Plan Review Details - Permit 02111690
Plan Review Stops For Permit 02111690
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-19 Cont ID  
Sent By dpalmer Date 2003-05-19 Time 07:53 Rev Time 0.25
Received By dpalmer Date 2003-05-19 Time 07:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-05-16 Time 09:12 Rev Time 0.75
Received By dpalmer Date 2003-04-03 Time 06:14 Sent To P
Notes
2003-04-03 00:00:00************** UNSAT ***************
  
 PLEASE SEE ORIG NOTES
  
 1)NOTE: PLEASE SEE 225-31 FOR MEANS
 OF DISC AT ANY BLDG FED FROM ANOTHER.
 PLEASE ALSO CLARIFY HOW BRANCH CIRCUITS
 WOULD BE FED TO DETACHED BLDG W/OUT
 PANELS IN MAIN HOUSE?
  
 2)NOTE: PLEASE SEE 250-31 FOR GROUNDING
 OF DETACHED BLDGS.
  
 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2,
 PLANS STILL MISSING SD`S INSIDE ALL
 SLEEPING ROOMS. PLEASE ALSO NOTE, SD
 ON EACH LEVEL OF A MULTI-LEVEL RES HOUSE
 IN THE IMMEDIATE VICINITY OF STAIRWAY
 NFPA-72 2-5.2.1.6
 PLEASE ALSO NOTE, SD`S ARE NOT PERMITTED
 IN KITCHEN, MAY BE HEAT IF DESIRED.
 SD`S ARE TO BE A MIN OF 3' FROM BATH
 DOORS.
  
 4)NOTE: PLEASE SEE 210-52 FOR RECEPT
 SPACING ALONG WALLS.PLEASE SEE THAT
 THERE ARE SOME MISSING ON SECOND FLOOR.
 ALSO 210-52E REAR OF DWELLING
 5)NOTE: PLEASE SEE MISSING RECEPT FOR
 A/C COND UNITS. 210-63
  
 6)NOTE: PLEASE CLARIFY RISER, SHOWS
 HAND WRITTEN CHANGES THAT A& B ARE DISC`
 S? PANELS SHOW MLO? PLEASE INDICATE
 IF MCB AND PLEASE REF BACK TO NOTE#1.
  
 7)NOTE: PLEASE SEE FS/FAC 61G15-23.002,
 61G1-16.004, PLEASE SEE INFORMATION
 REQ`D FOR TITLE BLOCK ON PLANS THAT ARE
 SIGNED AND SEALED BY ARCH'S/ ENGINNERS.
 471/481.
  
 8)NOTE: PLEASE SEE MAX OCP FOR AHU#2,
 7.5KW @150%. MAX AT 2P50A. SHOWN AT 60A.
 PLEASE VERIFY.
 PLEASE ALSO SHOW ACCES TO AHU#1, SHOWN
 W/ ALL FOUR SIDE ENCLOSED? 110-26
  
 PLEASE ALSO SEE FS 553.80(2)(B) FOR
 PLANS AND RESPECT TO DESIGN PROFESSIONAL
 -S.. SEE LETTER ATTACHED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-23 Cont ID  
Sent By sthyng Date 2003-03-27 Time 15:11 Rev Time 1.00
Received By dpalmer Date 2002-12-23 Time 09:32 Sent To P
Notes
2002-12-23 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, PLANS NEED TO BE
 COMPLETED FOR REVIEW.
 PLEASE SEE THE FOLLOWING CODE ARTS. FOR
 REVIEW NOTES.
  
 NFPA-72 8-1.4
 NEC,
 230-72,230-71
 225-31
 220-16,210-52B
 250-66
 210-12
 210-52C-1
 210-52D,210-11-C1
 210-8A-6
  
 2)NOTE: PLEASE PROVIDE ALL ROOM
 DESIGNATIONS ON PLANS.
  
 3)NOTE: PLEASE DARKEN LINES ON PLANS.
  
 4)NOTE: PLEASE SIGN AND SEAL SECOND SET.
 481.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-05-16 Cont ID  
Sent By shernand Date 2003-05-16 Time 09:12 Rev Time 0.00
Received By shernand Date 2003-05-16 Time 09:12 Sent To E
Notes
2003-05-16 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-03-27 Cont ID  
Sent By sthyng Date 2003-03-27 Time 15:11 Rev Time 0.00
Received By sthyng Date 2003-03-27 Time 15:11 Sent To E
Notes
2003-03-27 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-22 Cont ID  
Sent By btrobaug Date 2002-11-22 Time 17:30 Rev Time 0.00
Received By btrobaug Date 2002-11-22 Time 17:30 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-05-27 Cont ID  
Sent By pkrauss Date 2003-05-27 Time 08:53 Rev Time 0.25
Received By pkrauss Date 2003-05-27 Time 08:53 Sent To R
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-04-09 Cont ID  
Sent By kstevens Date 2003-05-27 Time 08:47 Rev Time 0.40
Received By pkrauss Date 2003-04-09 Time 11:25 Sent To R
Notes
2003-04-09 00:00:00DENIED:1ST REVIEW DONE BY H. MOSER
  
 1.PLANS DO NOT INDICATE RETURN AIR
 DUCTS OR GRILLES.
  
 2.RETURN AIR DUCTS OR TRANSFER AIR
 REQUIRED FROM THE BEDROOM AREAS AS PER
 2001 FBC(M) 601.4.
  
 PLEASE NOTE SUFFICIENT SPACE SHALL BE
 PROVIDED FOR CONSTRUCTION, INSPECTION,
 CLEANING AND MAINTENANCE OF THE AIR
 HANDLING UNITS.4" MINIMUM AROUND THE
 AHU AS PER 2001 FBC(M) 603.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-01-11 Cont ID  
Sent By kstevens Date 2003-04-03 Time 18:15 Rev Time 0.50
Received By hmoser Date 2003-01-11 Time 10:09 Sent To R
Notes
2003-01-11 00:00:00PLAN DENIED
 NO ARCHITECT SEAL ON PLANS
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8221

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-05-24 Cont ID  
Sent By kstevens Date 2003-05-24 Time 08:46 Rev Time 0.25
Received By kstevens Date 2003-05-24 Time 08:46 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-04-03 Cont ID  
Sent By dpalmer Date 2003-05-19 Time 07:54 Rev Time 0.25
Received By kstevens Date 2003-04-03 Time 18:11 Sent To M
Notes
2003-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 ADMIN. CODE CHAPTER
 ONE & AMENDMENTS.
  
 1) SECTION 104.2 TWO OR MORE COPIES OF
 DRAWINGS REQUIRED. TWO COPIES OF SHEET
 #16 REQUIRED. PLEASE CHANGE OUT SHEET
 WITH RED LINES AND SUBMIT 2ND SHT 16
 WITH CHANGES FROM ARCHITECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-11 Cont ID  
Sent By dpalmer Date 2003-04-03 Time 06:14 Rev Time 0.66
Received By kstevens Date 2003-01-11 Time 05:18 Sent To M
Notes
2003-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 16 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE. PLEASE SEE RED LINE
 CORRECTIONS. TABLE 906.1 VENT FOR TUB
 EXCEEDS MAXIMUM DISTANCE OF FIXTURE TRAP
 FROM VENT. DRAIN LINE FROM BATH #2 SHALL
 TIE IN DOWN STREAM OF POWDER ROOM. NO
 TRAP SHOWN FOR WASH MACHINE.
 2) SHT 16 PLEASE SHOW THERMAL EXPANSION
 CONTROL, (EXPANSION TANK), AT WATER
 HEATER DETAIL. SECTION 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2003-05-27 Cont ID  
Sent By rmcdouga Date 2003-05-27 Time 15:24 Rev Time 3.00
Received By rmcdouga Date 2003-05-27 Time 15:24 Sent To  
Notes
2003-05-27 00:00:00BUILDING PROVISO
  
 1) SUBMIT PRODUCT APPROVALS FOR EXTERIOR
 WOOD DOORS PRIOR TO INSTALLING.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2003-04-10 Cont ID  
Sent By pkrauss Date 2003-05-27 Time 08:56 Rev Time 4.00
Received By rmcdouga Date 2003-04-10 Time 11:43 Sent To  
Notes
2003-04-10 00:00:00DENIED
  
 1) SEPARATE PERMIT IS REQUIRED FOR THE
 SITE WALL.
  
 2) SMOKE DETECTORS ARE REQUIRED TO BE
 LOCATED PER FBC 905.2.2.
  
 3)SPECIFY ATTIC VENTILLATION AS REQUIRED
 BY FBC 2309.7. THE NET FREE VENT AREA
 FOR THE EXISTING SLOPED ROOF GIVEN IS
 NOT ADEQUATE. (PROVIDE CALCULATIONS)
 SPECIFY THE VENTS FOR THE FLAT ROOFS AT
 THE GARAGE AND HOUSE AND FOR THE SLOPED
 ROOF AT THE TOWER.
  
 4) PROVIDE (2) COPIES OF A RECENT
 SURVEY.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - OUTSWING FIBERGLASS DOOR AT GARAGE
 - OUTSWING WOOD ENTRY DOOR AT FOYER
 - SINGLE HUNG WINDOWS
 PLANS SPECIFY ALL SINGLE HUNG WINDOWS.
 THE PRODUCT APPROVALS ARE REQUIRED TO BE
 APPROVED BY HISTORIC PRESEVATION. THE
 PRODUCT APPROVALS SUBMITTED WERE FOR
 FIXED WINDOWS AND CASEMENT WINDOWS. IF
 THESE ARE USED CHANGE PLANS AND HAVE
 APPROVED BY HISTORIC PRESERVATION.
  
 6) A SEPARATE PERMIT WITH ADDITIONAL FEE
 WILL BE REQUIRED FOR ROOFING. IT WAS NOT
 SIGNED FOR ON THE APPLICATION.
  
 7)SEVERAL OF THE TRUSSES ON SHEETS 7 & 8
 HAVE CONNECTOR #3 SPECIFIED, HOWEVER
 THERE IS NO #3 LISTED IN THE CONNECTOR
 SCHEDULE.
  
 8) ALL EXTERIOR GLAZING TO BE IMPACT
 RESISTANT OR PROTECTED WITH STORM PANELS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2003-01-23 Cont ID  
Sent By pkrauss Date 2003-04-09 Time 11:43 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-01-23 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SMOKE DETECTORS ARE REQUIRED TO BE
 LOCATED PER FBC 905.2.2.
  
 3) SPECIFY ATTIC VENTILATION AS REGUIRED
 BY FBC 2309.7.
  
 4) SPECIFY SIZE OF ATTIC ACCESSES. IN
 GARAGE AND EXISTING STRUCTURE. SEE FBC
 2309.6.
  
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE EXPOSURE CATEGORY AND
 INTERNAL PRESSURE COEFFICIENT.
  
 6) PROVIDE (2) COPIES OF A SURVEY.
  
 7) SPECIFY ON THE PLANS THAT THE WELDED
 WIRE MESH WILL BE SUPPORTED ON APPROVED
 MATERIAL AT 3' O.C. OR INDICATE LOCATION
 OF CONTROL JOINTS. SEE FBC 1909.3.
  
 8) THE GLAZED FRENCH DOORS ARE REQUIRED
 TO HAVE IMPACT RESISTANT GLAZING OR
 HAVE IMPACT PROTECTION PER FBC 1606.1.4.
  
 9) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. FOR ANY
 GLAZING THAT IS NOT IMPACT RATED.
  
 10) THE GROUND FLOOR ON SHEET 2 SHOWS AN
 EXTERIOR DOOR AND WINDOW AT THE MASTER
 BATH TUB. THE ELEVATION ON SHEET 10 ONLY
 SHOWS THE DOOR. ARE THE INTERIOR AND
 EXTERIOR DOORS OPENING TO A BATHTUB?
 PLEASE CLARIFY.
  
 11) PROVIDE A SECTION OR DETAIL OF THE
 6" CONCRETE BALCONY AT THE SECOND FLOOR
 ABOVE THE COURTYARD. SHOW HOW STEEL
 REINFORCING IS TIED TO MAIN STRUCTURE.
 SHOW GUARDRAIL HEIGHT, SPACING OF
 INTERMEDIATE RAILS, METHOD OF ATTACHMENT
 LOAD RESISTING REQUIREMENTS, ETC. SEE
 FBC 1015 AND 1608.2.2.
  
 12) ALL ROOMS USED FOR SLEEPING PURPOSES
 (INCLUDING PLAYROOM) ARE REQUIRED TO
 HAVE AN EMERGENCY ESCAPE AND RESCUE
 OPENING THAT COMPLIES WITH FBC 1005.4.
 NOTE: THE SECOND FLOOR MUST HAVE A NET
 CLEAR OPENING AREA OF 5.7 SQ.FT.
  
