Plan Review Details - Permit 02120666
Plan Review Stops For Permit 02120666
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-01-06 Cont ID  
Sent By jwitmer Date 2003-01-06 Time 14:53 Rev Time 2.10
Received By jwitmer Date 2003-01-06 Time 14:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-18 Cont ID  
Sent By hpiskura Date 2002-12-18 Time 15:20 Rev Time 0.00
Received By hpiskura Date 2002-12-18 Time 11:00 Sent To  
Notes
2002-12-18 00:00:00THE VARIOUS FURRED WOOD PANELING
 INSTALLATIONS MUST COMPLY WITH FBC
 803.9.PROVIDE SPECIFIC METHODS OR
 NOTES, DO NOT REFERENCE THE CODE
 SECTION.
  
 THE RELOCATED DOORS BEING USED WHERE
 FIRE RATED DOORS ARE REQUIRED MUST BE
 LABELED FOR THEIR APPLICATION.ALSO,
 THE CARD READER MUST BE INSTALLED IN
 ACCORDANCE WITH FBC 1012.1.7.
  
  
 THE NOTE ON THE DOOR SCHEDULE "UNDERCUT
 DOORS AS NECESSARY TO CLEAR FLOOR
 FINISHES" CANNOT ARBITRARILY BE APPLIED
 TO FIRE RATED DOORS.SEE NFPA 80-96 FOR
 THE LIMITATIONS RELATIVE TO FLOOR
 SURFACES AND NOTE ON PLANS AS NECESSARY.
  
 PLEASE PROVIDE A FRAMING AND FASTENING
 DETAIL FOR THE SOFFIT CONSTRUCTION
 DEPICTED IN SECTION 4 ON SHEET D901.
  
 THE VINYL AND FABRIC WALL COVERINGS
 MUSTBE LISTED IN ACCORDANCE WITH FBC
 803.5.2 AS WELL AS THE RELOCATED CARPET.
  
 THE PLANS MUST HAVE THE ARCHITECT'S
 EMBOSSED SEAL AS PROVIDED FOR IN
 CHAPTER 481 OF FLORIDA STATUTES.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-26 Cont ID  
Sent By btrobaug Date 2003-02-26 Time 17:05 Rev Time 0.50
Received By btrobaug Date 2003-02-26 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-24 Cont ID  
Sent By btrobaug Date 2003-02-24 Time 14:12 Rev Time 0.50
Received By btrobaug Date 2003-02-24 Time 14:12 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-16 Cont ID  
Sent By btrobaug Date 2003-01-27 Time 13:36 Rev Time 1.00
Received By jleahy Date 2002-12-16 Time 08:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-02-24 Cont ID  
Sent By nmccray Date 2003-02-24 Time 14:48 Rev Time 0.00
Received By nmccray Date 2003-02-24 Time 14:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-01-07 Cont ID  
Sent By btrobaug Date 2003-02-24 Time 14:12 Rev Time 0.00
Received By mcarsill Date 2003-01-07 Time 09:59 Sent To  
Notes
2003-01-07 00:00:001) THIS PLAN WAS REVIEWED AND FAILED
 UNDER PLAN PERMIT # 02120665
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096, EXT. 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-01-03 Cont ID  
Sent By mcarsill Date 2003-01-03 Time 13:35 Rev Time 0.00
Received By mcarsill Date 2003-01-03 Time 13:35 Sent To  
Notes
2003-01-03 00:00:001) NO PRODUCT APPROVALS PROVIDED FOR
 DOOR (100A).
  
 2) AGAIN COULD NOT LOCATE EMERGENCY
 LIGHTING EQUIPMENT WITHIN
 TENANT SPACE.
  
 3) ANY LOCKING DEVICES SHALL COMPLY
 WITH SPECIAL LOCKING ARRANGEMENTS IN
 CHAPTER 7, OF THE 2000 LIFE SAFETY
 CODE, SECTIONS A-E.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-20 Cont ID  
Sent By mcarsill Date 2002-12-20 Time 14:33 Rev Time 0.00
Received By mcarsill Date 2002-12-20 Time 14:33 Sent To  
Notes
2002-12-20 00:00:001) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 2) PLEASE PROVIDE PRODUCT APPROVAL FOR
 TYPE A DOOR (1000A). NOTES SUGGEST FIRE
 SAFETY ETCHED PATTERN GLASS PANELS.
  
 3) DOOR SCHEDULE SUGGESTS EXISTING
 LOCKING DEVICES ON EGRESS DOORS. PLEASE
 REVIEW SPECIAL LOCKING ARRANGEMENTS,
 CHAPTER 7, 2000 EDITION OF THE LIFE
 SAFETY CODE.
  
 4) PLEASE CLEARLY ILLUSTRATE LOCATIONS
 OF EMERGENCY LIGHTING EQUIPMENT WITHIN
 TENANT SPACE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2003-02-13 Time 15:21 Sent To M
Notes
2003-02-13 00:00:00TO MECH INBOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-27 Cont ID  
Sent By btrobaug Date 2003-01-27 Time 13:35 Rev Time 0.00
Received By btrobaug Date 2003-01-21 Time 13:35 Sent To E
Notes
2003-01-27 00:00:00TO JAKE./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-02 Cont ID  
Sent By dpalmer Date 2003-01-02 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2003-01-02 Time 12:53 Sent To  
Notes
2003-01-02 00:00:00TO COMM BOARD #54

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-07 Cont ID  
Sent By jwitmer Date 2003-01-07 Time 10:09 Rev Time 0.00
Received By jwitmer Date 2002-12-10 Time 13:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-02-14 Cont ID  
Sent By pkrauss Date 2003-02-14 Time 10:46 Rev Time 0.40
Received By pkrauss Date 2003-02-14 Time 10:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-04 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 15:21 Rev Time 1.00
Received By hmoser Date 2003-01-04 Time 06:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-01-04 Cont ID  
Sent By pkrauss Date 2002-12-27 Time 10:50 Rev Time 1.00
Received By hmoser Date 2002-12-27 Time 09:58 Sent To  
Notes
2002-12-27 00:00:00PROVISO:
  
 SMOKE EVAC & FAN SHUTDOWN REQUIRED AT
 FINAL MECHANICAL INSPECTION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-06 Cont ID  
Sent By kstevens Date 2003-01-06 Time 10:43 Rev Time 0.33
Received By kstevens Date 2003-01-06 Time 10:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-27 Cont ID  
Sent By kstevens Date 2002-12-27 Time 13:01 Rev Time 0.50
Received By kstevens Date 2002-12-27 Time 13:01 Sent To  
Notes
***NONE***