| 2002-12-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW |
| | 1) COMPLY WITH FBC-2001 SEC 424.2 |
| | PRIVATE SWIMMING POOLS. (ADD TO NOTES) |
| | 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP- |
| | MENT AVOIDANCE. (DETAIL) THIS DETAIL NOT |
| | CLEAR (SECTION 104.2.1 FBC CHAPTER 1) |
| | 3) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER. (DETAIL) THIS DETAIL IS NOT |
| | CLEAR (SECTION 104.2.1 FBC CHAPTER 1) |
| | 4) FBC-2001 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL) |
| | 5) FBC-2001 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| | 19) FBC-2001 104.2 BUILDING DRAWINGS, & |
| | SPECIFICATIONS. TOO MANY SWIMMING POOL |
| | PIPING SCHEMATICS ON THE PLANS. THIS IS |
| | VERY CONFUSING. SHOW INDIVIDUAL PIPING |
| | SCHEMATIC FOR POOL BEING BUILT,W/SPA. |
| | SHOW PIPING FOR THE ENTIRE SYSTEM, PIPE |
| | SIZES, VENTS, SUCTION AND DISCHARGE PIP- |
| | ING EXT. DELETE ALL OTHER SCHEMATICS. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |