Plan Review Details - Permit 02120090
Plan Review Stops For Permit 02120090
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-04-10 Cont ID  
Sent By dpalmer Date 2003-04-10 Time 15:57 Rev Time 0.50
Received By dpalmer Date 2003-04-10 Time 15:57 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-24 Cont ID  
Sent By shernand Date 2003-04-07 Time 16:12 Rev Time 0.50
Received By dpalmer Date 2002-12-24 Time 13:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-09 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 11:32 Rev Time 1.00
Received By dpalmer Date 2002-12-09 Time 10:33 Sent To  
Notes
2002-12-09 00:00:00************ UNSAT *******************
  
 1)NOTE: PLEASE NOTE CIRCUITING FOR
 EM/EX LTS NEED TO BE ON THE SAME CIRCUIT
 (S) AS LIGHTING ON THOSE AREAS.
 700-12E
  
 2)NOTW: PLEASE NOTE, NO PANEL SCHEDULES
 SUBMITTED FOR NEW PANELS?
 PLEASE SUBMIT AND CORRELATE WITH PLANS.
  
 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 FOR ENTIRE SERVICE. PLEASE NOTE,
 RISER MENTIONS A EXIST 800A SERVICE
 COMING IN. PLEASE NOTE 300MCM ARE
 ONLY RATED AT 285A`S PER 310-16/110-14
 THIS PUTS SERVICE AT 600A`S.
 NO LOAD CALCS WERE SUBMITTED FOR NEW
 PANELS AND LOADS BEING ADDED.
 PLEASE NOTE, ALL CONTINUOS LOADS AT 125%
  
 4)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 #2 BEING FED TO 200A DSIC AND CHNAGE
 AHS BEEN HAND WRITTEN ON PLAN CHANGING
 FROM 100A TO 200A.
 PLEASE NOTE, ANY HANDWRITTEN CHANGES ON'
 PLANS, MUST BE DONE BY THE ARCH OF
 RECORD. 481.221.
  
 5)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN MAIN DISC`S AND
 PANELS. SIZE PER 250-122
  
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-04-22 Cont ID  
Sent By nmccray Date 2003-04-22 Time 15:10 Rev Time 0.00
Received By nmccray Date 2003-04-22 Time 15:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-04-07 Cont ID  
Sent By shernand Date 2003-04-07 Time 16:12 Rev Time 0.00
Received By shernand Date 2003-04-07 Time 16:12 Sent To E
Notes
2003-04-07 00:00:00DPALMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-19 Cont ID  
Sent By btrobaug Date 2002-12-19 Time 11:32 Rev Time 0.00
Received By btrobaug Date 2002-12-19 Time 11:32 Sent To E
Notes
2002-12-19 00:00:00TO DVP./WRT.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved