Plan Review Details - Permit 02120069
Plan Review Stops For Permit 02120069
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-01-23 Cont ID  
Sent By lsmith Date 2003-01-23 Time 11:58 Rev Time 0.50
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-16 Cont ID  
Sent By kstevens Date 2002-12-14 Time 20:01 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-12-16 00:00:00BUILDING REVIEW NOTES:
  
 1. NEED COPY OF CONTRACT TO VERIFY
 VALUE FOR PERMIT.
 2. NEED DETAIL SHOWN ON DRAWINGS FOR
 METHOD OF PROTECTING POOL AREA FROM
 HOUSE PER FBC 424.2.17
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-11 Cont ID  
Sent By dpalmer Date 2002-12-11 Time 07:02 Rev Time 0.25
Received By dpalmer Date 2002-12-11 Time 07:02 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-02 Cont ID  
Sent By btrobaug Date 2002-12-02 Time 17:36 Rev Time 0.00
Received By btrobaug Date 2002-12-02 Time 17:35 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-05-27 Cont ID  
Sent By pschmitz Date 2003-05-27 Time 10:56 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2003-05-27 00:00:00LETTER FROM ENGINEER RE: MAIN DRAIN
 INSPECTION OK. PES

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-23 Cont ID  
Sent By kstevens Date 2003-01-23 Time 14:39 Rev Time 0.75
Received By kstevens Date 2003-01-23 Time 14:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-14 Cont ID  
Sent By dpalmer Date 2002-12-11 Time 07:18 Rev Time 0.50
Received By kstevens Date 2002-12-14 Time 19:58 Sent To B
Notes
2002-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92, AND NSPI-5. (ADD TO
 NOTES)
 2) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 3) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 4) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 17) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-02 Time 17:36 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***