| 2002-12-09 00:00:00 | ************ UNSAT ******************* |
| | |
| | 1)NOTE: PLEASE NOTE CIRCUITING FOR |
| | EM/EX LTS NEED TO BE ON THE SAME CIRCUIT |
| | (S) AS LIGHTING ON THOSE AREAS. |
| | 700-12E |
| | |
| | 2)NOTW: PLEASE NOTE, NO PANEL SCHEDULES |
| | SUBMITTED FOR NEW PANELS? |
| | PLEASE SUBMIT AND CORRELATE WITH PLANS. |
| | |
| | 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS |
| | FOR ENTIRE SERVICE. PLEASE NOTE, |
| | RISER MENTIONS A EXIST 800A SERVICE |
| | COMING IN. PLEASE NOTE 300MCM ARE |
| | ONLY RATED AT 285A`S PER 310-16/110-14 |
| | THIS PUTS SERVICE AT 600A`S. |
| | NO LOAD CALCS WERE SUBMITTED FOR NEW |
| | PANELS AND LOADS BEING ADDED. |
| | PLEASE NOTE, ALL CONTINUOS LOADS AT 125% |
| | |
| | 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS |
| | #2 BEING FED TO 200A DSIC AND CHNAGE |
| | AHS BEEN HAND WRITTEN ON PLAN CHANGING |
| | FROM 100A TO 200A. |
| | PLEASE NOTE, ANY HANDWRITTEN CHANGES ON' |
| | PLANS, MUST BE DONE BY THE ARCH OF |
| | RECORD. 481.221. |
| | |
| | 5)NOTE: PLEASE CLARIFY MEANS OF EQUIP- |
| | -MENT GROUNDING BETWEEN MAIN DISC`S AND |
| | PANELS. SIZE PER 250-122 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMAITON FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |