Plan Review Details - Permit 02120665
Plan Review Stops For Permit 02120665
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-01-13 Cont ID  
Sent By jwitmer Date 2003-01-13 Time 15:10 Rev Time 1.25
Received By jwitmer Date 2003-01-13 Time 15:07 Sent To  
Notes
2003-01-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120665
 ADD: 222 LAKEVIEW #1100
 CONT: CATALFUMO (ANNA)
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 PROVISO:
  
 1)ELEVATOR LOBBY DOORS / TO BE COMPLETED
 (02110927) BEFORE CERTIFICATE OF COMPLE-
 TION FOR THIS SPACE. SEE 412.6.1 AND
 412.6.2
  
 2) PLEASE PROVIDE FRAMING AND FASTENING
 DETAIL FOR SOFFIT TO THE EXISTING
 STRUCTURAL MEMBERS ABOVE BEFORE FRAMING
 INSPECTION.
  
 3) THE PLAN INDICATES CARD READERS INTHE
 DOOR SCHEDULE. PLEASE PROVIDE MANUFAC-
 TURES SPEC COMPLYING W/ 1012.6.1(2-3)
 OR DELETE FROM PLANS BY FRAMING INSPEC-
 TION.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-01-06 Cont ID  
Sent By jwitmer Date 2003-01-06 Time 15:50 Rev Time 2.10
Received By jwitmer Date   Time   Sent To  
Notes
2003-01-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120665
 ADD: 222 LAKEVIEW / 1100
 CONT: CATALFUMO
 TEL: (561)694-8818
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 SECOND REVIEW
  
 1) 412.6.1 ALL ELEVATORS ON ALL FLOORS
 SHALL OPEN INTO LOBBIES WHICH ARE
 SEPERATE FROM THE REMAINDER OF THE
 BUILDING BY 1-HR FIRE RESISTANT CONSTRUC
 TION WITH 20 MINUTE OPENING PROTECTIVES.
  
 2) 412.6.2 OPENINGS IN THE ELEVATOR
 LOBBY SHALL BE LIMITED TO THOSE REQUIRED
 FOR THE ACCESS TO THE ELEVATORS AND FOR
 EGRESS FROM THE BUILDING. EXIT STAIRWAYS
 CHUTES, JANITORS CLOSETS, GUEST ROOMS,
 SERVICE ROOMS, ETC, SHALL NOT OPEN INTO
 THE ELEVATOR LOBBY.
  
 3) PLEASE PROVIDE A LIFE SAFETY PLAN
 FOR THE FLOOR SO THAT EGRESS FROM ALL
 AREAS PROPOSED TO BE SEPERATE MAYBE
 DETERMINED.
  
 4) PLEASE PROVIDE A FRAMING & FASTENING
 DETAIL FRO THE SOFFIT CONSTRUVTION
 DEPICTED IN SECTION 3& 4 ON SHEET D9-01
 WHAT TYPE OF FASTENERS IS TO BE USED TO
 FASTEN THE SOFFIT TO THE STRUCTURE
 ABOVE?
  
 5) SHET D4-11 FINISH PLAN, INDICATES
 MATERIALS TO BE USED, BUT THE CLASSIFICA
 TION, FLAME SPREAD, SMOKE DEVELOPMENT
 IS MISSING!!! SEE 803.2 CLASSIFICATION
 ALSO 803.5.2 TEXTILE WALL COVERINGS.
  
 6) FINISH LEGEND- CPT-3 NOT USED, REVISE
 FLOOR PLAN, INDICATES 10 ROOMS USING
 THIS PRODUCT!
  
 7) FINISH LEGEND- FWC 3&4 PLEASE PROVIDE
 PRODUCT INFORMATION, FLAME SPREAD/ SMOKE
 DEVELOPMENT.
  
 8) CARD READER/ AUTO CLOSER 1012.6.1
 (2) THE DOORS UNLOCK UPON LOSS OF POWER
 CONTROLLING THE LOCK OR LOCKING MECHAN-
 ISM: AND
 (3) AN IRREVERSIBLE PROCESS RELEASES THE
 LOCK WITHIN 15 SECONDS UPON APPLICATION
 TO THE RELEASE DEVICE REQUIRED IN
 1012.1.8.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-18 Cont ID  
Sent By hpiskura Date 2002-12-18 Time 16:04 Rev Time 0.00
Received By hpiskura Date 2002-12-18 Time 15:47 Sent To  
Notes
2002-12-18 00:00:00THE ELEVATOR LOBBY AS SHOWN DOES NOT
 COMPLY WITH FBC 412.6.
  
 PLEASE PROVIDE A LIFE SAFETY PLAN FOR
 THE FLOOR SO THAT EGRESS FROM THE AREAS
 PROPOSED TO BE SEPARATED MAY BE
 DETERMINED. SEE FBC 104.2.
  
 A COPY OF THE NOTES FOR THE 10TH FLOOR
 COMPANION PERMIT ARE ATTACHED HERE
 SINCE THE SAME ISSUES APPLY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-26 Cont ID  
Sent By btrobaug Date 2003-02-26 Time 17:38 Rev Time 0.00
Received By btrobaug Date 2003-02-26 Time 17:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-16 Cont ID  
Sent By jleahy Date 2002-12-16 Time 08:21 Rev Time 1.00
Received By jleahy Date 2002-12-16 Time 08:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-01-14 Cont ID  
Sent By nmccray Date 2003-01-14 Time 15:25 Rev Time 0.00
Received By nmccray Date 2003-01-14 Time 15:25 Sent To  
Notes
2003-01-14 00:00:00PROVISO:
  
 1) PROVIDE MORE EMERGENCY LIGHTING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2003-01-07 Cont ID  
Sent By mcarsill Date 2003-01-07 Time 09:47 Rev Time 0.00
Received By mcarsill Date 2003-01-07 Time 09:47 Sent To  
Notes
2003-01-07 00:00:001) NO PRODUCT APPROVALS PROVIDED FOR
 DOOR (100A).
  
 2) AGAIN COULD NOT LOCATE EMRGENCY
 LIGHTING EQUIPMENT WITHIN TENANT SPACE.
  
 3) ANY LOCKING DEVICES SHALL COMPLY
 WITH SPECIAL LOCKING ARRANGEMENTS IN
 CHAPTER 7, OF THE 2000 LIFE SAFETY
 CODE, SECTIONS A-E.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096, EXT. 8497
 835=2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-01-03 Cont ID  
Sent By mcarsill Date 2003-01-03 Time 13:03 Rev Time 0.00
Received By mcarsill Date 2003-01-03 Time 13:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 14:07 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 14:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-02 Cont ID  
Sent By dpalmer Date 2003-01-02 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2003-01-02 Time 13:45 Sent To  
Notes
2003-01-02 00:00:00TOCOMM BOARD #53

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-04 Cont ID  
Sent By hmoser Date 2003-01-04 Time 06:21 Rev Time 1.00
Received By hmoser Date 2003-01-04 Time 06:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-19 Cont ID  
Sent By pkrauss Date 2002-12-19 Time 14:27 Rev Time 1.15
Received By pkrauss Date 2002-12-19 Time 11:31 Sent To  
Notes
2002-12-19 00:00:00PROVISO:
  
 SMOKE EVAC & FAN SHUTDOWN REQUIRED FOR
 FINAL INSPECTION.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-04 Cont ID  
Sent By jleech Date 2003-01-04 Time 06:18 Rev Time 0.50
Received By jleech Date 2003-01-04 Time 06:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-17 Cont ID  
Sent By kstevens Date 2002-12-17 Time 14:05 Rev Time 0.50
Received By kstevens Date 2002-12-17 Time 14:05 Sent To  
Notes
2002-12-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) PLEASE SUBMIT A SANITARY RISER DIA-
 GRAM AND A WATER RISER DIAGRAM. SHOW ALL
 PIPE SIZES. SHOW REQUIRED WATER HAMMER
 ARRESTOR PER 604.9 LOCATED NEAR FIXTURE
 IN AN "EFFECTIVE RANGE" NOT AT TOP OF
 DROP. SEC 104.2 (AMENDMENTS)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377