| Plan Review Stops For Permit 02120549 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-09 |
Time |
14:20 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2002-12-09 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2002-12-09 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THAT THE GROUND CONDUCTORS | | | NOTED IN NOTES #4,8,& 12,FROM THE METERS | | | TO THE FIRST MEANS OF DISCONNECT CAN | | | NOT BE INSTALLED AS THEY WOULD CREATE A | | | PARALLEL GROUND PATH WITH THE NEUTRAL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
|