| Plan Review Stops For Permit 02120892 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2004-01-09 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-01-09 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-01-09 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2004-01-09 00:00:00 | BUILDING PLAN REVIEW | | | **REVISION DENIED** | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) FBC 11-4.1.3(11)SHOWER.ADDRESS | | | PLUMBING PLAN REVIEW (12/13/02) COMMENT | | | ABOUT ACCESSIBLE SHOWER PROVISION. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2003-12-03 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-12-03 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-12-03 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2003-08-08 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-08-08 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-08-08 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2003-08-08 00:00:00 | REVISION SUBMITTED 8/7/03 FOR ADDITIONAL | | | WINDOWS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-07-10 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-07 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-07-10 |
Time |
19:12 |
Sent To |
|
|
| Notes |
| 2003-07-10 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | REVISION SUBMITTED 6/27/03 | | | | | | --PROVISO-- | | | FBC 1606.1.7THE WIND LOAD DESIGN | | | PARAMETERS HAVE BEEN UNINTENTIALLY | | | OMITTED FROM THIS 6/20/03 REVISION OF | | | SHEET 5.FOR THIS INFORMATION REFER TO | | | THE 1/30/03 REVISION.DO NOT DISCARD | | | THE 1/30/03 REVISION OF SHEET 5. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2003-05-01 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-04-14 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-04-14 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2003-05-01 00:00:00 | PROVISO HAS BEEN MET: | | | APPLICATION FOR UNDERGROUND UTILITIES | | | AND CIVIL/SITE WORKS PERMIT NOW RECEIVED | | | (PERMIT #03042760) | | 2003-04-14 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | NOTE: SEE ATTACHED ENGINEERING REVIEW | | | COMMENT SHEET.THE BUILDING PERMIT CAN | | | BE ISSUED ONLY AFTER THE REQUIRED | | | SEPARATE PERMIT APPLICATION FOR | | | UNDERGROUND UTILITIES AND CIVIL/SITE | | | WORKS IS SUBMITTED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-02-21 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-02-20 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-02-20 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2003-02-20 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 1/23/03: | | | | | | 4) FBC TABLE 500FROM THE AREAS GIVEN | | | ON SHEET 1, THE PRINCIPLE INTENDED USE | | | (REF: FBC 303.2) IS WAREHOUSE.SHEET 1 | | | DECLARES THE BUILDING AS TYPE IV | | | UNPROTECTED WITH NO SPRINKLERS. FOR THIS | | | CONSTRUCTION TYPE AND BUILDING OCCUPANCY | | | TABLE 500 LIMITS THE ALLOWABLE AREA TO | | | 16000 SQFT.THE PROPOSED AREA EXCEEDS | | | THIS AMOUNT.AMEND THE PLANS TO | | | DEMONSTRATE COMPLIANCE. | | | | | | 6) FBC 1004.2.1TWO INDEPENDENT EXITS | | | REQUIRED. THE ADDITION OF A SECOND STAIR | | | FROM THE 'STORAGE LOFT', AS REQUIRED BY | | | THE PREVIOUS REVIEW, IS NOTED.BOTH | | | STAIRS DISCHARGE INTO THE WAREHOUSE | | | FLOOR AREA AND CANNOT THEREFOR BE | | | CONSIDERED INDEPENDENT EXITS.EXIT IS | | | DEFINED IN FBC 202 AS BEING 'SEPARATED | | | FROM ALL OTHER SPACES'.A SECOND | | | INDEPENDENT MEANS OF EGRESS IS REQUIRED | | | FROM THE 'STORAGE LOFT'. AMEND THE | | | PLANS.PLEASE NOTE THAT 553.80(2)(B) FS | | | (FLORIDA STATUTES) REQUIRES THAT LOCAL | | | GOVERNMENT SHALL IMPOSE A FEE OF FOUR | | | TIMES THE PERMIT FEE IF PLANS ARE | | | REJECTED THREE OR MORE TIMES FOR FAILURE | | | TO CORRECT A CODE VIOLATION.THIS IS | | | THE SECOND SUCH REVIEW. | | | | | | 8) PROVISO: | | | SUBMIT A PRODUCT APPROVAL FOR THE | | | PROPOSED ROOFING. | | | | | | 9) PROVISO: | | | ROLL-UP DOOR PRODUCT APPROVAL.SUBMIT | | | A PRODUCT APPROVAL APPLICABLE TO THE | | | SIZE OF THE PROPOSED ROLL-UP DOOR.THE | | | SUBMITTED PRODUCT APPROVAL | | | NOA# 00-0508.1 DOES NOT COVER THE DOOR | | | WIDTH SHOWN ON THE PLANS. | | | | | | 10) IF NEW PLAN SHEETS ARE REQUIRED, IN | | | ORDER TO ADDRESS THE ABOVE COMMENTS, THE | | | OLD SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHALL BE INCLUDED WITH THE | | | RESUBMITTAL FOR COMPARISON OF REVISIONS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-01-23 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2003-01-02 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-01-23 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2003-01-23 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) FBC* 104.2.4SITE SURVEY.A SIGNED | | | AND SEALED SURVEY DRAWING PREPARED BY A | | | QUALIFIED SURVEYOR IS REQUIRED (REF: | | | 472.025(1) FL. STATUTES.) | | | | | | 2) FBC* 104.1.1DUMPSTER.A SEPARATE | | | PERMIT APPLICATION WILL BE REQUIRED FOR | | | THE DETACHED DUMPSTER ENCLOSURE. | | | | | | 3) FBC* 104.1.1AWNINGS.A SEPARATE | | | PERMIT APPLICATION WILL BE REQUIRED FOR | | | THE INSTALLATION OF THE VINYL AWNINGS. | | | | | | 4) FBC T500 AND T600THE PLANS SHALL | | | STATE WHETHER THE BUILDING IS | | | SPRINKLERED OR UNSPRINKLERED. | | | | | | 5) FBC 704.3TENANT SEPARATION WALLS. | | | THE PLANS SHALL BE AMENDED TO STATE THE | | | 1-HOUR FIRE RATING REQUIREMENT FOR THE | | | TENANT FIRE SEPARATION WALLS AT THE | | | TOILETS AND 'FUTURE PARTITION' LOCATIONS | | | | | | 6) FBC 1027.1.1NUMBER OF EXITS FROM | | | THE STORAGE LOFT.THE 'LOFT' DOES NOT | | | MEET THE FBC 503.2.3.2 REQUIREMENTS FOR | | | A MEZZANINE, AND SO MUST BE CONSIDERED | | | AS A SECOND STORY.A SINGLE EXIT IS | | | ONLY PERMITTED IN A STORAGE OCCUPANCY | | | WITH A MAXIMUM OF ONE STORY.A SECOND | | | MEANS OF EGRESS IS REQUIRED FROM THE | | | STORAGE LOFT. | | | | | | 7) SHEET 8, SECTION 1.STORAGE LOFT | | | FLOOR.THE STATED LISTING NUMBER | | | 'UL 501' DOES NOT APPEAR TO BE A VALID | | | LISTING.SHOULD THIS BE 'UL# L501'? | | | AMEND THE PLANS AS NECESSARY. | | | | | | 8) SUBMIT A PRODUCT APPROVAL FOR THE | | | PROPOSED ROOFING. | | | | | | 9) ROLL-UP DOOR PRODUCT APPROVAL.THE | | | DOOR ELEVATIONS ON PLAN SHEET #2, | | | SPECIFY A 16'-0" WIDE DOOR.THIS WIDTH | | | APPEARS TO BE OUTSIDE THE SCOPE OF THE | | | SUBMITTED ROLL-UP DOOR PRODUCT APPROVAL | | | NOA# 00-0508.1.THE PRODUCT APPROVAL | | | DRAWING SHEETS ARE NOT COMPLETELY | | | LEGIBLE BUT THE PLAN VIEW ON SHEET 1 | | | SHOWS A MAXIMUM DOOR WIDTH WHICH IS LESS | | | THAN 16'-0".SUBMIT AN APPROPRIATE | | | PRODUCT APPROVAL OR REVISE THE PLANS | | | ACCORDINGLY. | | | | | | 10) IF NEW PLAN SHEETS ARE REQUIRED, IN | | | ORDER TO ADDRESS THE ABOVE COMMENTS, THE | | | OLD SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHALL BE INCLUDED WITH THE | | | RESUBMITTAL FOR COMPARISON OF REVISIONS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2003-12-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-12-22 |
Time |
07:46 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-12-22 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2003-12-22 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE COMMENTS FROM | | | PREVIOUS REVIEW. | | | SAME COMMENTS. | | | | | | 2)NOTE: PLEASE SEE ATTACHED COPY OF FS | | | 553.80(2)(B). PLANS COMING BACK W/ SAME | | | COMMENTS.NEXT REVIEW WILL BE THIRD | | | REVIEW W/ SAME COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected]. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2003-11-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-11-04 |
