Plan Review Details - Permit 02120165
Plan Review Stops For Permit 02120165
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-30 Cont ID  
Sent By hmoser Date 2002-12-28 Time 07:00 Rev Time 0.25
Received By dpalmer Date 2002-12-30 Time 18:49 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-02 Cont ID  
Sent By shernand Date 2003-05-02 Time 18:04 Rev Time 0.00
Received By shernand Date 2003-05-02 Time 18:04 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:17 Rev Time 0.00
Received By btrobaug Date 2002-12-04 Time 17:16 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-05-08 Cont ID  
Sent By pkrauss Date 2003-05-08 Time 09:11 Rev Time 0.25
Received By pkrauss Date 2003-05-08 Time 09:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-28 Cont ID  
Sent By shernand Date 2003-05-02 Time 18:04 Rev Time 0.25
Received By hmoser Date 2002-12-28 Time 07:00 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-17 Cont ID  
Sent By sgraham Date 2002-12-12 Time 09:57 Rev Time 0.25
Received By jleech Date 2002-12-17 Time 17:11 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2003-01-08 Cont ID  
Sent By jgomez Date 2003-01-08 Time 17:40 Rev Time 2.50
Received By jgomez Date 2003-01-08 Time 17:40 Sent To  
Notes
2003-01-08 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8: WILL NEED TO PROVIDE
 THE ELEVATION CERTIFICATE.
 3-SHEET A-1: REVISE/CLARIFY NOTE #24.
 SEE SEC. 1007.5.1 FBC 2001.
 NOTE: HANDRAIL AND GUARDRAIL ARE NOT
 THE SAME.
 4-GLASS BLOCK TO BE SAFETY GLASS IF FACE
 THICKNESS IS LESS THAN 0.25". SECTION
 2405.2.2 FBC 2001.
 5-SHEET A-4: REVISE/CLARIFY NOTE #1. SEE
 SEC. 1007.5.1 FBC 2001.
 NOTE: HANDRAIL AND GUARDRAIL ARE NOT
 THE SAME.
 6-PROVIDE GENERAL SPECS FOR FIREBLOCKING
 AT ALL CONCEALED SPACES AS REQUIRED BY
 SEC. 2305.1.4 FBC 2001.
 7-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION AT TOP OF COLUMN LOCATED
 BETWEEN GARAGE & KITCHEN. CLARIFY HOW
 IS COLUMN TOP CONNECTOR RECEIVING THE
 TWO GIRDER TRUSSES. SEE FLOOR FRAMING
 PLAN. SEC. 104.2.1.2 CITY AMENDMENTS.
 8-SHEET S-3: PROVIDE SPECS ON STRUCTURAL
 WALL SECTIONS FOR FIRECUT REQUIREMENTS
 SEC. 2305.4 FBC 2001.
 9-DETAIL R19: CLEARLY SPECIFY ALL
 CONNECTORS. ROOF FRAMING PLAN DOESN'T
 SPECIFY THEM.SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 10-SPECIFY SIZE OF ANCHOR BOLT & WASHER
 FOR GARAGE DOOR STRUCTURAL BUCK DETAIL
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:17 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***