Plan Review Details - Permit 02120612
Plan Review Stops For Permit 02120612
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By hpiskura Date 2003-02-07 Time 10:29 Rev Time 0.00
Received By hpiskura Date 2003-02-07 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-01-14 Cont ID  
Sent By hpiskura Date 2003-01-14 Time 08:11 Rev Time 0.00
Received By hpiskura Date 2003-01-13 Time 16:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 06:01 Rev Time 0.25
Received By dpalmer Date 2003-02-07 Time 06:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-27 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 17:42 Rev Time 1.50
Received By dpalmer Date 2002-12-27 Time 17:41 Sent To  
Notes
2002-12-27 00:00:00*************** UNSAT *****************
  
  
 PLEASE NOTE, ALL ELECTRICAL SHEETS WERE
 STAMPED IN ERROR. PLEASE ADDRESS THE
 FOLLOWING COMMENTS AND SUBMIT NEW SHEETS
 IN SETS WHEN ALL REVIEWS ARE COMPLETE
 AND PLANS ARE RESUBMITTED FOR REVIEW.
  
 1)NOTE: PLEASE NOTE CIRCUITING FOR ALL
 EMERGENCY AND EXITS LTS TO MEET 700-12
 WHICH WILL HAVE AN EFFECT ON LOADING
 OF CIRCUITS, CIRCUIT #`S AND PANEL
 SCHEDULES.
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENST
 AS PANELS MAY CHANGE LOCATION DUE TO
 FIRE RATING OF ROOMS WHERE PANELS ARE
 LOCATED.
  
 3)NOTE: PLEASE CLARIFY FIXTURES/TYPES
 IN ORDER TO MEET 700-16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By mcarsill Date 2003-02-07 Time 09:56 Rev Time 0.00
Received By mcarsill Date 2003-02-07 Time 09:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-19 Cont ID  
Sent By mcarsill Date 2002-12-19 Time 13:53 Rev Time 0.00
Received By mcarsill Date 2002-12-19 Time 13:53 Sent To  
Notes
2002-12-19 00:00:001) DUCT SMOKE DETECTORS ARE REQUIRED
 TO ACTIVATE THE FIRE ALARM SYSTEM. IN
 THE FIRE ALARM NOTES SECTION, IT
 INDICATES A SUPERVISORY SIGNAL WILL
 BE PROVIDED.
  
 2) IT APPEARS THAT MAGNETIC LOCKS
 ARE PRESENT ON EXIT DOORS. LOCKS ON
 EGRESS DOORS SHALL COMPLY WITH
 DELAYED EGRESS OR ACCESS CONTROLLED.
 PLEASE REVIEW SPECIAL LOCKING
 ARRANGEMENTS IN CHAPTER SEVEN OF THE
 2000 EDITION OF THE LIFE SAFETY CODE.
  
 3) ALL ELECTRICAL, MECHANICAL, AND
 STORAGE ROOM DOORS ARE TO BE FIRE
 SEPARATED FROM OTHER AREAS OF THE
 BUILDING BY AT LEAST ONE HOUR WITH
 RATED OPENING PROTECTIVE DEVICES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2003-02-18 Time 15:14 Sent To P
Notes
2003-02-18 00:00:00PLUMB INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 12:40 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 12:40 Sent To  
Notes
2003-02-04 00:00:00TO COMM BOARD #13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-09 Cont ID  
Sent By btrobaug Date 2002-12-09 Time 18:04 Rev Time 0.00
Received By btrobaug Date 2002-12-09 Time 18:04 Sent To  
Notes
2002-12-09 00:00:00COMM BOARD #14./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-08-15 Cont ID  
Sent By pkrauss Date 2003-08-15 Time 09:03 Rev Time 0.15
Received By pkrauss Date 2003-08-15 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By hmoser Date 2002-12-28 Time 12:34 Rev Time 1.50
Received By hmoser Date 2002-12-28 Time 12:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-02-24 Cont ID  
Sent By pschmitz Date 2003-02-24 Time 11:29 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2003-02-24 00:00:00REVISION, APPROVED, PES.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-18 Time 15:25 Rev Time 1.25
Received By kstevens Date 2003-02-07 Time 17:44 Sent To  
Notes
2003-02-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) ANSWER NOTED CONCERNING THE 20%
 DISPROPORTIONAL COST FOR ACCESSIBILITY.
 PLEASE ITEMISE ALL ACCESSIBILITY IMPROV-
 MENTS AND SHOW COST OF EACH TO DETERMINE
 HOW MUCH OF THE CONTRACT WAS SPENT FOR
 THESE ITEMS.
 2) FROM PERVIOUS REVIEW: SHT P-2 WATER
 HEATER DETAIL. THERMAL EXPANSION CONTROL
 IS NOT ACHEIVED WITH A HEAT TRAP. EXPAN-
 SION CONTROL REQUIRED BY SECTION 607.3.2
 IS ACCOMPLISHED WITH AN EXPANSION TANK.
 PLEASE CHANGE DETAIL.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-06 Cont ID  
Sent By kstevens Date 2003-01-06 Time 09:45 Rev Time 1.50
Received By kstevens Date 2003-01-06 Time 09:44 Sent To  
Notes
2003-01-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT AD-1 ALL CAPPED PLUMBING SHALL BE
 INSPECTED PRIOR TO COVERING.
 2) SHT A-1 TOILET ROOM #153, PER SECTION
 11-4.1.6(1) ALL SPACES SHALL BE ACCESS-
 IBLE. PER 1-4.1.6(2) 20% ABOVE CONTRACT
 SHALL BE SPENT TO BRING SPACES UP TO NEW
 CONSTRUCTION REQUIREMENTS. PLEASE SHOW
 HOW THE $60,000 WILL BE SPENT.
 3) SHT A-4 DETAIL #04, SINK SHALL COMPLY
 WITH 11-4.24 AND ALL SUBSECTIONS. PLEASE
 PROVIDE DETAILS.
 4) SHT P-2 WATER HEATER DETAIL, PLEASE
 COMPLY WITH 607.3.2. SHOW THERMAL EX-
 PANSION CONTROL.
 5) SHT P-2 WATER RISER DIAGRAM, ALL
 WATER HAMMER ARRESTORS REQUIRED BY SEC.
 604.9 SHALL BE LOCATED NEAR THE FIXTURE,
 IN AN "EFFECTIVE RANGE" PER PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS, NOT AT
 THE TOP OF THE DROP IN THE CEILING AS
 SHOWN.
  
 REVIEW BY KEN STEVENS