
2003-07-08 00:00:00COMM BOARD #51

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-27 Cont ID  
Sent By shernand Date 2003-06-27 Time 15:10 Rev Time 0.00
Received By shernand Date 2003-06-27 Time 15:10 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:43 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 08:43 Sent To  
Notes
2003-03-24 00:00:00TO COMM BOARD #61

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-12 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 16:47 Rev Time 0.00
Received By btrobaug Date 2003-02-10 Time 16:47 Sent To  
Notes
2003-02-12 00:00:00COM BOARD #3./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-20 Cont ID  
Sent By btrobaug Date 2002-12-20 Time 18:32 Rev Time 0.00
Received By btrobaug Date 2002-12-13 Time 18:33 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-12-11 Cont ID  
Sent By pkrauss Date 2003-12-11 Time 09:15 Rev Time 0.33
Received By pkrauss Date 2003-12-11 Time 09:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2003-12-02 Cont ID  
Sent By pkrauss Date 2003-12-02 Time 09:49 Rev Time 0.33
Received By pkrauss Date 2003-12-02 Time 09:48 Sent To  
Notes
2003-12-02 00:00:00PLANS SUBMITTED MUST BE SIGNED BY THE
 ENGINEER OF RECORD. PLANS SUBMITTED WITH
 MASTER 02120892

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-04-11 Cont ID  
Sent By lsmith Date 2003-10-31 Time 09:52 Rev Time 0.40
Received By pkrauss Date 2003-04-11 Time 15:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-24 Cont ID  
Sent By pkrauss Date 2003-02-24 Time 15:03 Rev Time 0.45
Received By pkrauss Date 2003-02-24 Time 14:58 Sent To  
Notes
2003-02-24 00:00:00PROVISO:
  
 PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPERS, ON
 THE JOBSITE FOR ROUGH INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-17 Cont ID  
Sent By pkrauss Date 2003-01-17 Time 16:29 Rev Time 0.50
Received By pkrauss Date 2003-01-17 Time 16:23 Sent To  
Notes
2003-01-17 00:00:00DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) TABLE 403.3 OR ASHRAE
 62-89.PROVIDE CALCS FOR ALL AREAS OF
 THE BUILDING.
  
 2.PROVIDE SUBMITTAL FOR THE FIRE
 DAMPERS SHOWN ON PLAN SHEET 13, ACCESS
 DOORS REQUIRED.
  
 3.AS PER 2001 FBC(M) 606.2.2, DUCT
 SMOKE DETECTORS REQUIRED.FAN SHUTDOWN
 BY DUCT SMOKE DETECTOR SHALL HAVE
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status F Date 2003-12-19 Cont ID  
Sent By kstevens Date 2003-12-19 Time 18:24 Rev Time 0.50
Received By kstevens Date 2003-12-19 Time 18:24 Sent To  
Notes
2003-12-19 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) SHT 3, NEW SHOWER STALL SHALL BE
 ACCESSIBLE PER SECTION 11-4.1.3(11),
 IF BATHING ROOMS ARE PROVIDED, THEN EACH
 PUBLIC AND COMMON USE BATHROOM SHALL
 COMPLY WITH 11-4.23. - SHOW COMPLIANCE
 WITH 11-4.21 SHOWER STALLS & FIG. 35B.
 SHOW SHOWER UNIT 11-4.21.6, & 11-4.21.7
 CURB. INDICATE THAT SHOWER WILL BE
 ACCESSIBLE NOT ADAPTABLE ON REVISION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-03 Cont ID  
Sent By kstevens Date 2003-07-03 Time 17:49 Rev Time 0.50
Received By kstevens Date 2003-07-03 Time 17:49 Sent To E
Notes
2003-07-03 00:00:00REVISION OK - ADDED ADA SHOWER - CHANGED
 FLOOR PLAN, WATER RISER & SANT. RISER
 DIAGRAMS

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-12 Cont ID  
Sent By shernand Date 2003-06-27 Time 15:10 Rev Time 0.50
Received By kstevens Date 2003-04-12 Time 06:43 Sent To  
Notes
2003-04-12 00:00:00PASSED/PROVISO
  
 HORIZONTAL STORM DRAIN SHALL BE 6" @ 2%
 WHEN SECOND DRAIN IS ADDED. SEE SHEET #7

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-03-05 Cont ID  
Sent By kstevens Date 2003-03-05 Time 17:13 Rev Time 0.75
Received By kstevens Date 2003-03-05 Time 17:12 Sent To  
Notes
2003-03-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 2 - MAXIMUM SQUARE FOOTAGE TO BE
 DRAINED ON 4" PIPE @ 2% IS 2355. BELOW
 ROOF AREA SHOWS 2434 SQUARE FEET BEING
 DRAINED ON HORIZONTAL PIPE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-11 Cont ID  
Sent By kstevens Date 2003-01-11 Time 06:56 Rev Time 1.25
Received By kstevens Date 2003-01-11 Time 06:55 Sent To  
Notes
2003-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED FOR EACH WAREHOUSE BAY. ALSO
 SEE SECTION 410.1
 2) SHT 7 PLEASE PROVIDE CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 AND 1107. ADD 1/2 AREA OF
 ALL VERTICAL WALLS. MAXIMUM OF 1600 SQ
 FT FOR HORIZONTAL 4" PIPE. SHOW TOTAL
 SQUARE FOOTAGE FOR ROOF AND TOTAL DRAIN-
 ING INTO EACH DRAIN.
 3) PLEASE PROVIDE A STORM RISER DIAGRAM.
 INDICATE PIPE SIZE AND SHOW ACCUMULATED
 SQ FT AT EACH RISER.
 4) SHT 13 THERMAL EXPANSION CONTROL IS
 REQUIRED. SECTION 607.3.2 PLEASE SHOW AN
 EXPANSION TANK AT WATER HEATER DETAIL.
 5) RPZ BACKFLOW REQUIRED ON WATER SERV-
 ICE.
 6) SHT 13 GENERAL MECHANICAL NOTE #10,
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 PROVIDE WATER HAMMER ARRESTORS REQUIRED
 IN SECTION 604.9
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-02 Cont ID  
Sent By btrobaug Date 2002-12-20 Time 18:32 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***