 13) PROVIDE AT LEAST ONE BATHROOM ON
 HABITABLE GRADE WITH A 29" CLEAR OPENING
 PER FBC CHAPTER 11.
  
 14) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR WINDOWS
 - EXTERIOR DOORS
 - GARAGE DOORS
 NOTE: ALL PRODUCT APPROVALS MUST BE
 REVIEWED AND APPROVED BY THE CITY OF WPB
 HISTORICAL DEPARTMENT.
  
 15) GLAZING WITHIN 3 FT. HORIZONTALLY OF
 A STANDING OR WALKING SURFACE AT A TUB
 OR SHOWER MUST BE SAFETY GLASS PER FBC
 2405.2. IMPACT RATED GLASS IS ACCEPTABLE
  
 16) THE CHIMNEY IS REQUIRED TO EXTEND
 AT LEAST 2 FT. HIGHER THAN ANY PORTION
 OF THE ROOF OR BUILDING THAT IS LOCATED
 WITHIN 10 FT. HORIZONTALLY OF SUCH
 CHIMNEY PER FBC 2804.2.4.
  
 17) PROVIDE A DETAIL OF THE WOOD FRAME
 INTERIOR LOAD BEARING WALLS. INDICATE
 THE CONNECTORS THAT WILL BE REQUIRED TO
 PROVIDE A CONTINOUS LOAD PATH TO THE
 FOUNDATION.
  
 18)INDICATE FIREBLOCKING WHERE CONCEALED
 SPACES AT WALLS INTERSECT FLOORS OR
 CEILINGS PER FBC 705.3.
  
 19) SPECIFY THE LOCATIONS AND MATERIAL
 THAT WILL BE USED TO PROVIDE
 DRAFTSTOPPING AT THE FLOOR/CEILING
 ASSEMBLY REQUIRED BY FBC 2305.2.
  
 20) PROVIDE BUCK ATTACHMENT DETAILS FOR
 WINDOWS, DOORS AND GARAGE DOORS. SEE FBC
 1707.4.4.1 AND 1707.4.4.2.
  
 21) THE WALL SECTION ON SHEET 14 SHOWS
 R-19 INSULATION AND THE ENERGY
 CALCULATIONS LIST R-30. PLEASE CORRECT.
  
 22) PROVIDE A HURRICANE ANCHOR SCHEDULE.
 SPECIFY THE ANCHORS AND CONNECTORS TO BE
 USED AND THE NATURE, LOCATION AND
 MAGNITUDE OF THE LOADS TO BE RESISTED
 FOR THE TRUSSES. INDICATE THE CONNECTORS
 TO BE USED FOR ALL BEAM TO COLUMN OR
 WALL ATTACHMENTS. SPECIFY CONNECTORS FOR
 LOAD PATH AT WOOD FRAME BEARING WALL ON
 BEAMS AT GARAGE.
  
 23) SPECIFY THE SPECIAL ROOF SHEATHING
 NAILING REQUIREMENTS REQUIRED BY THE
 CITY OF WPB AMENDMENTS TO FBC TABLE
 2306.1.
  
 24) PROVIDE DETAILS AND SPECIFICATIONS
 FOR INTERIOR STAIRS, HANDRAIL AND
 GUARDRAIL. INCLUDE HEIGHTS, BALUSTER
 SPACING, SIZE, GRASPABILITY, LOAD
 REQUIREMENTS, FIRE BLOCKING, ETC. SEE
 FBC 1007, 1015, 1026.5, 1608.2, 2305.1.4
 (3).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2003-01-14 Cont ID  
Sent By lmartine Date 2003-01-14 Time 11:39 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
2003-01-14 00:00:00PER GRACE AND ROBIN, OK TO APPROVE

Review Stop Z ZONING
Rev No 1 Status F Date 2002-12-11 Cont ID  
Sent By btrobaug Date 2002-11-22 Time 17:30 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-12-11 00:00:001. MUST HAVE 1000 SQ. FT OR 75%
 LANDSCAPINGING IN THE FRONT SETBACK
 2. SEPARATE PERMIT REQUIRED FOR
 THE WALL, MUST HAVE EASEMENT RELEASE
 FROM THE WPBWATER DEPT.
2002-12-05 00:00:00DENIED,


Account Summary | Usage Policy | Privacy Policy