Plan Review Details - Permit 02111682
Plan Review Stops For Permit 02111682
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-25 Cont ID  
Sent By jwitmer Date 2003-02-25 Time 14:22 Rev Time 0.50
Received By jwitmer Date 2003-02-25 Time 14:22 Sent To  
Notes
2003-02-25 00:00:00REVISION: CEILING RETURN

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-01-14 Cont ID  
Sent By dpalmer Date 2003-02-25 Time 10:44 Rev Time 1.25
Received By jwitmer Date 2003-01-14 Time 15:43 Sent To  
Notes
2003-01-14 00:00:00 
  
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02111682
 ADDRESS: 1801 PALM BEACH LAKES BLVD
 SUITE # 200
 CONT: ALLEGHENY DESIGN
 TELL # (954)485-8600
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 *****PROVISO******
  
 1) COMMENT# 5, SUSPENDED CEILING FRAMING
 SYSTEM. SHALL BE PROVIDED, ENGINEERED,
 AND INSTALLED BY CONTRACTOR PER MANUFAC-
 TURERS SPEC. PROVIDE 2 COPIES BEFORE THE
 FRAMING INSPECTION. PROVIDE DETAILS AS
 TO HOW THIS STRUCTURE SHALL BE INSTALLED
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-26 Cont ID  
Sent By jwitmer Date 2002-12-26 Time 08:02 Rev Time 1.25
Received By jwitmer Date 2002-12-26 Time 08:02 Sent To  
Notes
2002-12-26 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02111682
 ADD: 1801 PALM BEACH LAKES/ 200
 CONT:PLAN REVIEW
 ALLEGHENY DESIGN MGMF
 TEL: (954)485-8600
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 2)705.7.1 JOINTS INSTALLED IN OR BE-
 TWEEN FIRE RESISTANT WALLS, FIRE RESIS-
 TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES
 AND FIRE RESISTANT ROOFS OR ROOF/ CEIL-
 ING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE
 FOR A PERIOD NOT LESS THAN THE RE-
 QUIRED FIRE RESISTANCE RATING OF THE
 WALL, FLOOR OR FLOOR IN OR BETWEEN
 WHICH IT IS INSTALLED.
  
 3)705.1.2 PENETRATIONS SHALL BE PRO-
 TECTED BY AN APPROVED PENETRATION FIRE-
 STOP SYSTEM AS TESTED IN ACCORDANCE WITH
 ASTM E 814, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH OF
 WATER COLUMN AND AN F RATING OF NOT LESS
 THAN REQUIRED RATING OF THE WALL
 PENETRATED.
  
 4) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 SHEET A3.2 SECTIONS 6&7 INDICATE A
 ELLIPTICAL DROPPED CEILING, NOTE INDICAT
 ES CEILING TO BE HUNG BY MANUFACTURERS
 SPECIFICATIONS? PLEASE PROVIDE!
  
 6) 11-4.35 DRESSING ROOMS, DRESSING AND
 FITTING ROOMS REQUIRED TO BE ACCESSIBLE
 BY 11-4.1 SHALL COMPLY WITH 11-4.35 AND
 SHALL BE ON AN ACCESSIBLE ROUTE, (1-5).
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-13 Cont ID  
Sent By dpalmer Date 2003-01-13 Time 16:37 Rev Time 0.75
Received By dpalmer Date 2003-01-13 Time 16:37 Sent To  
Notes
2003-01-13 00:00:00************** NOTES *************
  
 PLEASE SEE NOTES REDLINED ON PLANS.
 PLEASE NOTE THAT PLANS ARE THE SAME ONES
 THAT WERE SUBMITTED THE FIRST TIME FOR
 REVIEW AND NO CHANGES TO FIRST REVIEW
 COMMENST WERE MADE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-03 Cont ID  
Sent By nmccray Date 2003-01-08 Time 15:32 Rev Time 1.00
Received By dpalmer Date 2002-12-03 Time 13:10 Sent To  
Notes
2002-12-03 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASENOTE, PLANS REFERENCE
 NOTES TO THE "96" NEC. PLEASE NOTE,
 WE ARE UNDER THE 99 NEC.
  
 2)NOTE: PLEASE SEE 700-12 FOR CIRCUITING
 FOR EM/EX LTS.
  
 3)NOTE: PLEASE CLARIFY, WATER HEATER
 SHOWN ON PLANS WITH A DISC AND PANEL
 SCHEDULE SHOWS A LOCK ON DEVICE. PLEASE
 NOTE CERTAIN "LOCK ON " DEVICES ARE NOT
 ACCEPTABLE. JUST A NOTE.
  
 4)NOTE: PLEASE NOTE, NOTE#9 ON E-1
 MENTIONS TO CONTACT "LL" REP. PLEASE
 NOTE, SHOULD READ FPL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLANS ARE IN GOOD SHAPE WITH
 ONLY MINOR ITEMS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-01-08 Cont ID  
Sent By nmccray Date 2003-01-08 Time 15:32 Rev Time 0.00
Received By nmccray Date 2003-01-08 Time 15:31 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-06 Cont ID  
Sent By mcarsill Date 2002-12-06 Time 16:27 Rev Time 0.00
Received By mcarsill Date 2002-12-06 Time 16:26 Sent To  
Notes
2002-12-06 00:00:001) PLEASE INDICATE ON PLANS THE
 INTERIOR FINISH CLASSIFICATION FOR
 THE WALLS AND CEILINGS.
  
 2) WHEN PAINTING THE CEILING, CARE IS
 TO BE TAKEN NOT TO PAINT THE EXISTING
 FIRE SPRINKLER HEADS. IF THE FIRE
 SPRINKLER HEADS ARE PAINTED, THEY WILL
 HAVE TO BE REPLACED. CLEANING OF FIRE
 SPRINKLER HEADS ARE NOT ALLOWED.
  
 3) EXIT SIGN IN STOCKROOM SHOULD BE
 POSITIONED IN FRONT OF THE DOOR THAT
 LEADS BACK INTO THE RETAIL SPACE.
  
 4) NO INFORMATION ON HOW THE EXISTING
 FIRE SPRINKLER SYSTEM WILL BE REMODELED
 OR ALTERED. SEPARATE PLANS AND PERMITS
 WILL BE REQUIRED PRIOR TO STARTING
 WORK.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-25 Cont ID  
Sent By dpalmer Date 2003-02-25 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2003-02-25 Time 10:44 Sent To B
Notes
2003-02-25 00:00:00TO JIM WITMER'S DESK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By pkrauss Date 2002-12-23 Time 10:15 Rev Time 0.35
Received By pkrauss Date 2002-12-23 Time 10:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By kstevens Date 2002-12-23 Time 09:21 Rev Time 1.00
Received By kstevens Date 2002-12-23 Time 09:21 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved