Plan Review Details - Permit 02120658
Plan Review Stops For Permit 02120658
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-04-02 Cont ID  
Sent By jwitmer Date 2004-04-02 Time 10:33 Rev Time 0.75
Received By jwitmer Date 2004-04-02 Time 10:33 Sent To  
Notes
2004-04-02 00:00:0004-02-2004 "AS BUILTS"JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-02-25 Cont ID  
Sent By btrobaug Date 2004-03-26 Time 07:15 Rev Time 1.25
Received By jwitmer Date 2004-02-25 Time 15:45 Sent To  
Notes
2004-02-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120658
 ADD: 6815 S FLAGLER DR
 CONT: HINCKLEY CONST
 TEL: (561)718-9051
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION:
 ACTION: DENIED
  
 PLANS FOR PUBLIC RECORD ARE REQUIRED TO
 BE IN INK NOT PENCIL, THEY WILL NOT
 PRINT FOR RECORD RETENTION.
  
 2) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6".
 PLANS INDICATE A EXISTING ELEVATION OF
 5.67' PLUS A RISE OF 1.75'= 7'-5 1/4"
 NOT THE REQUIRED 7'-6". A FLOOD ELEVA-
 TION CERTIFICATE SHALL BE REQUIRED BEFOR
 A CERTIFICATE OF OCCUPANCY WILL BE
 ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-04-08 Cont ID  
Sent By pkrauss Date 2004-02-23 Time 08:35 Rev Time 0.75
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-03-28 Cont ID  
Sent By dpalmer Date 2003-04-03 Time 14:41 Rev Time 2.50
Received By jwitmer Date 2003-03-28 Time 12:32 Sent To  
Notes
2003-03-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120658
 ADD: 6815 S FLAGLER DRIVE
 CONT: HINCKLEY CONSTRUCTION
 TEL: (561)832-3310
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 BUILDING PLAN REVIEW
 ACTION: PROVISO:
  
 1)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 2)2804.4.4. FACTORY-BUILT CHIMNEYS
 FOR USE WITH CLOSED COMBUSTION WOOD
 BURNING APPLIANCES SHALL COMPLY WITH
 THE TYPE HT REQUIREMENT UL 103.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-03-03 Cont ID  
Sent By jwitmer Date 2003-03-03 Time 13:42 Rev Time 3.25
Received By jwitmer Date 2003-03-03 Time 13:42 Sent To  
Notes
2003-03-03 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02120658
 ADD: 6815 S FLAGLER DR
 CONT: HINKLEY CONSTRUCTION
 TEL: (561)832-3310
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 ADDRESS ON CURRENT NOC NOT CORRECT.
  
 2) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". THE ADDITION IS
 LOCATED IN A A5 FLOOD ZONE, MINIMUM
 FLOOR ELEVATION IS 7'-6" THE NGVD GIVEN
 FOR ORIGINAL HOUSE IS 5.67 + 1.75 FINISH
 FLOOR ELEVATION IS 7'-51/4" NOT 7'-6".
  
 3) PREVIOUS COMMENT #(8) :
 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) FIXED WINDOWS ABOVE CASEMENT WINDOWS
 B) MULLIONS HORIZONTAL / VERTICAL
 C) SWING DOORS W/ SIDELIGHTS
 D) ROOFING ASSEMBLIES
  
 4)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 5)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 6)2804.4.1 FACTORY-BUILT CHIMNEYS
 FACTORY BUILT CHIMNEYS SHALL BE LISTED
 AND SHALL BE INSTALLED IN ACCORDANCE
 WITH THE CONDITIONS OF THE LISTING, AND
 MANUFACTURER'S INSTRUCTION.
  
 7)2804.4.4. FACTORY-BUILT CHIMNEYS
 FOR USE WITH CLOSED COMBUSTION WOOD
 BURNING APPLIANCES SHALL COMPLY WITH
 THE TYPE HT REQUIREMENT UL 103.
  
 8)CHIMNEYS FOR THE USE WITH FACTORY-
 BUILT FIREPLACES SHALL MEET THE
 REQUIREMENTS OF UL 127.
  
 9)2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
  
 10)2810 FRESH AIR INTAKES, FRESH AIR
 INTAKESSHALL BE SCREENED WITH A CORRO-
 SION RESITANT MATERIAL NOT LARGER THAN
 1/2 INCH MESH. FRESH AIR INTAKES SHALL
 NOT BE TAKEN FROM A LOCATION CLOSER THAN
 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR
 SANITARY SEWER VENT OUTLET, UNLESS SUCH
 VENT IS NOT LESS THAN 24" ABOVE THE
 FRESH AIR VENT. FRESH AIR INTAKE VENTS
 LOCATED ON THE ROOFS WILL BE PROPERLY
 MARKED WITH A UNIVERSAL MARKING,
 ***"INTAKE"***, PERMANETLY ATTACHED.
 SEE 705.1.1.4 FOR FIRE PROTECTION.
  
 COMMENT: NOTES ON MECH PLANS.
 WE ARE LOOKING FOR THE MANUFACTURERS
 SPEC/ INSTALLATION GUIDE.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)659-8096 X 8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-02-04 Cont ID  
Sent By sgraham Date 2003-01-24 Time 16:49 Rev Time 4.50
Received By jwitmer Date 2003-02-04 Time 06:52 Sent To  
Notes
2003-02-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02120658
 ADD: 101 ALPINE ROAD
 CONT: HINCKLY CONSTRUCTION
 TEL: (561)832-3310
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE RECORDED PROPERTY ADDRESS IS
 101 ALPINE RD. DOES THE OWNER WANT TO DO
 A ADDRESS CHANGE TO 6815 S FLAGLER? IF
 SO THEY SHOULD WRITE A LETTER FOR AN ADD
 RESS CHANGE, WE WILL REARCH THE PROPOSED
 ADDRESS TO SEE IF IT IS AVAILABLE AND
 NOTIFY ALL AGENCIES OF THE CHANGE.
  
 2) NOTICE OF COMMENCEMENT IS UNDER 101
 ALPINE ROAD IF THE ADDRESS IS TO BE
 CHANGED.
  
 3) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". THE ADDITION IS
 LOCATED IN A A5 FLOOD ZONE MINIMUM FLOOR
 ELEVATION IS 7'-6''. INDICATE WHAT THE
 FLOOR ELEVATION IS NOT IN REFRENCE TO
 EXISTING FLOOR ELEVATION.
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SOIL BORING TEST INDICATING
 WHAT THE MINIMUM BEARING CAPACITY IS?
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 STRUCTURAL PLANS INDICATE THE USE OF A
 PRECAST SLAB SYSTEM "AUREA SLAB", PRO-
 VIDE ADDITIONAL INFORMATION, COULD NOT
 FIND ANYTHING ON ENTERNET?
  
 6) S-3 INDICATES THE MEAN ROOF HEIGHT
 OF 30'-0". THIS IS FROM THE EXISTING
 FLOOR LEVEL OF EXISTING RESIDENCE.
 WHAT IS IT FROM NGVD?
  
 7) TRUSS ANCHOR SCHEDULE ANCHOR D,E&F
 USE A USP2 WHICH IS A WOOD TO WOOD
 ANCHOR, PLANS INDICATE THAT IT IS A
 EMBEDDED ANCHOR?
  
 8)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.MISSING REPORTS:
 A) FIXED WINDOWS
 B) CASEMENT WINDOWS
 C) MULLIONS
 D) SWING DOORS
 E) SWING DOORS W/ SIDELIGHTS
 F) ROOFING ASSEMBLIES
 G) STORM SHUTTERS
  
 9)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 11)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 12) 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 13)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 14)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) 1816.1.6. SOILS TREATMENT SHALL BE
 REQUIRED UNDER ALL EXTERIOR CONCRETE
 ON GRADE WITHIN 1 FOOT OF THE PRIMARY
 STRUCTURE SIDEWALLS. SHEET A2 & A7 INDI-
 CATE THERE ARE VARIOUS SLABS NEXT TO
 THE STRUCTUE.
  
 16)2804.4.1 FACTORY-BUILT CHIMNEYS
 FACTORY BUILT CHIMNEYS SHALL BE LISTED
 AND SHALL BE INSTALLED IN ACCORDANCE
 WITH THE CONDITIONS OF THE LISTING, AND
 MANUFACTURER'S INSTRUCTION.
  
 17)2804.4.4. FACTORY-BUILT CHIMNEYS
 FOR USE WITH CLOSED COMBUSTION WOOD
 BURNING APPLIANCES SHALL COMPLY WITH
 THE TYPE HT REQUIREMENT UL 103.
  
 18)CHIMNEYS FOR THE USE WITH FACTORY-
 BUILT FIREPLACES SHALL MEET THE
 REQUIREMENTS OF UL 127.
  
 19)2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
  
 20)2810 FRESH AIR INTAKES, FRESH AIR
 INTAKESSHALL BE SCREENED WITH A CORRO-
 SION RESITANT MATERIAL NOT LARGER THAN
 1/2 INCH MESH. FRESH AIR INTAKES SHALL
 NOT BE TAKEN FROM A LOCATION CLOSER THAN
 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR
 SANITARY SEWER VENT OUTLET, UNLESS SUCH
 VENT IS NOT LESS THAN 24" ABOVE THE
 FRESH AIR VENT. FRESH AIR INTAKE VENTS
 LOCATED ON THE ROOFS WILL BE PROPERLY
 MARKED WITH A UNIVERSAL MARKING,
 ***"INTAKE"***, PERMANETLY ATTACHED.
 SEE 705.1.1.4 FOR FIRE PROTECTION.
  
 21) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE MANUFACTURERS SPEC FOR PRIVATE
 (RESIDENTIAL) ELEVATOR.
  
 22) 1007.5.3 HANDRAILS: STAIRS LEADING
 FROM THE COVERED TERRACE MAY HAVE A
 GUARDRAIL BUT NO HANDRAIL MEETING THIS
 SECTION.
  
 23) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 MISSING INFORMATION ON HOW THE CHIMNEY
 WILL FRAME INTO THE ROOF FRAMING?
  
 24) SHEET A-7 SECTION 2, SECOND FLOOR
 TERRACE, WHAT TYPE OF MATERIAL IS TO BE
 USED TO STOP RAIN FROM PENETRATING THE
 SLAB INTO THE INTERIOR? STRUCTURAL
 DETAILS S2 DETAIL OF DECK 11/S5 MISSING?
  
 25)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2004-03-26 Cont ID  
Sent By btrobaug Date 2004-03-26 Time 07:15 Rev Time 1.00
Received By btrobaug Date 2004-03-25 Time 18:05 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-02-13 Cont ID  
Sent By pkrauss Date 2004-03-23 Time 13:57 Rev Time 0.50
Received By dpalmer Date 2004-02-13 Time 07:01 Sent To M
Notes
2004-02-13 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT TWO SETS OF PLANS
 SIGNED, DATED AND SEALED BY THE ARCH
 AND ENGINEER OF RECORD. PLEASE SEE
 ONE SET IS A COPY OF THE SIGNED AND
 SEALED PLANS. PLEASE SEE ONE SET IS
 DONE AND SUBMITTED IN PENCIL. PLEASE
 NOTE THIS NOT PERMITTED.
 PLANS MUST BE REPRINTED.
 PLEASE ALSO INCLUDE ALL LICENSE #'S
 IN TITLE BLOCK FOR ENGINEER. CERTIFICATE
 OF AUTHORIZATION # IS REQUIRED PER
 FS 471.023. 61G15-23.002 OF FAC.
 ABOVE ALSO PER FS 471.025, 481.221
  
 2)NOTE: PLEASE SEE THAT PLANS ARE NOW
 COMING BACK IN AFTER ORIG CORRECTIONS
 WERE MADE TO PLANS. RISER IS ONCE
 AGAIN INDICATING A 425A SERVICE WITH A
 400A METER CAN.
 PLEASE SUBMIT A COMPLETED RISER DIAGRAM
 FOR FULL REVIEW. ONE SHEET HAS THE ORIG
 RISER CROSSED OUT. THE OTHER SHEET IS
 MISSING INFORMATION NEEDED.
 PLEASE INCLUDE ALL CONDUCTOR SIZES.
 215.5
  
 3)NOTE: PANEL "C" DOES NOT LIST PANEL
 "D". NO OCP.?
  
 4)NOTE: PLEASE SHOW AHU KW RATINGS IN
 LOAD CALCULATIONS. LOAD CALCS DO NOT
 SEEM TO CORRELATE WITH OCP SHOWN ON
 PANEL SCHEDULE.
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS MIN OF
 20'FROM COOKING APPL. NFPA-72 8-1.4.2
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 6)NOTE: PLEASE SHOW A/C UNITS ON PLANS,
 DISC'S PER 440.11 AND RECEPTS REQ'D PER
 210.63
  
 PLEASE SUBMIT TWO COMPLETED SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-04-03 Cont ID  
Sent By csiegber Date 2004-02-06 Time 15:14 Rev Time 0.75
Received By dpalmer Date 2003-04-03 Time 13:55 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-03-21 Cont ID  
Sent By shernand Date 2003-04-02 Time 15:50 Rev Time 0.75
Received By dpalmer Date 2003-03-21 Time 05:23 Sent To P
Notes
2003-03-21 00:00:00************** UNSAT *****************
  
 PLEASE SEE FIRST TWO REVIEWS.
 THERE ARE STILL A COUPLE OF NOTES NOT
 DONE.
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR ALL
 NEW EQUIPMENT. MAINS/PANELS AND BRKRS
 ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. IT WAS NOTED ON PANEL
 SCHEDULE THAT BRANCH BRKRS ARE TO
 SERIES RATED WHICH IS OK. HOWEVER NOTH-
 -ING WAS SUBMITTED FOR NEW MAIN DISC OR
 PANEL?? 110-9/215-5
  
 2)NOTE: PLEASE SIZE SEC`S PER 310-15.
 PLANS NOW SHOW 250MCM WHICH IS RATED
 FOR A 300A SERVICE PER 310-15. PLANS
 SHOW A 400A SERVICE.
  
 3)NOTE:PLEASE SEE LOAD CALCULATIONS,NOW
 A/C`S HAVE BEEN ADDED BUT LOAD CALCS
 NEED TO BE DONE PER NEC 220.
 PLEASE ALSO NOTE, MAX OCP FOR 5KW CAN
 NOT EXCEED 150% OF LOAD. THE MIN IS 125%
 PER 424-3B
 PLEASE ALSO SEE OCP SHOWN FOR 4.5KW
 WATER HEATER. WH OCP SHOULD BE SET A MIN
 OF 125% OF LOAD AND MAX 150%. PLEASE
 ADJUST.422-13/422-11E
  
 4)NOTE: PLEASE HAVE REVSION DATES SHOWN
 ON RIGHT SIDE OF PLANS, ALL SHOWN AS
 00/00/00?
  
 PLEASE NOTE PREVIOUS NOTES MENTIONED
 FS 553-80(2)(B) WHICH SAYS A 4X FEE
 SHALL BE ADDED FOR PLANS W/ COMMENTS
 ATTACHED AND TURNED DOWN FOR THE SAME
 NOTES 3 OR MORE TIMES. PLEASE SEE LETTER
 ATTACHED. PLEASE CALL TO SET UP A TIME
 TO GO OVER PLANS AND IF BEFORE RESUB-
 -MITTING PLANS A MEETING IS DESIRED TO
 OVER PLANS, PLEASE CALL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-24 Cont ID  
Sent By sthyng Date 2003-03-17 Time 16:25 Rev Time 0.50
Received By dpalmer Date 2003-02-24 Time 06:19 Sent To P
Notes
2003-02-24 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SEE RISER, PLANS NOW
 SHOW A 425A SERVICE ON A 400A METERCAN.
 PLEASE CORRELATE SERVICE SIZE WITH
 EQUIPMENT.
  
 2)NOTE: PLEASE SHOW SERVICE ENTRANCE
 CONDUCTOR SIZES FROM METER TO GUTTER AND
 ON TO 225A, SHOWS 2/0`S FOR 200A.
 310-15/240-3
  
 3)NOTE: PLEASE SEE PLANS, SHOW THREE
 A/C SYSTEMS AND ONLY ONE SHOWN ON LOAD
 CALCULATIONS,???
  
 4)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. PLEASE SEE THAT MOST OF THE NOTE
 -S FROM FIRST REVIEW ARE THE SAME AND
 HAVE NOT BEEN ADDRESSED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE ALSO SEE LETTER ATTACHED
 PER FS 553.80(2) (B). IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-30 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 14:24 Rev Time 1.00
Received By dpalmer Date 2003-01-30 Time 08:09 Sent To M
Notes
2003-01-30 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY LOCATION OF NEW
 PANEL? PLANS SHOW A NEW PANEL IN KITCHEN
 , PLEASE CLARIFY IF THIS THE SAME PANEL
 SHOWN ON RISER. IF SO, PLEASE SEE 230-72
 FOR GROUPING OF MAINS.
  
 2)NOTE: PLEASE SUBMIT AIC RATING(S) FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 ALL MAINS, PANELS, BRKRS ARE TO BE
 RATED FOR THE AVAILABLE FULAT CURRENT.
 110-9
  
 3)NOTE: PLEASE NOTE/CLARIFY SIZE OF
 EXISTING SERVICE ENTRANCE CONDUCTORS.
  
 4)NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 AND SHOW ALL NEW ITEMS W/ WIRE AND OCP
 SIZES.
 PLEASE SHOW WIRING AND SIZES FOR AHU`S/
 CU`S.
  
 5)NOTE: PLEASE LIST THE REQ`D BATH(S)
 DEDICATED CIRCUIT(S) PER 210-52D,210-11-
 C-3.
  
 6)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS FOR BEDROOM/SLEEPING ROOMS
 PER 210-12
  
 7)NOTE: MISSING SD`S REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS. NFPA-72
 8-1. ALSO ON EACH LEVEL OF A MULTI-LEVEL
 HOUSE.
 8)NOTE: PLEASE SHOW ALL KITCHEN COUNTER-
 -SPACE OUTLETS AS GFI/GFI PROTECTED PER
 210-8-A-6.
  
 9)NOTE: PLEAS CLARIFY LOAD SHOWN FOR
 WATER HEATER (1). SHOWN AS 9KW? 40A OCP,
 PLEASE SEE NEC 422-13
  
 10)NOTE: PLEASE SHOW A/C UNITS ON
 ELECTRICAL PLANS AND SHOW DISC`S PER
 440-11.
  
 11)NOTE: PLEASE SEE MISSING OUTLET(S)
 PER 210-52, MASTER BEDROOM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-03-17 Cont ID  
Sent By csiegber Date 2004-03-17 Time 14:14 Rev Time 0.00
Received By csiegber Date 2004-03-17 Time 14:14 Sent To M
Notes
2004-03-17 00:00:00TO PK DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 15:14 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 15:14 Sent To E
Notes
2004-02-06 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-04-02 Cont ID  
Sent By shernand Date 2003-04-02 Time 15:50 Rev Time 0.00
Received By shernand Date 2003-04-02 Time 15:50 Sent To E
Notes
2003-04-02 00:00:00DPALMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-03-17 Cont ID  
Sent By sthyng Date 2003-03-17 Time 16:25 Rev Time 0.00
Received By sthyng Date 2003-03-17 Time 16:25 Sent To E
Notes
2003-03-17 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-20 Cont ID  
Sent By dpalmer Date 2003-02-20 Time 14:23 Rev Time 0.00
Received By dpalmer Date 2003-02-20 Time 14:23 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-27 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 11:57 Rev Time 0.00
Received By dpalmer Date 2003-01-27 Time 11:57 Sent To P
Notes
2003-01-27 00:00:00TO PLUMB INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 17:26 Rev Time 0.00
Received By btrobaug Date 2003-01-17 Time 17:26 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 17:42 Rev Time 0.00
Received By btrobaug Date 2002-12-10 Time 17:42 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2004-03-23 Cont ID  
Sent By pkrauss Date 2004-03-23 Time 13:56 Rev Time 0.25
Received By pkrauss Date 2004-03-23 Time 13:56 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2004-02-23 Cont ID  
Sent By csiegber Date 2004-03-17 Time 14:14 Rev Time 0.40
Received By pkrauss Date 2004-02-23 Time 08:27 Sent To B
Notes
2004-02-23 00:00:00DENIED:
 ONE SET OF PLANS ARE DRAWN IN PENCIL.
 THE COPY OF ORIGINAL PLANS SHALL HAVE
 ORIGINAL SIGNATURE & DATE BY THE
 ARCHITECT.PLANS ARE TO BE SEALED BY
 THE ARCHITECT PER FS 481.221.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-03-26 Cont ID  
Sent By dpalmer Date 2004-02-13 Time 07:01 Rev Time 0.35
Received By pkrauss Date 2003-03-26 Time 13:42 Sent To  
Notes
2003-03-26 00:00:00PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-03-03 Cont ID  
Sent By kstevens Date 2003-03-24 Time 09:54 Rev Time 0.30
Received By pkrauss Date 2003-03-03 Time 14:49 Sent To  
Notes
2003-03-03 00:00:00COMMENTS FROM 1/31/03 NOT ADDRESSED.
  
 PROVIDE MANUAL J CALCULATIONS AS PER
 2001 FBC CHAPTER 13 SECTION 607.1.ABC.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-31 Cont ID  
Sent By dpalmer Date 2003-01-30 Time 08:10 Rev Time 0.40
Received By pkrauss Date 2003-01-31 Time 11:50 Sent To  
Notes
2003-01-31 00:00:00PLEASE PROVIDE MANUAL J CALCULATIONS AS
 REQUIRED PER 2001 FBC CHAPTER 13 SECTION
 607.1.ABC.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-03-24 Cont ID  
Sent By dpalmer Date 2003-03-21 Time 05:38 Rev Time 0.50
Received By kstevens Date 2003-03-24 Time 09:36 Sent To M
Notes
2003-03-24 00:00:00PASSED/PROVISO
  
 AIR CHAMBERS NOT APPROVED 604.9
 WATER HEATERS SHALL HAVE THERMAL EXPANS-
 ION CONTROL 607.3.2
 SEPARATE GAS PERMIT REQUIRED. PLEASE
 INDICATE TYPE OF GAS AND DELIVERY PRESS-
 URE WHEN APPLYING FOR GAS PERMIT. IF 1/2
 LB NATURAL THEN 3/4" GALV. PIPE REQD.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-01 Cont ID  
Sent By dpalmer Date 2003-02-24 Time 06:20 Rev Time 0.50
Received By kstevens Date 2003-03-01 Time 07:13 Sent To  
Notes
2003-03-01 00:00:00PASSED/PROVISO
  
 AIR CHAMBERS NOT APPROVED604.9.
 WATER HEATERS SHALL HAVE THERMAL EXPANS-
 ION CONTROL.
 SEPARATE GAS PERMIT REQUIRED. PLEASE
 INDICATE TYPE OF GAS AND DELEVERY PRESS-
 URE WHEN APPLYING FOR GAS. - IF 1/2 LB
 NATURAL GAS THEN 3/4" GALV PIPE REQUIRED

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-28 Cont ID  
Sent By dpalmer Date 2003-01-27 Time 11:58 Rev Time 0.75
Received By kstevens Date 2003-01-28 Time 13:21 Sent To E
Notes
2003-01-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
  
 1) SHT P1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. FIRST FLOOR
 SINK AND LAV ARE NOT VENTED. VERTICAL
 DRY VENT SHALL BE BETWEEN W/C AND SHOWER
 SECOND FLOOR, HORIZONTAL DRY VENTS ARE
 NOT APPROVED. (TUB VENT NOT REQUIRED, &
 W/C VENT CAN BE TAKEN OFF ON THE RISE TO
 WASH VENT. (SEE RED LINE CHANGES).
 2) SHT P1 WATER RISER DIAGRAM, AIR CHAM-
 BERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS, REQUIRED BY SEC 604.9, AT WASH
 MACHINE, ICE MAKER, & DISHWASHER.
 3) SHT P1 WATER RISER DIAGRAM, WATER
 HEATERS REQUIRE THERMAL EXPANSION CONT-
 ROL SECTION 607.3.2 - P/T DISCHARGE LINE
 SHALL DRAIN OUTSIDE WITH NO TRAPPED SEC-
 TIONS. SECTION 504.7.1 - 2ND FLOOR WATER
 HEATER SHALL HAVE AN EMERGENCY PAN PER
 SECTION 504.8.
 4) SHT P1 A SEPARATE GAS PERMIT IS RE-
 QUIRED. SEE FOLLOWING GAS PERMIT APPLI-
 CATION REQUIREMENTS.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 F) ALL GAS APPLIANCES SHALL BE LISTED
 FOR RESIDENTIAL USE ONLY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2003-01-24 Cont ID  
Sent By sgraham Date 2003-01-24 Time 16:49 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-02 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 17:27 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-02 00:00:00DENIED
 1. NEED A FLOOR PLAN SHOWING EXISTING
 HOUSE
 2. IN SF7 ZONE DISTRICT ONLY ONE
 KITCHEN WILL BE ALLOWED
 3. TOTAL HEIGHT OF HOUSE MUST NOT EXCEED
 33'
 4. THE CORNER SIDE SETBACK MUST BE
 12.5'


Account Summary | Usage Policy | Privacy Policy