| 2003-01-09 00:00:00 | BUILDING REVIEW PROVISO: |
| | 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| | SHUTTERS UNDER A SEPARATE PERMIT. |
| | 2-FLOD ZONE A9: NEED TO PROVIDE THE |
| | ELEVATION CERTIFICATE. |
| | 3-SHEET A-1: REVISE/CLARIFY NOTE #24. |
| | SEE SEC. 1007.5.1 FBC 2001 FOR HEIGHT |
| | OF HANDRAILS.**NOTE: HANDRAILS AND |
| | GUARDRAILS ARE NOT THE SAME. |
| | 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE |
| | THICKNESS IS LESS THAN 0.25". SECTION |
| | 2405.2.2 FBC 2001. |
| | 5-SHEET A-4: REVISE/CLARIFY NOTE #1. SEE |
| | SEC. 1007.5.1 FBC 2001 FOR HEIGHT OF |
| | HANDRAILS. **NOTE: HANDRAILS AND |
| | GUARDRAILS ARE NOT THE SAME. |
| | 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING |
| | AT ALL CONCEALED SPACES AS REQUIRED BY |
| | SEC. 2305.1.4 FBC 2001. |
| | 7-PROVIDE COMPLETE DETAIL/SECTION FOR |
| | CONNECTION AT TOP OF COLUMN LOCATED |
| | BETWEEN GARAGE AND KITCHEN. CLARIFY |
| | HOW IS SPECIFIED STRAP HOLDING THE |
| | TWO GIRDER TRUSSES. SECTION 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL |
| | WALL SECTIONS FOR FIRECUT REQUIREMENTS |
| | SEC. 2305.4 FBC 2001. |
| | 9-DETAIL R19: CLEARLY SPECIFY ALL CONNEC |
| | TORS. ROOF FRAMING PLAN DOESN'T SHOW |
| | THEM.SEC. 104.2.1.2 CITY AMENDMENTS. |
| | 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER |
| | FOR GARAGE DOOR STRUCTURAL BUCK DETAIL |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |