| 2002-12-18 00:00:00 | 1) THE EMERGENCY VOICE MESSAGE IS TO |
| | BE REVISED, CHANGE THE WORD FIRE TO AN |
| | EMERGENCY HAS BEEN REPORTED. ALSO ADD |
| | DO NOT USE THE ELEVATORS. |
| | |
| | 2) PLEASE PROVIDE A COPY OF THE SIGNED |
| | CONTRACT FOR THE FIRE ALARM SYSTEM. |
| | THE VALUE OF THE JOB SHOULD INCLUDE |
| | ALL PARTS AND LABOR. |
| | |
| | 3) PLEASE ADD A NOTE TO THE PLANS, THAT |
| | FIRE ALARM DEVICES ARE NOT TO BE |
| | INSTALLED UNTIL FINAL TRADE CLEAN-UP |
| | HAS BEEN PERFORMED. |
| | |
| | 4) PLEASE ADD A NOTE TO THE PLANS, THAT |
| | THE FIRE ALARM SYSTEM IS TO BE |
| | COMPLETELY TESTED AND APPROVED PRIOR TO |
| | SCHEDULING AN INSPECTION WITH FIRE |
| | RESCUE PERSONNEL. |
| | |
| | 5) PLANS DO NOT REFLECT TAMPER SWITCHES |
| | FOR ANY EXTERIOR BACKFLOW DEVICE CONTROL |
| | VALVES FOR THE FIRE SYSTEM. PLEASE |
| | INDICATE THIS ON THE PLANS. |
| | |
| | 6) WHERE ARE THE TAMPER SWITCHES FOR |
| | THE TRASH CHUTE AND ELEVATOR SPRINKLER |
| | PIPING. |
| | |
| | 7) ALL ROOMS PLANNED FOR THE HANDICAPPED |
| | MUST BE EQUIPPED WITH SPEAKER STROBES. |
| | PLEASE ADVISE LOCATIONS. |
| | |
| | 8) THE REQUIRED FIRE ALARM SYSTEM IS |
| | TO BE MONITORED BY A LICENSED UL LISTED |
| | CENTRAL STATION APPROVED BY THE FIRE |
| | RESCUE DEPARTMENT. SIGNALS THAT ARE TO |
| | BE RECEIVED INCLUDE GENERAL ALARM, |
| | SUPERVISORY, TROUBLE, AND WATERFLOW |
| | ALARM. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |