| 2002-12-26 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 02111682 |
| | ADD: 1801 PALM BEACH LAKES/ 200 |
| | CONT:PLAN REVIEW |
| | ALLEGHENY DESIGN MGMF |
| | TEL: (954)485-8600 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 2)705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | 3)705.1.2 PENETRATIONS SHALL BE PRO- |
| | TECTED BY AN APPROVED PENETRATION FIRE- |
| | STOP SYSTEM AS TESTED IN ACCORDANCE WITH |
| | ASTM E 814, WITH A MINIMUM POSITIVE |
| | PRESSURE DIFFERENTIAL OF 0.01 INCH OF |
| | WATER COLUMN AND AN F RATING OF NOT LESS |
| | THAN REQUIRED RATING OF THE WALL |
| | PENETRATED. |
| | |
| | 4) TABLE 803.3 MINIMUM INTERIOR FINISH |
| | CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS |
| | BASED ON OCCUPANCY |
| | |
| | 5)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SHEET A3.2 SECTIONS 6&7 INDICATE A |
| | ELLIPTICAL DROPPED CEILING, NOTE INDICAT |
| | ES CEILING TO BE HUNG BY MANUFACTURERS |
| | SPECIFICATIONS? PLEASE PROVIDE! |
| | |
| | 6) 11-4.35 DRESSING ROOMS, DRESSING AND |
| | FITTING ROOMS REQUIRED TO BE ACCESSIBLE |
| | BY 11-4.1 SHALL COMPLY WITH 11-4.35 AND |
| | SHALL BE ON AN ACCESSIBLE ROUTE, (1-5). |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | JIM WITMER |
| | PLAN REVIEW |
| | TEL: (561)659-8096 EX.8412 |
| | FAX: (561)659-8026 |