Plan Review Details - Permit 02111519
Plan Review Stops For Permit 02111519
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2006-06-09 Cont ID  
Sent By jgomez Date 2006-06-09 Time 10:30 Rev Time 0.00
Received By jgomez Date 2006-06-09 Time 10:30 Sent To  
Notes
2006-06-09 00:00:00OPENED THIS STOP BY MISTAKE. NEED TO
 OPEN R STOP. JG.

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2006-05-31 Cont ID  
Sent By btrobaug Date 2006-05-08 Time 10:26 Rev Time 0.75
Received By btrobaug Date 2006-05-08 Time 07:51 Sent To P
Notes
2006-05-08 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 THERE ARE ELECTRICAL SHEETS SUBMITTED
 WITH THIS REVISION BUT NO INDICATION OF
 WHAT WAS REVISED. PLEASE CLOUD OR
 OTHERWISE INDICATE CHANGES FOR REVIEW.
 IF NO CHANGES TO THESE SHEETS, DO NOT
 INCLUDE IN THE REVISION SET.
 THE GENERAL LIGHTING LOAD IS SHOWN AS
 1/3 OF THE TOTAL IN BOTH PANELS. PLEASE
 CALCULATE PER 220.3(A)
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-03-21 Cont ID  
Sent By btrobaug Date 2006-03-21 Time 13:55 Rev Time 0.50
Received By btrobaug Date 2006-03-21 Time 13:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-15 Cont ID  
Sent By btrobaug Date 2006-03-15 Time 15:26 Rev Time 0.50
Received By btrobaug Date 2006-03-15 Time 14:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-14 Cont ID  
Sent By btrobaug Date 2006-02-14 Time 17:28 Rev Time 0.50
Received By btrobaug Date 2006-02-14 Time 17:22 Sent To B
Notes
2006-02-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SMOKE DETECTORS MUST BE ADDED IN AND
 OUTSIDE THE ADDED BEDROOM PER NFPA-72
 AND FBC.
  
 2} THE LOAD CALCULATIONS MUST BE CHANGED
 TO INCLUDE THE ADDITIONAL LIVING SPACE.
  
 3} THE INCREASED VALUE OF THE PROJECT
 MUST BE ADDED TO THE VALU ON THE
 ORIGINAL APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-13 Cont ID  
Sent By btrobaug Date 2006-02-13 Time 07:36 Rev Time 0.50
Received By btrobaug Date 2006-02-13 Time 07:11 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-21 Cont ID  
Sent By rregueir Date 2002-12-14 Time 13:41 Rev Time 0.50
Received By btrobaug Date   Time   Sent To R
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-07 Cont ID  
Sent By adarroug Date 2006-06-07 Time 13:35 Rev Time 0.00
Received By adarroug Date 2006-06-07 Time 13:35 Sent To M
Notes
2006-06-07 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-24 Time 11:02 Rev Time 0.00
Received By adarroug Date 2006-04-24 Time 11:02 Sent To B
Notes
2006-04-24 00:00:00TO "JGOMEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 10:48 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 10:48 Sent To M
Notes
2006-03-17 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 09:09 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 09:09 Sent To M
Notes
2006-03-02 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 14:35 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 14:35 Sent To E
Notes
2006-02-06 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-21 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 18:31 Rev Time 0.00
Received By btrobaug Date 2002-11-21 Time 18:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-06-14 Cont ID  
Sent By tgordon Date 2006-06-14 Time 16:52 Rev Time 0.20
Received By tgordon Date 2006-06-15 Time 07:59 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-05-04 Cont ID  
Sent By tgordon Date 2006-05-04 Time 14:43 Rev Time 0.30
Received By tgordon Date 2006-05-04 Time 14:43 Sent To E
Notes
2006-05-04 00:00:00*** DENIED ***
 1) SUBMITTAL FOR BBQ GRILL HOOD IS FOR A
 INDOOR HOOD, PLEASE SUBMIT INFOMATION
 FOR OUTDOOR USE.
  
 2) PLEASE SEE BUILDING REVIEW NOTES
 REGUARDING ENERGY CALCULATIONS AND
 SUBMIT CORRECTED E-CAL'S..
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-03-17 Cont ID  
Sent By tgordon Date 2006-03-17 Time 15:16 Rev Time 0.45
Received By tgordon Date 2006-03-17 Time 15:16 Sent To  
Notes
2006-03-17 00:00:00REVISION TO MECH. PLANS AND E-CAL'S..

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-03-03 Cont ID  
Sent By tgordon Date 2006-03-03 Time 12:06 Rev Time 0.45
Received By tgordon Date 2006-03-03 Time 12:06 Sent To  
Notes
2006-03-03 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 113,600 TOTAL BTU'S, AND THE PLANS ARE
 CALLING FOR 119,900 TOTAL BTU'S. THE
 PLANS CAN NOT CALL FOR MORE BTU'S THAN
 THE E-CAL'S, PLEASE CORRECT.
  
 2) AHU #1 SUPPLT AIR DUCT TO FIRST FLOOR
 IS 12" SO THE RETURN AIR DUCT NEEDS TO
 BE 12" NOT 10" PLEASE CORRECT.
  
 3) AHU #1 THE RETURN AIR DUCT TO THE
 SECOND FLOOR NEEDS TO BE SIZED.
  
 4) THE RETURN AIR GRILL 30X18 TO AHU #2
 IS TO SMALLFOR A 5 TON SYSTEM PLEASE
 CORRECT.
  
 5) NOT ALL SUPPLY AIR DUCTS ARE SIZED
 PLEASE CHECK AND CORRECT.
  
 6) THE JOB ADDERSS MUST APPEAR ON ALL
 SHEETS OF THE PLANS.
  
 7)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-02-22 Cont ID  
Sent By tgordon Date 2006-02-22 Time 11:36 Rev Time 0.25
Received By tgordon Date 2006-02-22 Time 11:36 Sent To Z
Notes
2006-02-22 00:00:00*** DENIED ***
 1) NEED TO SUBMIT REVISED MECHANICAL
 PLANS DUE TO ROOM ADDITION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-14 Cont ID  
Sent By kstevens Date 2002-12-09 Time 17:21 Rev Time 0.60
Received By rregueir Date 2002-12-14 Time 13:41 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-06-13 Cont ID  
Sent By jleech Date 2006-06-13 Time 12:16 Rev Time 0.00
Received By jleech Date 2006-06-13 Time 12:16 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-05-09 Cont ID  
Sent By btrobaug Date 2006-05-31 Time 10:13 Rev Time 0.00
Received By jleech Date 2006-05-09 Time 07:19 Sent To Z
Notes
2006-05-09 00:00:00DENIED;
 SANITARY RISER DIAGRAM; PLEASE SIZE ALL
 PIPES. A REVISIONS WASREQUESTED BY KEN
 STEVENS 3/25/03. RISER DIAGRAM HAS NOT
 BEEN REVISED. SEE ORIGINAL APPROVED
 PLANS PAGE A-9. ONE SET OF PLANS MARKED
 IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-02-22 Cont ID  
Sent By jleech Date 2006-02-22 Time 09:22 Rev Time 0.33
Received By jleech Date 2006-02-22 Time 09:22 Sent To M
Notes
2006-02-22 00:00:00DENIED;
 NEW BATHROOM NOT SHOWN ON SANITARY RISER
 DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-25 Cont ID  
Sent By kstevens Date 2003-03-25 Time 13:56 Rev Time 0.25
Received By kstevens Date 2003-03-25 Time 13:56 Sent To  
Notes
2003-03-25 00:00:00PASSED/PROVISO
  
 REVISION REQUIRED - SHOW ALL PIPE SIZES

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-09 Cont ID  
Sent By jgomez Date 2003-03-25 Time 13:26 Rev Time 0.25
Received By kstevens Date 2002-12-09 Time 17:14 Sent To M
Notes
2002-12-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT A2 SANITARY RISER DIAGRAM, DOES
 NOT REFLECT THE FLOOR PLAN. BIDET IN
 MASTER BATH AND SHOWER IN CABANA ARE NOT
 SHOWN ON RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 6 Status P Date 2006-06-09 Cont ID  
Sent By jgomez Date 2006-06-09 Time 11:52 Rev Time 2.00
Received By jgomez Date 2006-06-09 Time 10:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status F Date 2006-05-01 Cont ID  
Sent By jgomez Date 2006-05-01 Time 17:53 Rev Time 2.50
Received By jgomez Date 2006-05-01 Time 17:53 Sent To M
Notes
2006-05-01 00:00:00BUILDING REVISION 2ND CHECKLIST:
 1- WIND LOAD CRITERIA: CLEARLY LIST ALL
 FIVE ITEMS AS REQUIRED BY SECTION
 1606.1.7 FBC 2001.
  
 2- SHEET A-5: AREA CALCULATIONS ARE
 WRONG. RECALCULATE ALL AREAS AND REVISE
 AS REQUIRED TO UPDATE VALUATION AND
 SQUARE FEET ACCORDINGLY.
  
 3- AFTER CALCULATIONS ARE REVISED. BRING
 BACK DRAWINGS TO PALM BEACH COUNTY FOR
 RE-STAMPING.
  
 4- PROVIDE PRODUCT APPROVAL FOR:
 A) ENTRY DOORS AS SHOWN ON PLANS.
 B) 9'X8' GARAGE DOOR.
 C) CASEMENT WINDOWS ON SECOND FLOOR.
  
 5- PROVIDE CUT SHEETS FOR CASEMENT
 WINDOWS SIZES SHOWN ON 2ND FLOOR TO
 VERIFY COMPLIANCE WITH EGRESS OPENING.
 SEC. 1005.4.4 FBC 2001.
  
 6- ARCHITECT TO PROVIDE COMPLETE TILE
 FASTENING SPECIFICATIONS AS REQUIREDBY
 SEC. 104.2.1.1 CITY AMENDMENTS TO FBC
 2001.
 TYPICAL WALL SECTIONS SPECIFY "ATTACH
 CEMENT TILE PER SPECS". THIS NOTE
 DOESN'T PROVIDE THE REQUIRED SPECIFIC
 INFORMATION.
  
 7- PROVIDE SPECS FOR HOOD ABOVE BBQ
 GRILL APPROVED TO BE INSTALLED IN
 EXTERIOR LOCATION. INFORMATION SUBMITTED
 IS FOR INTERIOR INSTALLATION.
  
 8- A) REVISE RIGHT ELEVATION TO MATCH.
 PLANS SHOW FRENCH DOORS, WHILE ELEVATION
 SHOW WINDOWS.
 B) SPECIFY DESIGN PRESSURES FOR ALL
 OPENINGS IN RIGHT ELEVATION. SEC. 1606
 FBC 2001.
  
 9- SPECIFY THE DESIGN PRESSURES FOR
 9'X8' GARAGE DOOR. SEC. 1606 FBC 2001.
  
 10- CHAPTER 481 FLORIDA STATUTE AND FAC
 SEC. 61G1-16.004: NEED NAME OF ARCHITECT
 SIGNING AND SEALING DRAWINGS IN ALL
 SHEETS. SOME SHEETS ARE MISSING THE
 ARCHITECT'S NAME AND ON THE OTHERS THE
 NAME OF THE ARCHITECT IS NOT LEGIBLE
 BECAUSE IS WRITTEN ON TOP OF THE BLACK
 BACKGROUND. SEE PLANS. REVISE AS REQ'D.
  
 11- REVISE ENERGY CALCULATIONS:
 A) PLANS WERE APPROVED USING THE FBC
 2001, NOT FBC 2004. REVISE FORM AS REQ'D
 B) A/C AREA TO MATCH REVISED AREA.
 C) REVISE UNDER ATTIC AREA. SEE SEC.
 602.1ABC.1.2 OF CHAPTER 13 FBC 2001 TO
 INCLUDE THE AREAS CONSIDERED CEILING
 AREA.
  
 12- PROVIDE COMPLETE INFORMATION FOR
 STAIRS: NEED DIMENSIONS, RISER AND
 TREADS SIZES. SEC.104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001 AND SECTION 1007
 FBC 2001.
  
 13- A) PROVIDE COMPLETE AND CLEAR SPECS
 AND DETAILS FOR ALL COLUMNS TO MATCH
 COLUMN LEGEND. EG: LANAI COLUMNS DON'T
 MATCH ONE SHOWN IN COLUMN LEGEND.
 B) COLUMN LEGEND: NUMBER OF RE-BARS
 SHOWN DON'T MATCH THE WRITTEN SPECS. SEE
 8"X20" AND 12"X12" COLUMNS AND REVISE.
  
 14- A) ROOF OVER CHIMNEY (ABOVE CHIMNEY
 FLUE): PROVIDE MANUFACTURER'S SPECS
 WHICH ALLOWS FLUE TERMINATION TO HAVE
 BUILT IN ROOF ABOVEAS SHOWN ON
 EXTERIOR ELEVATIONS. PROVIDE COMPLETE
 SPECS FOR CLEARANCES, MATERIALS, ETC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC/01
 B) CHIMNEY SHOWN ON REAR ELEVATION
 DOESN'T MATCH BUILDING SECTION SHOWN ON
 DRAWING A9. REVISE AS REQUIRED.
  
 15- PROVIDE COMPLETE WALL SECTION THRU
 2"X8" BEARING WALL ON 2ND FLOOR ABOVE
 GARAGE BY THE STAIRWAY. SPECIFY ALL
 FASTENERS. SECTION104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
  
 16- SHEET A9:
 A) SECTION 1 IS INCOMPLETE.
 B) CHIMNEY DETAIL:
 * SPECIFY ALL FASTENERS.
 **CHIMNEY DOESN'T MATCH ELEVATIONS.
 ***SPECIFY FIREBLOCKING MATERIAL
 & LOCATION. SEC. 2305.1 FBC 2001.
 **** RAILING DETAIL DOESN'T APPLY TO
 THIS PROJECT. REVISE AS REQUIRED.
  
 17- TYPICAL 2 STORY WALL SECTION SHOWN
 ON SHEET A1 DOESN'T APPLY TO THIS
 PROJECT.REVISE AS REQUIRED.
  
 18- SHEET A5:
 A) REVISE STRUCTURAL BUCK DETAILS.
 SEE SEC. 1707.4.4.2 FOR PROPER WAY OF
 INSTALLING BUCKS. BUCKS NEED TO PROVIDE
 FULL SUPPORT TO DOORS & WINDOWS FRAMES.
 B) SPECIFY SIZE OF STEEL PLATE FOR
 BOLLARD TO PROTECT GAS WATER HEATER.
 SEC. 104.1.2 CITY AMENDMENTS TO FBC 2001
  
 19- SHEET A7:
 A) CONNECTOR TH2 IS A WOOD TO WOOD
 CONNECTOR. NEED A WOOD TO MASONRY
 CONNECTOR. REVISE AS REQUIRED. SEE
 USP CATALOGUE FOR PROPER SELECTION.
 B) ROOF FRAMING PLAN BY LANAI AREA
 CALLS FOR 2TA8. THERE IS NOT TA8
 CONNECTOR IN THE USP CATALOGUE. IS THERE
 A CUSTOM MADE CONNECTOR?. PROVIDE
 PRODUCT APPROVAL FOR IT.
 C) EMBEDDED MASONRY CONNECTOR SHOWN
 ON TOP RIGHT HAND SIDE CORNER: SPECIFY
 HOW LONG ARE THE #5 STUDS EMBEDDED INTO
 THE CONCRETE. SEC. 104.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (5610805-6712

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2006-02-15 Cont ID  
Sent By jgomez Date 2006-02-15 Time 18:25 Rev Time 3.00
Received By jgomez Date 2006-02-15 Time 18:25 Sent To P
Notes
2006-02-15 00:00:00BUILDING REVISION CHECKLIST:
 1- INFORMATION REQUESTED ON PROVISO
 DATED 3-25-03 WAS NEVER SUBMITTED.
 CONTRACTOR AGREED TO PROVIDE INFORMATION
 BUT WAS NEVER SUBMITTED. PROVIDE ALL
 INFORMATION. SEE ATTACHED PROVISO COPY
 AND SUBMIT ALL INFORMATION.
  
 2- SHEET A-5 NEED TO UPDATE AREA CALCS
 TO INCLUDE THE NEW A/C AREA AND REAR
 PORCH ADDITION. BRING PLANS TO PALM
 BEACH COUNTY TO UPDATE TOTAL SQUARE
 FOOTAGE AND PAY IMPACT FEES IF REQUIRED.
 BRING BACK STAMPED DRAWINGS.
  
 3- PROVIDE PRODUCT APPROVAL FOR:
 A) OVAL WINDOW.
 B) 16'-0" X 9'-0" GARAGE DOOR.
  
 4- PROVIDE CALCULATIONS FOR THE DESIGN
 PRESSURES CALCULATED FOR WINDOWS LOCATED
 AT THE END ZONE IN THE SECOND STORY
 BEDROOM ABOVE GARAGE. CALCULATIONS
 SUBMITTED ARE TOO LOW. REVISE AS
 REQUIRED. SEC. 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
  
 5- ARCHITECT TO SPECIFY NUMBER AND TYPE
 OF NAILS REQUIRED FOR ROOF TILE
 FASTENING AS REQUIRED BY SEC. 104.2.1.1
 OF CITY AMENDMENTS TO FBC 2001.
  
 6- PROVIDE COMPLETE SPECS AND LISTING
 FOR "OUTDOOR" BBQ HOOD AND BBQ GRILL TO
 BE INSTALLED. SEC. 2808 FBC 2001.
  
 7- RIGHT ELEVATION DOESN'T MATCH PLANS.
 SEE REVISED REAR PORCH. REVISE ELEVATION
 TO MATCH FLOOR PLANS.
  
 8- ARCHITECT TO PROVIDE SPECIFIC DAY
 WHEN PLANS WERE SEALED. MONTH ALONE IS
 NOT A COMPLETE DATE. ALSO, PRINT THE
 NAME OF THE PERSON SEALING THE PLANS.
 SEE CHAPTER 481 FLORIDA STATUTES AND
 61G1-16.004 OF FLORIDA ADMINISTRATIVE
 CODE FOR TITLE BLOCK REQUIREMENTS.
 PROVIDE COMPLETE INFORMATION AS REQ'D.
  
 9- PROVIDE REVISED ENERGY CALCULATIONS
 SHOWING NEW A/C AREA.
  
 10- PROVIDE COMPLETE INFORMATION FOR
 STAIR:SECTION/DETAIL TRHU STAIRS.
 SPECIFY RAILING HEIGHT AND LOCATION.
 RISER AND TREAD DIMENSIONS. STAIR WIDTH.
 SEC. 1007 FBC 2001.
  
 11- PROVIDE COMPLETE SPECS AND DETAILS
 FOR ALL COLUMNS AT COVERED LANAI.
 INCLUDING COLUMN BY BBQ AREA. SPECIFY
 TOP AND BOTTOM CONNECTIONS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 12- PROVIDE COMPLETE BATHROOM WITH DOOR
 THAT ALLOWS 29"CLEAR OPENING AS REQUIRED
 BY SEC. 11-11 FBC 2001.
  
 13- SPECIFY ATTIC ACCESS IN SECOND FLOOR
 AS REQUIRED BY SEC. 2309.6 FBC 2001.
  
 14- PROVIDE COMPLETE DETAIL/SECTION WITH
 SPECS FOR ATTACHMENT OF WOOD BUCKS TO
 STEEL COLUMNS AT LIVING ROOM AREA.
 (NOTE: TAPCONS ARE MASONRY CONNECTORS.
 NOT DESIGNED FOR WOOD OR STEEL).
  
 15- CHIMNEY FLUE CAP. PROVIDE
 MANUFATURER'S INFORMATION WHICH ALLOWS
 FLUE TERMINATION TO HAVE BUILT IN FLUE
 CAP AS SHOWN ON EXTERIOR ELEVATIONS.
 PROVIDE COMPLETE SPECS FOR CLEARANCES,
 MATERIALS, ETC. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 16- SECOND FLOOR PLAN IS MISSING
 INFORMATION. NEED DIMENSIONS, ROOM
 NAMES, DOOR SIZES. WINDOW TYPE AND SIZES
 TO VERIFY EGRESS REQUIREMENTS.
  
 17- PROVIDE COMPLETE WALL SECTION THRU
 2X8 BEARING WALL ON SECOND FLOOR ABOVE
 GARAGE BY THE STAIRWAY. SPECIFY ALL
 FASTENERS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 18- SECOND FLOOR ROOF FRAMING PLAN.
 SPECIFY ALL TRUSS CONNECTIONS AT MASONRY
 AND AT WOOD FRAMED WALL. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 19- NEED TO SPECIFY SMOKE DETECTORS AT
 FIRST FLOOR AND SECOND FLOOR AS REQUIRED
 BY SEC. 905.2.2 FBC 2001.
  
 20- NEED RE-RECORDED NOC. NOC EXPIRES 1
 YR AFTER RECORDING.
  
 21- SHEET A4: A) REVISE SPACING FOR WWM
 SUPPORTS. SEE SEC. 1909.3 FBC 2001.
 B) SPECIFY COLUMN SIZE & REINFORCEMENT
 FOR COLUMN AT ENTRY PORCH, LIVING ROOM,
 BEDROOM #4 VESTIBULE. SEE PLANS FOR
 COMMENTS.
 C) SPECIFY FOOTING PAD FOR STEEL
 COLUMNBY GARAGE STAIRWAY.
  
 22- SHEET A5: A) WHERE ARE SECTIONS 1/A2
 AND 2/A2 LOCATED AT?.
 B) PROVIDE COMPLETE SPECS/DETAILS FOR
 BOLLARD TO PROTECT GAS WATER HEATER.
 SPECIFY EMBEDMENT, REINFORCEMENT, ETC.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC/01
  
 23- SHEET A7: A) SPECIFY BEAM AT LANAI
 AREA BY THE LIVING AREA. SEE COMMENTS ON
 PLANS.
 B) WHAT'S CONNECTOR TH2 AND BU
 SPECIFIED AT SECOND FLOOR FRAMING PLAN
 BY THE GARAGE AREA?
 C) SHOW CRICKET AT CUPOLA ABOVE MASTER
 BATHROOM. SEE PLANS.
 D) SPECIFY ALL CONNECTORS.SEE PLANS
 FOR MISSING CONNECTORS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 ***NOTE: RETURN REDLINED PRINTS AFTER
 CORRECTIONS ARE DONE TO ORIGINAL
 DRAWINGS TO EXPEDITE REVIEW PROCESS.
  
 24- SHEET A9: A) SECTION1 DOESN'T
 MATCH PLANS. REVISE AS REQUIRED.
 B) CHIMNEY DETAIL: SPECIFY ALL
 FASTENERS. SEE COMMENTS ON PLANS. ALSO,
 SPECS CALL FOR VERTICAL FRAMING TO
 EXTEND INTO ATTIC AND TO BE ATTACHED TO
 TRUSS BOTTOM CHORD. REVISE DETAIL TO
 REFLECT THESE SPECIFICATIONS. SEE PLANS.
  
 C) WHERE IS SECTION SHOWN AT BOTTOM OF
 PAGE TAKEN AT? SEE PLANS. ALSO, UPDATE
 CONNECTOR.
 D) TYP. 1 STORY WALL SECTION: UPDATE
 HUGHES CONNECTOR AND SPECIFY SIZE AND
 NUMBER OF NAILS TO HOLD ROOF TILE.
  
 25- PROVIDE COMPLETE 2 STORY WALL
 SECTION. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2003-04-28 Cont ID  
Sent By jgomez Date 2003-04-28 Time 09:57 Rev Time 0.50
Received By jgomez Date 2003-04-28 Time 09:57 Sent To  
Notes
2003-04-28 00:00:00CHECKED IMPACT FEES RECEIPT AND STAMPED
 DRAWINGS BY PALM BEACH COUNTY.
 BUILDING REVIEW APPROVED WITH PROVISO
 DATED 3-25-03.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status   Date 2003-03-25 Cont ID  
Sent By jgomez Date 2003-03-25 Time 10:47 Rev Time 3.50
Received By jgomez Date 2003-03-25 Time 10:47 Sent To P
Notes
2003-03-25 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-WIND LOAD CRITERIA: CLEARLY LIST ALL
 FIVE ITEMS AS REQUIRED BY SECTION
 1606.1.7 FBC 2001.
 2-REVISE EXTERIOR ELEVATIONS TO MATCH
 FLOOR PLANS. SEE FLOOR PLAN AND ROOF
 FRAMING PLAN AND REVISE AS REQUIRED.
 3-NEED COMPLETE INFORMATION ON CHIMNEY
 FRAMING SECTION AND CUPOLAS FRAMING
 PLANS. CLEARLY SPECIFY ALL FASTENERS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 4-NEED COMPLETE INFORMATION ON DETAIL AT
 CONNECTION OF WINDOWS TO STEEL COLUMNS
 CLEARLY SPECIFY ALL FASTENERS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-SPECIFY WWM SUPPORTS AND SPACING ON
 CONCRETE SLAB. SEE SECTION 1909.3
 FBC 2001.
 6-REVISE STRUCTURAL BUCK DETAIL FOR
 SWING DOORS. SEE SEC. 1707.4.4.2 FBC.
 7-SEE PLANS FOR ADDITIONAL COMMENTS AND
 PROVIDE INFORMATION/CLARIFICATION.
 8-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR W/ TRANSOM ABOVE SINGLE ASSEMBLY,
 FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY OR ARCHITECT TO DESIGN THE
 STRUCTURAL HEADER TO BE PART OF BLDG
 STRUCTURE. SEC. 104.2.1.2 CITY AMEND-
 MENTS TO FBC 2001.
 9-PROVIDE FIREPLACE AND BBQ UL LISTING
 AND COMPLETE SPECS.
 10-PROVIDE COMPLETE PRODUCT APPROVAL FOR
 GARAGE DOORS. INCLUDING COMPLETE
 PRODUCT APPROVAL REPORT AND DRAWINGS.
 11-PROVIDE SOIL TEST REPORT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-12-30 Cont ID  
Sent By btrobaug Date 2002-12-21 Time 10:47 Rev Time 4.50
Received By jgomez Date 2002-12-30 Time 09:40 Sent To  
Notes
2002-12-30 00:00:00CHECKLIST:
 1-PAYM IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DWGS AND RECEIPT.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-SURVEY AND SITE PLAN DON'T MATCH.
 VERIFY/CHECK DIMENSIONS.
 ALSO, POOL IS OVERLAPPING ON PLAN.
 4-UPDATE WIND LOAD CRITERIA ON SHEET A-1
 AND SPECIFY THE 5 MINIMUM ITEMS THAT
 ARE REQUIRED BY SEC. 1606.1.7 FBC 2001
 5-PROVIDE SPECIFICATIONS FOR PROTECTION
 OF GAS WATER HEATER LOCATED IN GARAGE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-PROVIDE AT LEAST ONE BATHROOM WITH
 DOOR THAT PROVIDE 29" MIN. CLEAR OP'G
 AS REQ'D BY SEC. 11-11 FBC 2001.
 7-PROVIDE COMPLETE STRUCTURAL DETAIL/
 SPECS FOR HANGING AIR HANDLING UNITS
 FROM CEILING. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-ENERGY CALCULATIONS: OWNER TO SIGN AND
 DATE BOTTOM OF FORM AND PROVIDE OWNER
 INFORMATION ON TOP OF FORM.
 9-EXTERIOR ELEVATIONS AND ROOF FRAMING
 PLAN DON'T MATCH. REVISE AS REQUIRED.
 SEE CUPOLAS, FRONT ELEVATION ROOF
 OUTLINE.
 10-PROVIDE COMPLETE STRUCTURAL SECTION
 FOR FRAMING OF CHIMNEY AND CUPOLAS.
 SPECIFY ALL FASTENERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC.
 11-PROVIDE COMPLETE STRUCTURAL FRAMING
 DETAILS AND SPECS FOR CONNECTIONS OF
 WINDOWS AND STRUCTURAL MULLIONS TO
 STEEL COLUMNS AT LIVING ROOM. (REFER
 TO PRODUCT APPROVAL FOR CONNECTIONS).
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 12-PROVIDE DETAIL/SPECS FOR CONNECTION
 AT TOP OF STEEL COLUMNS AT LIVING ROOM
 WINDOWS AND AT ENTRY PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 13-PROVIDE SPECS FOR WWM SUPPORTS AS
 REQUIRED BY SEC. 1909.3 FBC 2001.
 14-REVISE STRUCTURAL BUCK DETAIL FOR
 SWING DOORS. SEE SEC. 1707.4.4.2 FBC.
 15-SEE PLANS FOR ADDITIONAL COMMENTS AND
 RETURN REVIEWED SET TO EXPEDITE THE
 REVIEW PROCESS.
 16-OWES $429.33 FOR UPDATED VALUE AND
 RADON FEES.
 17-PROVIDE PRODUCT APPROVAL FOR:
 A)GARAGE SIDE DOOR.
 B)COMPLETE PRODUCT APPROVAL FOR GARAGE
 DOOR. REPORT AND APPROVED DRAWINGS.
 C)ENTRY DOOR SINGLE ASEMBLY AS SHOWN ON.
 PLANS.
 D)FIXED WINDOWS WITH THE SIZES AS SHOWN
 ON PLANS.
 E)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS. (PRODUCT
 APPROVAL FOR MULLIONS SUBMITTED IS FOR
 WINDOWS ONLY. SEE PRODUCT APPROVAL
 DRAWINGS).
 F)FIREPLACE UL LISTING & COMPLETE SPECS.
 G)BBQ UL LISTING AND COMPLETE SPECS.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-06-15 Cont ID  
Sent By mmclean Date 2006-06-15 Time 12:02 Rev Time 0.00
Received By mmclean Date 2006-06-15 Time 12:02 Sent To  
Notes
2006-06-15 00:00:00NEW PLANS - RESTAMP PLANS.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK/SCREEN ENCLOSURE.
  
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-03-03 Cont ID  
Sent By mmclean Date 2006-03-03 Time 16:28 Rev Time 0.00
Received By mmclean Date 2006-03-03 Time 16:28 Sent To  
Notes
2006-03-03 00:00:00REVISION - ADDING A PORCH IN REAR OF
 PROPERTY.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 18:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***