Plan Review Details - Permit 02120463
Plan Review Stops For Permit 02120463
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-09-22 Cont ID  
Sent By pkrauss Date 2003-10-14 Time 12:27 Rev Time 0.88
Received By jwitmer Date 2003-09-22 Time 17:54 Sent To  
Notes
2003-09-22 00:00:0009-22-03
 BUILDING PROVISO
 PERMIT:02120463
 712 PARK PLACE
  
 1)1507.3.8. ASPHALT SHINGLES LOW
 SLOPE ROOFING, UNDERLAYMENT APPLICATION
 FOR ROOF SLOPES FROM 2:12 UP TO 4:12,
 UNDERLAYMENT SHAL BE A MINIMUM OF TWO
 LAYERS APPLIED AS FOLLOWS:
 1) STARTING AT THE EAVE, A 19-INCH
 STRIP OF UNDERLAYMENT SHALL BE APPLIED
 PARALLEL WITH THE EAVE AND FASTENED
 SUFFICIENTLY TO STAY IN PLACE.
 2) STARTING AT THE EAVE, 36-INCH-WIDE
 STRIPS OF UNDERLAYMENT FELT SHALL BE
 APPLIED OVER LAPPING SUCCESSIVE SHEETS
 19 INCHES AND FASTENED SUFFICIENTLY TO
 STAY IN PLACE.
  
 2) PROVIDE A UPDATED NOTICE OF COMMENCE-
 MENT.
  
 3) PROVIDE PERMIT APPLICATION OR PROVIDE
 A NEW COPY.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-09-22 Cont ID  
Sent By jwitmer Date 2003-09-22 Time 15:12 Rev Time 0.75
Received By jwitmer Date 2003-09-22 Time 15:12 Sent To  
Notes
2003-09-22 00:00:00REV# 4 ADDITION OF WINDOWS TO MASTER
 BEDROOMJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-27 Cont ID  
Sent By pkrauss Date 2003-09-17 Time 09:26 Rev Time 3.50
Received By jwitmer Date 2003-01-27 Time 13:40 Sent To  
Notes
2003-01-27 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02120463
 ADD:712 PARK PLACE
 CONT: SERRAES CONSTRUCTION
 TEL: (561)848-6607
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) THE ONLY ADDRESS ON FILE FOR THIS PRO
 PERTY IS 712 PARK PLACE. TO RECEIVE A
 ADDRESS FOR THE BACK UNIT THE OWNER MUST
 REQUEST FOR THE ADDITIONAL ADDRESS FOR
 THE BACK UNIT, THEN ONCE THIS REQUEST
 HAS BEEN RESEARCHED THE ADDRESS WOULD
 BE GIVEN TO THE BACK UNIT.
  
 2)FIGURE 1606 WIND-BORNE DEBRIS
 REGION; INDICATES THAT W.P.B. CITY OF IS
 LOCATED IN THE 140 MPH ZONE. PLANS ARE
 TO INDICATE THIS.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)1606.1.1(6) SUBJECT TO THE LIMITATIONS
 OF 1606.1.1.1, 1606.1.4 AND 1606.1.6,
 THE PROVISIONS OF THE FC &PA GUIDE TO
 CONCRETE MASONRY RESIDENTIAL CONSTRUC-
 TION IN HIGH WIND AREA SHALL BE PERMIT-
 TED FOR APPLICABLE CONCRETE MASONARY
 BUILDINGS OF A GROUP R3 OCCUPANCY FOR A
 WIND SPEED OF 130 MPH OR LESS IN EXPOS-
 URE B OR 110 MPH OR LESS IN EXPOSURE C.
 THE 2001 FL. CODE REQUIRES A DESIGN
 PROFESSIONAL ENG. OR ARCH. TO DESIGN
 MASONARY BUILDINGS IN A 140 MPH WINDZONE
  
 5)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION. FORM 600B-01, ZONE SOUTH 7,8,& 9.
  
 6) PAGE 3 INDICATES A 8"X12" CONCRETE
 BEAM WITH 2 # 5'S/ THE DRAWING INDICATES
 4 REBARS, THE SPAN IS APPROX. 10'-0"
 WITH OUT ANY STIRRUPS? ACI 530 7.5.3.1
 SHEAR REINFORCEMENT SHALL BE PROVIDED
 PARALLEL TO THE DIRECTION OF APPLIED
 FORCE. SPACING OF SHEAR REINFORCEMENT
 SHALL NOT EXCEED THE LESSER OF D/2 OR
 48".
  
 7)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PAGE 12 INDICATES A 2X8 NAILER(PT) TO BE
 FASTENED TO A MASONARY WALL, THE PLAN
 DOES NOT INDICATE IS THIS BLOCK, A BEAM?
 THE PLAN CALLS FOR TAP-INS, SIMPSON DOES
 NOT CALL ANY OF THERE FASTENERS BY THIS
 NAME, PROVIDE A MODEL NUMBER? THE SPAC-
 ING CALLS OUT FOR A 4'-0" SPACING? GIVE
 CALCULATIONS FOR THE ANCHOR TO BE USED,
 INDICATING THE TRIBUTARY AREA & LOADING?
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop E ELECTRICAL
Rev No 7 Status N Date 2006-06-19 Cont ID  
Sent By dpalmer Date 2006-06-19 Time 16:22 Rev Time 0.00
Received By dpalmer Date 2006-06-19 Time 16:22 Sent To PC
Notes
2006-06-19 00:00:00PANEL SCHEDULE SUBMITTAL NOT REVIEWED,
 TO BE REVISED AT LATER DATE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-06-12 Cont ID  
Sent By dpalmer Date 2006-06-12 Time 12:22 Rev Time 0.00
Received By dpalmer Date 2006-06-12 Time 12:22 Sent To PC
Notes
2006-06-12 00:00:00REVISED KITCHEN.
 REDLINED 210.52C1-5
  
 PANEL SCHEDULE SUBMITTED NOT PART OF
 STAMPED REVS', AS IT DOES NOT MEET 408.4

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-05-18 Cont ID  
Sent By btrobaug Date 2006-05-18 Time 18:57 Rev Time 1.00
Received By btrobaug Date 2006-05-18 Time 18:09 Sent To PC
Notes
2006-05-18 00:00:00DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} IF THE CUT OF THE KITCHEN SUBMITTED
 PREVIOUSLY (3/15/06) IS TO BE REVIEWED
 WITHTHIS REVISION, PLEASE SIGN SAME PER
 104.2.1 FBC. ALSO INDICATE GFI'S PER
 210.8(A)(6)ON THE PLAN. THE ADDRESS IS
 WRONG ON THAT SHEET STILL.
  
 2} ALL 15 AMP BREAKERS ON THE PANEL
 SCHEDULE ARE FEEDING # 16 WIRE.
 SEE310.16 FOR CORRECT CONDUCTOR SIZES
 FOR OCP.
  
 THIS REVISION IS NOT A SUBMITTAL AND HAS
 A FEE DUE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-03-23 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 07:34 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 07:14 Sent To PC
Notes
2006-03-23 00:00:00************* UNSAT *************
  
 ** PLEASE SEE SOME NOTES NEED TO BE
 CORRECTED AND ALSO SEE BELOW FROM REVIEW
 DATED ON 10/8/03 WHICH WERE NEVER
 SUBMITTED FOR INFORMATION REQUIRED.
 PLEASE KNOW, NO FURTHER ELECTRICAL
 REVISIONS CAN BE DONE UNTIL ALL MIN FROM
 OCT 2003 AND RECENT REV'S ARE SUBMITTED.
  
  
 1)NOTE: PLEASE SEE ADDRESSING ON PLANS
 SHALL CORRELATE WITH APPLICATION AND OUR
 SYSTEM IN WHICH THE PERMIT WAS PULLED.
 THIS ADDRESS IS FOR 712, NOT 710 WHICH
 IS NOT WHAT THIS PERMIT WAS PULLED FOR.
  
 2)NOTE: PLEASE CORRELATE KITCHEN PLANS
 SUBMITTED. ONLY ONE LAYOUT IS NEEDED FOR
 CODE COMPLIANCE.
  
  
 3)NOTE: PLEASE SEE 210.52C1 FOR SPACING.
  
 4) NOTE: PLEASE SEE 210.8A6, AS ALL
 COUNTER SPACE RECEPTS IN KITCHENS SHALL
 BE SHOWN AS GFI/ GFI PROTECTED. IF ANY
 RECEPTS ARE DEDICATED (IE:) MICRO, DISP
 ETC, PLEASE IDENTIFY.
  
 5)NOTE: PLEASE SEE PLANS MENTIONS DRAWN
 BY AND CONTAINS THE PRINTED NAME,
 HOWEVER PLANS ARE ALSO REQUIRED TO BE
 SIGNED BY THAT PERSON.
 FBC ADMIN SECTION 104.2.1
  
 6)NOTE: PLEASE SEE SOME ROOMS WHERE THE
 PLANS INDICATE THE ENTIRE RECEPT BEING
 SWITCH. PLEASE KNOW, THIS IS ONLY
 PERMITTED IF AN ADDITIONAL RECEPT MEETS
 210.52. IF INDEED THESE ARE 1/2 SWITCH?
 PLEASE INDICATE.
  
 7) NOTE: PLEASE SEE NEC 210.12, PLANS
 INDICATE ARC FAULT FOR RECEPTS, WHICH IS
 OK AS THESE PLANS ORIGINALLY CAME IN
 UNDERTHE PREVIOUS REQUIREMENTS FOR
 AFCI PROTECTION, HOWEVER PLEASE SEE
 PLANS LENDS TO THE RECEPTS BEING PART OF
 THE LIGHTING CIRCUITS, WHICH WOULD THEN
 REQUIRE AFCI PROTECTION. PLEASE SEE RMS
 ARE BEING SHOWN WITH A SWITCHED LT
 FIXTIURE (NO FANS) AND SWITCHED RECEPTS.
 WHEN PANEL SCHEDULE AS REQUIRED IS
 SUBMITTED, THIS WILL BE VERIFIED. PLEASE
 SEE NOTES BELOW.
  
 ** NOTES FROM 10/8/03**
  
 ************ NOTES REDLINED *******
  
 PANELSCHEDULE WITH ALL OCP SIZES AND
 WIRE SIZES TO BE REVISED AND SUBMITTED
 BEFORE FINAL.
 SEE 250.32 FOR GROUNDING AT TWO OR MORE
 BDLGS.
 PLEASE SUBMIT ALL OTHER REVISIONS BEFORE
 ROUGH, AS STAMPED ON PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ****************************************
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-08 Cont ID  
Sent By dpalmer Date 2003-10-08 Time 07:24 Rev Time 0.50
Received By dpalmer Date 2003-10-08 Time 07:01 Sent To M
Notes
2003-10-08 00:00:00************ NOTES REDLINED *******
  
 PANELSCHEDULE WITH ALL OCP SIZES AND
 WIRE SIZES TO BE REVISED AND SUBMITTED
 BEFORE FINAL.
 SEE 250.32 FOR GROUNDING AT TWO OR MORE
 BDLGS.
 PLEASE SUBMIT ALL OTHER REVISIONS BEFORE
 ROUGH, AS STAMPED ON PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-10-03 Time 15:46 Rev Time 0.50
Received By dpalmer Date 2003-09-15 Time 06:50 Sent To P
Notes
2003-09-15 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE THAT ORIG PERMIT
 APPLICATION DID NOT COME BACK IN W/
 PACKAGE. PLEASE SUBMIT PERMIT APPL.
 PLEASE ALSO SEE THAT PLANS ARE STILL
 SHOWING 710 PARK PL??? PERMIT APPL AND
 PROPERTY ID USED IS FOR 712 PK PL??
 PLEASE SEE THAT WORK WAS ALREADY DONE ON
 712 ON PREVIOUS PERMITS?
 PLEASE CORRELATE AND CORRECT.
  
 2)NOTE: PLEASE SEE THAT NOC SUBMITTED
 HAS SINCE EXPIRED. NOC IOS FROM JAN 2001
 A NEW RECORDED NOC WILL BE REQ'D BEFORE
 PICKING UP PERMIT.
  
 3)NOTE: PLEASE SEE THAT SD'S ARE STILL
 MISSING INSIDE BEDROOMS, INCLUDING DEN,
 WHICH IS AN ADAPTABLE BEDRM.
 NFPA-72
  
 4)NOTE: PLEASE SEE THAT PLANS NEED TO BE
 STAMPED FROM HISTORIC AGAIN. NEW SETS
 WERE SUBMITTED AND CHANGES MADE. ALSO
 NEEDS TO GO BACK TO OTHER TRADES DUE TO
 NEW PLANS AND CHANGES MADE.
  
 5)NOTE: PLEASE SEE MISSING RECEPT ON
 KITCHEN COUNTERSPACE PER 210.52C1
 NEXT TO STOVE.
  
 6)NOTE: PLEASE SEE THAT LOAD CALCULATION
 -S WERE NOT SUBMITTED AND MISSING FROM
 SETS? 215.5
 PLEASE SHOW SERVICE LOCATION."ON MAIN
 HOUSE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE SEE THAT ONLY A 90 DAY EXTENTION
 HAS BEEN GRANTED BY THE BLDG OFFICAL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-03 Cont ID  
Sent By csiegber Date 2003-09-10 Time 11:01 Rev Time 1.00
Received By dpalmer Date 2003-01-03 Time 06:51 Sent To P
Notes
2003-01-03 00:00:00************* UNSAT ***************
  
 PLEASE NOTE, ADDRESS ON PLANS SHOW 710
 PARL PL.? PLEASE NOTE SURVEY AND LEGAL
 ADDRESS FOR BLDG IN PALM BEACH PROPERTY
 APPR. OFFICE IS LISTED AS 712? PLEASE
 CLARIFY HOW THIS KEEPS BEING APPLIED FOR
 UNDER 710?
 PLEASE ALSO NOTE CODES HAVE CHANGED
 SINCE THIS FIRST CAME IN, WHICH WILL
 HAVE AN AFFECT ON OTHER TRADES AND
 REVIEW COMMENTS ORIGINALLY SET FORTH
 UNDER OLD PERMIT # WHICH EXPIRED.
  
 1)NOTE: PLEASE NOTE MISSING SD AT THE
 LOWER LEVEL IN THE VICINITY OF STAIRS.
 NFPA-72 8-1.4
 PLEASE ALSO NOTE MISSING TWO SD'S ON
 SECOND FLR, OUTSIDE BEDROOMS AND SD
 THAT NEEDS TO MOVED TO UPPER LEVEL OF
 STAIRS OUTSIDE SLEEPING ROOMS.NFPA-72
  
 2)NOTE: PLEASE CLARIFY WHAT APPEARS TO
 BE AN "ISLAND IN KITCHEN? IF SO, PLEASE
 SEE 210-52-C-2 ALSO TO BE GFI.
  
 3)NOTE: PLEASE CLARIFY PLANS SHOWING
 ALL GFI RECEPTS IN BEDROOMS? SINCE PLANS
 FIRST CAME THROUGH FOR REVIEW. AS OF
 JAN 1ST 2002, ARC FAULT BRKRS ARE REQ`D
 FOR ALL BEDROOM CIRCUITS AND ARE LISTED
 ON PANEL SCHEDULE. PER 210-12 NEC.
  
 4)NOTE: PLEASE CLARIFY HOW 2-5KW HEAT
 STRIPS ARE SHOWN AS 5600W ON LOAD CALCS?
  
 5)NOTE: PLEASE CLARIFY EQUIPMENT OUTSIDE
 GUEST RM. SHOWS A 220V AND 120V RECEPT?
 PLEASE NOTE, 2 AHU`S ARE ALREADY SHOWN.
  
 JUST A NOTE, IF THERE ARE GOING TO BE
 ANY CATV, TELEPHONE ORLOW SYSTEMS
 INSTALLED, PLEASE SHOW ON PLANS IN
 ORDER TO BE INCLUDED ON THIS APPLICATION
 PLEASE NOTE, IF DONE AT LATER DATE,
 SEPARATE PERMIT APPLICATION/PLANS WILL
 BE REQ`D.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 15:34 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 15:34 Sent To E
Notes
2006-06-19 00:00:00TO "DPALMER' DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-05-17 Cont ID  
Sent By adarroug Date 2006-05-17 Time 15:24 Rev Time 0.00
Received By adarroug Date 2006-05-17 Time 15:24 Sent To E
Notes
2006-05-17 00:00:00TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 10:14 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 10:14 Sent To E
Notes
2006-03-17 00:00:00TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-07-06 Cont ID  
Sent By adarroug Date 2005-07-06 Time 10:58 Rev Time 0.00
Received By adarroug Date 2005-07-06 Time 10:58 Sent To M
Notes
2005-07-06 00:00:00TO "PKRAUSS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 15:44 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 15:44 Sent To E
Notes
2003-10-03 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-10 Cont ID  
Sent By csiegber Date 2003-09-10 Time 11:01 Rev Time 0.00
Received By csiegber Date 2003-09-10 Time 11:01 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-26 Cont ID  
Sent By csiegber Date 2003-08-26 Time 11:55 Rev Time 0.00
Received By csiegber Date 2003-08-26 Time 11:55 Sent To E
Notes
2003-08-26 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-02 Cont ID  
Sent By dpalmer Date 2003-01-02 Time 12:16 Rev Time 0.00
Received By dpalmer Date   Time   Sent To E
Notes
2003-01-02 00:00:00TO DV PALMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 17:30 Rev Time 0.00
Received By btrobaug Date 2002-12-05 Time 17:30 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-07-14 Cont ID  
Sent By prafter Date 2005-07-14 Time 10:33 Rev Time 0.75
Received By prafter Date 2005-07-14 Time 10:33 Sent To  
Notes
2005-07-14 00:00:00MECH. PLAN REVISION:
  
 PROVISO:1. PROVIDE FOR AUX. DRAIN
 PANS WITH PROTECTION. 2003 FBC/M 307.2.3
 .
  
 2. DRYER VENT TO CONFORM WITH 2003
 FBC/M SECTION 504 .
  
 PAT RAFTER 561/805/6728 OR 8056719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-09 Cont ID  
Sent By dpalmer Date 2003-10-08 Time 07:24 Rev Time 0.33
Received By pkrauss Date 2003-10-09 Time 12:12 Sent To B
Notes
2003-10-09 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-09-17 Cont ID  
Sent By pkrauss Date 2003-09-17 Time 09:09 Rev Time 0.35
Received By pkrauss Date 2003-09-17 Time 09:08 Sent To B
Notes
2003-09-17 00:00:00PROVISO:
 PROVIDE LOCATION, SIZE OF RETURN AIR
 DUCT AND GRILLE FOR AHU #1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-01-16 Cont ID  
Sent By kstevens Date 2003-09-15 Time 18:44 Rev Time 0.40
Received By pkrauss Date 2003-01-16 Time 14:41 Sent To B
Notes
2003-01-16 00:00:00MECHANICAL PERMIT 02120464

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-15 Cont ID  
Sent By pkrauss Date 2003-09-17 Time 09:10 Rev Time 0.33
Received By kstevens Date 2003-09-15 Time 18:44 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-01-15 Cont ID  
Sent By dpalmer Date 2003-09-15 Time 06:50 Rev Time 0.33
Received By kstevens Date 2003-01-15 Time 12:17 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-01-02 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 17:30 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***