Plan Review Details - Permit 02120042
Plan Review Stops For Permit 02120042
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 13:59 Rev Time 0.00
Received By rbrown Date 2003-02-07 Time 10:11 Sent To  
Notes
2003-02-07 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 --PROVISO--
 FBC 1707.4SUBMIT A PRODUCT APPROVAL
 FOR THE NEW FRONT ENTRANCE DOOR.
  
 --PROVISO--
 FBC 1707.4.5.2STRUCTURAL MULLION.
 DETAIL 5 ON SHEET 2 SHALL INCORPORATE
 FRAMING ANCHORS TO RESIST LATERAL WIND
 LOAD IN SHEAR.SEE RED-LINED PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-14 Cont ID  
Sent By kstevens Date 2003-02-06 Time 12:29 Rev Time 0.00
Received By rbrown Date 2003-01-14 Time 14:48 Sent To  
Notes
2003-01-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 3401.7.2.6AS THE COST OF THE
 PROPOSED REPAIRS AND ALTERATIONS EXCEED
 50% OF THE VALUE OF THE EXISTING
 BUILDING,THE BUILDING SHALL BE MADE TO
 CONFORM TO THE CODE REQUIREMENTS FOR A
 NEW BUILDING, WITH THE STRUCTURAL
 EXCEPTIONS LISTED IN THIS SECTION OF THE
 CODE.MORE INFORMATION IS REQUIRED ON
 THE PLANS, TO DEMONSTRATE COMPLIANCE.
  
 2) FBC* 101.4.2 AMEND THE PLANS TO STATE
 THAT THE PROPOSED WORK IS DESIGNED TO
 FLORIDA BUILDING CODE 2001.
  
 3) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS (REF:
 COMMENT 1)
  
 4) FBC 1606.1.7WIND LOAD.THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.
  
 5) WINDOW PRODUCT APPROVAL.THE WINDOW
 SCHEDULE,ON DRAWING SHEET 1, SPECIFIES
 'PGT' SINGLE HUNG WINDOWS AS INDICATED
 ON THE ELEVATIONS.THE SUBMITTED 'PGT'
 PRODUCT APPROVAL NOA# 02-0327.04 IS FOR
 CASEMENT WINDOWS AND THEREFOR IS NOT
 APPLICABLE.SUBMIT AN APPROPRIATE
 WINDOW PRODUCT APPROVAL.
  
 6) FBC 1707.4.5.1THE PROPOSED WINDOW
 MULLIONS SHALL BE PART OF THE WINDOW
 PRODUCT APPROVAL TO BE SUBMITTED, OR
 SHALL BE SUBJECT OF A SEPARATE PRODUCT
 APPROVAL.
  
 7) FBC 1707.4SUBMIT A PRODUCT
 APPROVAL FOR THE NEW EXTERIOR DOOR.
  
 8) FBC* 104.2.1.2FROM DETAILS 1, 2 & 3
 ON SHEET 2, IT APPEARS THAT THE EXISTING
 ROOF SPANS IN THE EAST-WEST DIRECTION.
 THE PROPOSED ROOF SUPPORT SCHEME WILL
 REDIRECT THE ROOF LOADS TO THE NORTH AND
 SOUTH WALLS WHICH WERE NOT PREVIOUSLY
 LOADED THAT WAY. SUBMIT FURTHER DETAILS,
 INCLUDING THE HEADER ARRANGEMENT OVER
 THE WINDOWS AND DOORS IN THE NORTH AND
 SOUTH WALLS, TO JUSTIFY THE PROPOSAL.
  
 9) FBC 1707.4.4.3WINDOW AND DOOR BUCKS
 SUBMIT DETAILS TO SHOW ANCHORING OF THE
 DOORS AND WINDOWS TO THEIR ROUGH OPENING
  
 10) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 06:34 Rev Time 0.33
Received By dpalmer Date 2003-02-06 Time 06:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-01-03 Cont ID  
Sent By btrobaug Date 2003-01-30 Time 15:33 Rev Time 0.50
Received By dpalmer Date 2003-01-03 Time 16:29 Sent To B
Notes
2003-01-03 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATING(S) FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 110-9/215-5
  
 2)NOTE: PLEASE CLARFIFY EXACT LENGTH OF
 CONDUCTORS GOING OVERHEAD "INSIDE" THE
 BLDG. PLEASE NOTE PER 210-70 LOCAL
 AMENDMENTS, NO MORETHAN 8" OF UNPROTECT-
 ED CONDUCTORS INSIDE PERMITTED.
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 ON PANEL
 SCHEDULE.
  
  
 4)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS BETWEEN PANEL AND
 A/C UNITS.
  
 5)NOTE: PLEASE NOTE MISSING FRONT AND
 REAR RECEPTS PER 210-52E
  
  
 6)NOTE: PLEASE SHOW NEUTRAL LOAD CALCS
 FOR DOWN SIZING NEUTRAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-27 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2003-02-27 Time 13:59 Sent To B
Notes
2003-02-27 00:00:00TO RBOERTBROWN.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-30 Cont ID  
Sent By btrobaug Date 2003-01-30 Time 15:33 Rev Time 0.00
Received By btrobaug Date 2003-01-29 Time 15:32 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-02 Cont ID  
Sent By btrobaug Date 2002-12-02 Time 17:12 Rev Time 0.00
Received By btrobaug Date 2002-12-02 Time 17:12 Sent To P
Notes
2002-12-02 00:00:00IN BOX./WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-12-11 Cont ID  
Sent By kstevens Date 2002-12-07 Time 10:25 Rev Time 0.33
Received By hmoser Date 2002-12-11 Time 17:58 Sent To B
Notes
2002-12-11 00:00:00NO MECHANICAL PLANS

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-06 Cont ID  
Sent By kstevens Date 2003-02-06 Time 12:29 Rev Time 0.33
Received By kstevens Date 2003-02-06 Time 12:29 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-07 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 06:34 Rev Time 0.25
Received By kstevens Date 2002-12-07 Time 10:20 Sent To M
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy