Plan Review Details - Permit 02120797
Plan Review Stops For Permit 02120797
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-25 Cont ID  
Sent By hmoser Date 2003-03-01 Time 09:20 Rev Time 0.75
Received By btrobaug Date 2003-02-25 Time 14:58 Sent To M
Notes
2003-02-25 00:00:00TO HAROLD MOSER'S DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-06 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 15:27 Rev Time 0.75
Received By btrobaug Date 2003-01-06 Time 13:23 Sent To B
Notes
2003-01-06 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 4} CIRCUIT # 18 IS LABELED 15 AMPS AND
 SMALL APPLIANCE,PLEASE COMPLY WITH
 210-52(B).
  
 5} THE COMPUTER ROOM NEEDS ANOTHER
 RECEPTACLE TO COMPLY WITH 210-52(A)(1).
  
 6} PLEASE INDICATE WHERE THE SERVICE
 DISCONNECT IS LOCATED.
  
 7} THE HALL SMOKE DETECTOR MUST COMPLY
 WITH 8-1.4.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-12 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 15:27 Rev Time 0.00
Received By btrobaug Date 2003-02-12 Time 15:27 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-03-01 Cont ID  
Sent By hmoser Date 2003-03-01 Time 09:27 Rev Time 0.50
Received By hmoser Date 2003-03-01 Time 09:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-03-01 Cont ID  
Sent By btrobaug Date 2003-02-25 Time 15:05 Rev Time 0.50
Received By hmoser Date 2003-01-04 Time 10:50 Sent To E
Notes
2003-01-04 00:00:00PLAN DENIED
 1) REFER TO SECTION 601.4 BALANCED
 RETURN AIR FBC.(M)
 2) NEED EXHAUST FANS IN BATHROOMS.2 IN
 MASTER BATH
 3) SHOW DUCT IN MASTER BATH
 4) NEED EVAP.COIL MODEL NUMBER ON PLAN
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-04 Cont ID  
Sent By jleech Date 2003-01-04 Time 06:50 Rev Time 0.25
Received By jleech Date 2003-01-04 Time 06:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-03-05 Cont ID  
Sent By jgomez Date 2003-03-05 Time 15:06 Rev Time 3.00
Received By jgomez Date 2003-03-05 Time 15:06 Sent To  
Notes
2003-03-05 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-34SH WINDOWS TO HAVE 24" MINIMUM CLEAR
 HEIGHT OPENING AS REQUIRED BY SECTION
 1005.4.4 FBC 2001.
 2-PROVIDE SAFETY GLASS IN BATHROOM #2.
 SEC. 2405.2 FBC 2001.
 **ALSO, PROVIDE SAFETY GLASS IN MASTER
 BATHROOM IS FACE THICKNESS OF GLASS
 BLOCK IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 3-PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOW SIZES AS SHOWN ON LIVING AND
 FAMILY ROOM.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2003-01-21 Cont ID  
Sent By jgomez Date 2003-01-21 Time 12:18 Rev Time 4.00
Received By jgomez Date 2003-01-17 Time 17:48 Sent To  
Notes
2003-01-21 00:00:00BUILDING REVIEW COMMENTS:
 1-REVISE ENERGY CALCULATIONS:
 A)SEE PLANS FOR NUMBER OF BEDROOMS.
 B)COMPLETE TOP OF FORM. EG: ADDRESS,
 OWNER'S NAME, ETC. SEE FORM.
 C)OWNER/AGENT SIGN & DATE BOTTOM OF FORM
  
 2-34SH WINDOWS DON'T PROVIDE 24' CLEAR
 HEIGHT OPENING REQ'D BY SEC. 1005.4.4
 FBC 2001. CLARIFY/REVISE AS REQUIRED.
 ARE THESE CUSTOM MADE WINDOWS?
 3-SPECIFY SAFETY GLASS WHERE REQUIRED.
 SEE PLANS AND SEC. 2405.2.2 FBC 2001.
 4-PROVIDE SOIL TEST REPORT.
 5-PROVIDE DETAIL/SPECIFICATIONS FOR
 INSTALLATION OF CEILING AT FRONT AND
 REAR PORCH AS REQUIRED BY ASTM C926
 AND ASTM C-1063.(SEC. 2504.2 FBC 2001)
 6-SPECIFY SIZE OF ATTIC VENT. SECTION
 2309.6 FBC 2001.
 7-TYPICAL WALL SECTION. SPECIFY FIREBLOC
 KING. SEC. 2305.1.4 FBC 2001.
 **PROVIDE GENERAL SPECIFICATIONS FOR
 FIREBLOCKING AT ALL CONCEALED SPACES
 AS REQUIRED BY SEC. 2305.1.4 FBC 2001.
 8-SPECIFY SUPPORTS FOR WWM IN CONCRETE
 SLAB. SEE SEC. 1909.3 FBC 2001.
 9-ADDRESS IS INCORRECT IN THE NOTICE OF
 COMMENCEMENT. REVISE STREET AS REQ'D.
 10-PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS:
 A)PROVIDE KEY PLAN.
 B)PROVIDE INSTALLATION SCHEDULE. SEE
 ATTACHED CITY SAMPLE.
 C)CLEARLY MARK ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
  
 11-PROVIDE PRODUCT APPROVAL FOR GARAGE
 DOORS WITH LEGIBLE DRAWINGS.
 12-PRODUCT APPROVAL FOR ARCHED WINDOWS:
 A)NEED LEGIBLE DRAWINGS.
 B)MISSING PAGE 2 OF THE REPORT.
 C)CHECK DESIGN PRESSURES CALCULATED BY
 THE ENGINEER OF RECORD.
 13-RECTANGULAR WINDOW PRODUCT APPROVAL:
 A)NEED LEGIBLE DRAWINGS.
 B)PROVIDE PRODUCT APPROVAL FOR WINDOW
 SIZES AS SHOWN ON PLANS.
 C)PROVIDE STRUCTURAL BUCK DETAIL USING
 A 2X BUCK AS REQ'D ON THIS APPROVAL.
 14-PROVIDE COMPLETE PRODUCT APPROVAL
 REPORT AND DRAWINGS FOR CEMENT TILE.
 15-PROVIDE SBCCI OR DADE COUNTY PRODUCT
 APPROVAL FOR ENTRY DOORS, AND EXTERIOR
 SWING DOORS AS SHOWN ON PLANS.
 **BROWARD COUNTY PRODUCT APPROVALS ARE
 NOT ACCEPTED IN THIS OFFICE.
 16-CLARIFY WHY THERE IS NOT A THICKENED
 REINFORCED EDGE AT FOYER RECESS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 17-SHEET #2 OF 5: UPDATE/REVISE NOTE #3.
 SEE SEC. 2306.1 CITY AMENDMENTS TO FBC
 2001 FOR FASTENER SPACING @ ZONE 3.
 18-OWES $484.12 FOR UPDATED VALUE AND
 RADON FEES.
 19-ENGINEER OF RECORD TO PROVIDE ALL HIS
 INFORMATION AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES WHEN SUBMITTING
 INFORMATION FOR PUBLIC RECORDS.
 20-REVISE/UPDATE SURVEY. PROPERTY IS
 LOCATED ON FLOOD ZONE "B", NOT 'A8"
 AS PER LETTER OF MAP REVISION DATED
 DECEMBER, 3RD 1985.
  
  
 NOTES:
 **SEE COMMENTS BY THE OTHER TRADES.
 **PLEASE, RETURN SETS AFTER CORRECTIONS
 ARE DONE TO THE ORIGINAL CAD DRAWINGS
 TO EXPEDITE THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By sgraham Date 2002-12-23 Time 13:33 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
***NONE***