| 2003-01-02 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| | SHUTTERS UNDER A SEPARATE PERMIT. |
| | 2-FLOOD ZONE A8. NEED TO PROVIDE THE |
| | ELEVATION CERTIFICATE. |
| | 3-SHEET A-1: REVISE NOTE #24. SEE SEC. |
| | 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. |
| | **NOTE: HANDRAIL AND GUARDRAILS ARE NOT |
| | THE SAME THING. |
| | 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE |
| | THICKNESS IS LESS THAN 0.25". SECTION |
| | 2405.2.2 FBC 2001. |
| | 5-SHEET A-4: REVISE NOTE #1. SEE SECTION |
| | 1007.5.1 FBC 2001 FOR HANDRAIL HEIGHT. |
| | NOTE: HANDRAIL AND GUARDRAIL ARE NOT |
| | THE SAME THING. |
| | 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| | AT ALL CONCEALED SPACES AS REQUIRED BY |
| | SEC. 2305.1.4 FBC 2001. |
| | 7-PROVIDE COMPLETE DETAIL/SECTION FOR |
| | CONNECTION AT TOP OF COLUMN BETWEEN |
| | GARAGE AND KITCHEN. CLARIFY HOW IS |
| | COLUMN TOP CONNECTOR RECEIVING THE TWO |
| | GIRDER TRUSSES COMING FROM DIFFERENT |
| | POINTS. SEC. 104.2.1.2 CITY AMENDMENTS |
| | 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL |
| | WALL SECTIONS FOR FIRECUT REQUIREMENTS |
| | SEC. 2305.4 FBC 2001. |
| | 9-DETAIL R19: CLEARLY SPECIFY ALL CONNEC |
| | TORS. ROOF FRAMING PLAN DOESN'T SPEC |
| | THEM. SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER |
| | FOR GARAGE DOOR STRUCTURAL BUCK DETAIL |
| | SE. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 11-PROVIDE SOIL TEST REPORT. |