Plan Review Details - Permit 02111723
Plan Review Stops For Permit 02111723
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-11 Cont ID  
Sent By hpiskura Date 2003-02-11 Time 10:31 Rev Time 0.00
Received By hpiskura Date 2003-02-11 Time 09:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-12-24 Cont ID  
Sent By lmartine Date 2002-12-24 Time 14:39 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2002-12-24 00:00:00SUBMIT DOOR SCHEDULE, MINIMUM CLEAR
 OPENING SHALL BE 32"

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-07 Cont ID  
Sent By dpalmer Date 2003-02-07 Time 06:52 Rev Time 0.25
Received By dpalmer Date 2003-02-07 Time 06:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-05 Cont ID  
Sent By dpalmer Date 2002-12-05 Time 07:08 Rev Time 0.50
Received By dpalmer Date 2002-12-05 Time 07:08 Sent To  
Notes
2002-12-05 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE CLARIFY LOADS. PLEASE
 CLARFIY LOADS SHOWN AT 125% ARE 8@180?
 WHICH LOAD ARE THESE? RECEPTS. PLEASE
 NOTE LIGHTING ARE CONSIDERED CONTINUOUS
 LOADS ALSO.IF 8@180 ARE RECEPTS?, PLEASE
 VERIFY COUNT.
  
 2)NOTE: PLEASE CLARIFY LOADS (KW) SHOWN
 IN VOLTAGE COLUMN?
  
 3)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXSITNG
 EM LTS. PLEASE ALSO VERIFY LTS REQ`D
 ON SAME BRANCH CIRCUIT AS NORMAL LTS
 PER 700-12E
  
 5)NOTE: PLEASE CLARIFY NEW OR EXSITING
 SIGN CIRCUIT PER 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-02-06 Cont ID  
Sent By mcarsill Date 2003-02-06 Time 11:34 Rev Time 0.00
Received By mcarsill Date 2003-02-06 Time 11:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 11:02 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-30 Cont ID  
Sent By btrobaug Date 2003-01-30 Time 15:49 Rev Time 0.00
Received By btrobaug Date 2003-01-28 Time 15:49 Sent To  
Notes
2003-01-30 00:00:00COM BOARD #27./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2002-11-25 Time 17:51 Rev Time 0.00
Received By btrobaug Date 2002-11-25 Time 17:51 Sent To  
Notes
2002-11-25 00:00:00TO COMM BOARD # 46./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-12 Cont ID  
Sent By pkrauss Date 2003-02-12 Time 14:39 Rev Time 0.40
Received By pkrauss Date 2003-02-12 Time 14:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By pkrauss Date 2002-12-23 Time 13:43 Rev Time 0.40
Received By pkrauss Date 2002-12-23 Time 13:43 Sent To  
Notes
2002-12-23 00:00:00PROVISO:
  
 PLAN SHEET #3, CONDENSING UNIT ON THE
 ROOF STRUCTURE SHALL BE IN ACCORDANCE
 WITH 2001 FBC TABLE 1511.7.
  
 SHOP DRAWINGS SUBMITTED BY BY WALLEN
 SERVICES ARE NOT APPROVED UNLESS SEALED
 BY THE ENGINEER OF RECORD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-02-05 Cont ID  
Sent By kstevens Date 2003-02-05 Time 07:56 Rev Time 0.25
Received By kstevens Date 2003-02-05 Time 07:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-23 Cont ID  
Sent By kstevens Date 2002-12-23 Time 09:51 Rev Time 0.75
Received By kstevens Date 2002-12-23 Time 09:51 Sent To  
Notes
2002-12-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) RPZ BACKFLOW REQUIRED. MAXIMUM 4'
 ABOVE FINISHED FLOOR FOR SERVICE AND
 TESTING. FLOOR SINK REQUIRED FOR INDIR-
 ECT DRAINAGE FROM BACKFLOW.
 2) PLEASE SUBMIT A WATER RISER DIAGRAM.
 IF SHOCK CONTROL USED IT WILL BE PER
 SEC 604.9, AND WILL BE LOCATED NEAR THE
 FIXTURE NOT AT THE TOP OF DROPS IN CEIL-
 ING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377