Plan Review Details - Permit 02120294
Plan Review Stops For Permit 02120294
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-24 Cont ID  
Sent By jleech Date 2002-12-17 Time 20:15 Rev Time 0.25
Received By dpalmer Date 2002-12-24 Time 06:05 Sent To B
Notes
2002-12-24 00:00:00*********** NOTES REDLINED ***********
  
 1) SD NOT PERMITTED IN KITCHEN PER
 NFPA-72 8-1.4.1.6
 2)MISSING EQUIPMENT GROUND BETWEEN MAIN
 AND PANEL. SIZE PER 250-122
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-05 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 17:24 Rev Time 0.00
Received By btrobaug Date 2002-12-05 Time 17:24 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-14 Cont ID  
Sent By hmoser Date 2002-12-14 Time 09:59 Rev Time 0.33
Received By hmoser Date 2002-12-14 Time 09:59 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-17 Cont ID  
Sent By hmoser Date 2002-12-14 Time 09:59 Rev Time 0.33
Received By jleech Date 2002-12-17 Time 20:14 Sent To E
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-06 Cont ID  
Sent By lhatten Date 2003-01-06 Time 20:21 Rev Time 2.50
Received By lhatten Date 2003-01-05 Time 20:20 Sent To  
Notes
2003-01-06 00:00:00REVIEW & STAMPED PLANS 01/05/2003
 CALC. FEES & PRINT CARD 01/06/2003

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-05 Time 17:26 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***