Time |
07:23 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-11-04 |
Time |
07:23 |
Sent To |
|
|
| Notes |
| 2003-11-04 00:00:00 | ************* UNSAT ******************* | | | | | | PLEASE SEE THE FOLLOWING STATEMENT FOR | | | EXPLANATION OF "F" STATUS. | | | | | | 1)NOTE: PLANS/REVISION DATED 6/20/03 | | | CAME IN FOR REVIEW. PLANS CONTAINED THE | | | TITLE BLOCK FOR THE ENGINEER OF RECORD, | | | HOWEVER THEY WERE NOT SIGNED, DATED AND | | | SEALED BY THE ENGINEER. PER FS 471.025, | | | AND FAC 61G15-23.002 | | | REVISED ELECTRICAL PLAN IS NOW COMING | | | IN DATED 10/15/03. PLEASE SEE THAT | | | THE ORIGINAL REVOF 6/20/03 IS NOW SIGNED | | | AND SEALED, HOWEVER THIS REV DOES NOT | | | CORRELATE WITH NEW REV OF 10/15/03. | | | PANEL "P" ETC. | | | | | | PLEASE TAKE OUT ALL OLD/VOIDED SHEETS, | | | SUBMIT COMPLETE ELECTRICAL REVISIONS TO | | | LAST REVISED SET, HAVE PLANS SIGNED,DATE | | | -D AND SEALED BY THE ORIGINAL ENGINEER | | | OF RECORD(CHANE ENG) AND SUBMIT FOR | | | REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-07-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-07-17 |
Time |
15:19 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-07-17 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2003-07-17 00:00:00 | ************** UNSAT ************** | | | | | | 1)NOTE: PLEASE HAVEPLANS SIGNED,DATED | | | AND SEALED BY ENGINEER OF RECORD. | | | REQ'D UNDER FS 471 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-03-27 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-16 |
Time |
16:42 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-03-27 |
Time |
05:54 |
Sent To |
|
|
| Notes |
| 2003-03-27 00:00:00 | REVISED ELEC SHEET. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-02-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-24 |
Time |
06:08 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-02-24 |
Time |
06:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-01-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-13 |
Time |
10:12 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-01-13 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2003-01-13 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, PER FS/FAC 61G15-23 | | | .002. PLANS THAT ARE SIGNED AND SEALED | | | BY AN ENGINEER MUST HAVE A TITLE BLOCK | | | CONTAINING ALL INFORMATION AS SET FORTH | | | IN FS. | | | | | | 2)NOTE: PLEASE SEE FIRE REVIEW NOTES FOR | | | EMERGENCY LIGHTING. PLEASE ALSO SEE | | | 700-12E FOR CIRCUTING OF EXT AND EM LTS. | | | | | | 3)NOTE: PLEASE SEE 600-5 FOR REQ`D SIGN | | | CIRCUIT. | | | | | | 4)NOTE: PLEASE CLARFIY EGRESS LIGHTING | | | FOR STAIRWAY. | | | | | | 5)NOTE: PLEASE CLARIFY VOLTAGE, PANELS | | | SHOW 120/208V AND YET RISER SHOWS A | | | HIGH LEG? Y OR DELTA SYSTEM? | | | | | | 6)NOTE: PLEASE CLARIFY EQUIPMENT GROUND- | | | ING METHOD BETWEEN MAIN DISC/GUTTER AND | | | PANELS P/T. SIZE PER 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2003-05-01 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-05-01 |
Time |
10:13 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-05-01 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2003-05-01 00:00:00 | PASSED: | | | 1. SEE PERMIT # 03042760 FOR UNDERGROUND | | | UTILITIES AND SITE WORK . | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-03-24 |
Time |
10:59 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-03-24 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2003-03-24 00:00:00 | FAILED: | | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | | APPLICATION AND FEES FOR UNDERGROUND | | | UTILITIES AND CIVIL/ SITE WORKS WILL BE | | | REQUIRED.PLEASE SUBMIT TWO SETS OF | | | CIVIL PLANS ONLY, SIGNED & SEALED. | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2003-02-24 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-02-24 |
Time |
09:40 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2003-02-24 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2003-02-24 00:00:00 | FAILED: | | | 1. CIVIL SITE PLANS PD-1 AND PD-2 BY | | | WALLACE CIVIL ENGINEERS, NOT INCLUDED | | | IN 2ND SUBMITTAL. | | | 2. PLEASE REFER TO THE PREVIOUS PLAN | | | REVIEW COMMENTS DATED 01-07-03. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2003-01-07 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2003-01-07 |
Time |
13:47 |
Rev Time |
2.00 |
| Received By |
mamini |
Date |
2003-01-07 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2003-01-07 00:00:00 | FAILED: | | | 1. PLEASE NOTE THAT A SEPARATE PERMIT | | | APPICATION AND FEES FOR UNDERGROUND | | | UTILITIES AND CIVIL SITE WORKS WIIL BE | | | REQUIRED. | | | 2. SIDEWALK, CURB AND GUTTERS AS | | | REQUIRED BY THE PLANNING DEPARTMENT (SEE | | | ATTACHED LETTER) AROUND THE PROPERTY, | | | MUST BE SHOWN, PLEASE COORDINATE WITH | | | CITY ENGINEER'S OFFICE FOR THE | | | REQUIREMENTS. 659-8040 MR. RICHARD | | | PITTMAN. | | | 3. ALL DRIVEWAYS MUST BE CONSTRUCTED PER | | | CITY' STANDARDS AND RQUIREMENTS. | | | 4. A CLEAN OUT MUST BE INSTALLED IN | | | SEWER LATERALS IF ONE IS NOT THERE, IT | | | SHALL BE THE RESPONSIBILITY OF THE | | | DEVELOPER/ENGINEER/DEVELOPER TO DESIGN | | | AND INSTALL THE NEW INVERT ELEVATION FOR | | | THE BUILDING LATERAL TO MACH OR BE | | | HIGHER THAN THE EXISTING WHILE MAINTAIN- | | | ING THE PLUMBING CODE REQUIREMENT FOR | | | EFFLUENT PIPE FALL WITH MINIMUM OF THREE | | | FEET COVER. IF THESE REQUIREMENTS CAN NO | | | T BE MET, THE CITY MUST BE NOTIFIED | | | PRIOR TO INSTALLATION.659-8040, 659-8079 | | | 5. ALL BACKFLOW PREVENTERS AND | | | CONNECTIONS TO CITY SERVICES MUST BE | | | APPROVED BY PUBLIC UTILITIES ENGINEERING | | | SERVICES DEPT. 659-8040 MR. MANNY | | | GONZALEZ. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2003-11-13 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-11-13 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-11-13 |
Time |
07:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2003-07-15 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-07-15 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-07-15 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2003-07-15 00:00:00 | REVISION 6-27-03 NAM |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-03-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-03-28 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-03-28 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2003-02-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-02-13 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-02-13 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-01-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-01-03 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-01-03 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2003-01-03 00:00:00 | 1) PLEASE INDICATE LOCATIONS OF ANY | | | EXISTING FIRE HYDRANTS IN THE VICINITY | | | OF THE BUILDING. | | | | | | 2) HOW IS FIRE AND PARAMEDICAL EQUIPMENT | | | EXPECTED TO USE THE NEW GATES. ARE THE | | | NEW GATES ELECTRIC OR MANUAL. | | | | | | 3) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION. | | | | | | 4) PLEASE INDICATE LOCATIONS OF | | | EMERGENCY LIGHTING EQUIPMENT WITHIN | | | TENANT SPACE. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 6) WHAT IS THE SEPARATION BETWEEN THE | | | WAREHOUSE AND OFFICE AREA. | | | | | | 7) PLEASE EXPLAIN SINGLE EXIT THEORY | | | FROM SECOND LEVEL STORAGE AREA. | | | | | | 8) WHAT WILL THE PRINCIPAL USE OF THE | | | SEVEN RENTAL UNITS. | | | | | | 9) PLEASE INDICATE CONSTRUCTION TYPE | | | FOR THE BUILDING. | | | | | | 10) PLEASE EXPLAIN HOW THE GLASS | | | SPECIALITIES AREA BE USED. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2003-12-09 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-09 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-09 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2003-12-09 00:00:00 | TO COMM BD#23 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2003-11-03 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-03 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-03 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2003-11-03 00:00:00 | TO COMM BD#33 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
|
Date |
2003-10-31 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-10-31 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
2003-10-31 |
Time |
09:52 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2003-08-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2003-08-07 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2003-08-07 |
Time |
15:01 |
Sent To |
B |
|
| Notes |
| 2003-08-07 00:00:00 | TO RBROWN DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-07-16 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-16 |
Time |
16:41 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-16 |
Time |
16:41 |
Sent To |
E |
|
| Notes |
| 2003-07-16 00:00:00 | GAVE REVISION TO DP. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-07-08 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-08 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-08 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2003-07-08 00:00:00 | COMM BOARD #51 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-06-27 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-27 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-06-27 |
Time |
15:10 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-24 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-24 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2003-03-24 00:00:00 | TO COMM BOARD #61 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-02-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-02-12 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-02-10 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2003-02-12 00:00:00 | COM BOARD #3./WRT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-20 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-13 |
Time |
18:33 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2003-12-11 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-11 |
Time |
09:15 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2003-12-11 |
Time |
09:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2003-12-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-02 |
Time |
09:49 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2003-12-02 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2003-12-02 00:00:00 | PLANS SUBMITTED MUST BE SIGNED BY THE | | | ENGINEER OF RECORD. PLANS SUBMITTED WITH | | | MASTER 02120892 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-10-31 |
Time |
09:52 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-04-11 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-02-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-24 |
Time |
15:03 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-02-24 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2003-02-24 00:00:00 | PROVISO: | | | | | | PROVIDE MANUFACTURERS INSTALLATION | | | INSTRUCTIONS FOR THE FIRE DAMPERS, ON | | | THE JOBSITE FOR ROUGH INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-17 |
Time |
16:29 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2003-01-17 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2003-01-17 00:00:00 | DENIED: | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | | PER 2001 FBC(M) TABLE 403.3 OR ASHRAE | | | 62-89.PROVIDE CALCS FOR ALL AREAS OF | | | THE BUILDING. | | | | | | 2.PROVIDE SUBMITTAL FOR THE FIRE | | | DAMPERS SHOWN ON PLAN SHEET 13, ACCESS | | | DOORS REQUIRED. | | | | | | 3.AS PER 2001 FBC(M) 606.2.2, DUCT | | | SMOKE DETECTORS REQUIRED.FAN SHUTDOWN | | | BY DUCT SMOKE DETECTOR SHALL HAVE | | | NOTIFICATION TO ALARM/STROBE IN NORMALLY | | | OCCUPIED AREAS NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2003-12-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-19 |
Time |
18:24 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-12-19 |
Time |
18:24 |
Sent To |
|
|
| Notes |
| 2003-12-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | | | | 1) SHT 3, NEW SHOWER STALL SHALL BE | | | ACCESSIBLE PER SECTION 11-4.1.3(11), | | | IF BATHING ROOMS ARE PROVIDED, THEN EACH | | | PUBLIC AND COMMON USE BATHROOM SHALL | | | COMPLY WITH 11-4.23. - SHOW COMPLIANCE | | | WITH 11-4.21 SHOWER STALLS & FIG. 35B. | | | SHOW SHOWER UNIT 11-4.21.6, & 11-4.21.7 | | | CURB. INDICATE THAT SHOWER WILL BE | | | ACCESSIBLE NOT ADAPTABLE ON REVISION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2003-07-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-07-03 |
Time |
17:49 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-07-03 |
Time |
17:49 |
Sent To |
E |
|
| Notes |
| 2003-07-03 00:00:00 | REVISION OK - ADDED ADA SHOWER - CHANGED | | | FLOOR PLAN, WATER RISER & SANT. RISER | | | DIAGRAMS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-04-12 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-06-27 |
Time |
15:10 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-04-12 |
Time |
06:43 |
Sent To |
|
|
| Notes |
| 2003-04-12 00:00:00 | PASSED/PROVISO | | | | | | HORIZONTAL STORM DRAIN SHALL BE 6" @ 2% | | | WHEN SECOND DRAIN IS ADDED. SEE SHEET #7 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-03-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-03-05 |
Time |
17:13 |
Rev Time |
0.75 |
| Received By |
kstevens |
Date |
2003-03-05 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2003-03-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 2 - MAXIMUM SQUARE FOOTAGE TO BE | | | DRAINED ON 4" PIPE @ 2% IS 2355. BELOW | | | ROOF AREA SHOWS 2434 SQUARE FEET BEING | | | DRAINED ON HORIZONTAL PIPE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-01-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-11 |
Time |
06:56 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2003-01-11 |
Time |
06:55 |
Sent To |
|
|
| Notes |
| 2003-01-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) PER TABLE 403.1 A DRINKING FOUNTAIN | | | IS REQUIRED FOR EACH WAREHOUSE BAY. ALSO | | | SEE SECTION 410.1 | | | 2) SHT 7 PLEASE PROVIDE CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTIONS 1106 AND 1107. ADD 1/2 AREA OF | | | ALL VERTICAL WALLS. MAXIMUM OF 1600 SQ | | | FT FOR HORIZONTAL 4" PIPE. SHOW TOTAL | | | SQUARE FOOTAGE FOR ROOF AND TOTAL DRAIN- | | | ING INTO EACH DRAIN. | | | 3) PLEASE PROVIDE A STORM RISER DIAGRAM. | | | INDICATE PIPE SIZE AND SHOW ACCUMULATED | | | SQ FT AT EACH RISER. | | | 4) SHT 13 THERMAL EXPANSION CONTROL IS | | | REQUIRED. SECTION 607.3.2 PLEASE SHOW AN | | | EXPANSION TANK AT WATER HEATER DETAIL. | | | 5) RPZ BACKFLOW REQUIRED ON WATER SERV- | | | ICE. | | | 6) SHT 13 GENERAL MECHANICAL NOTE #10, | | | AIR CHAMBERS ARE NOT APPROVED. PLEASE | | | PROVIDE WATER HAMMER ARRESTORS REQUIRED | | | IN SECTION 604.9 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-01-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-20 |
Time |
18:32 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
B |
|
| Notes |
|
|