 BUILDING PLAN REVIEW
 PERMIT: 02111446
 ADD: 4200 N MILITARY TRAIL
 CONT: ALLIANCE CONSTRUCTION
 TEL: (305)443-2310
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) NO BUILDING ADDRESSES HAVE BEEN GIVEN
 TO SITE "K". THE CITY HAS ASKED FOR A
 FULL SCALE SITE MAP & RECORDED PLAT.
 WE DO HAVE A STREET NAME OF " BEAR LAKES
 COURT". ONCE A RECORDED PLAT IS GIVEN
 WE WILL BE ABLE TO GIVE YOU THE PCN
 AND STREET ADDRESSES.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS ARE MISSING SITE PLAN GIVING
 LOCATION IN RELATION TO OTHER BUILDINGS.
 THERE MAY BE TABLE 600 ISSUES.
  
 3)11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY. INDICATE ACCESIBLE ROUTE TO
 ALL BUILDINGS. FAIR HOUSING SEE:
 PUBLIC USE AREAS
 COMMON USE AREAS
  
 4) INDICATE IF THERE IS TO BE A PUBLIC
 SWIMMING POOL TO BE ON SITE. IF SO INDIC
 ATE COMPLIANCE WITH 424.1 SAFETY REQUIRE
 MENTS OF EFFECTIVE POOL BARRIER,
 64E-9.002 PUBLIC SWIMMING POOLS AND
 BATHING PLACES.
  
 5)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 6) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 PROVIDE SIGNED SEALED COPY OF GEOTECH
 REPORT.
  
 7)FL BLDG 1909.3 (EXEPTION# 2)
 CONCRETE SLABS ON GRADE CONTAINING 6X6/
 W1.4XW1.4 WELDED WIRE REINFORCEMENT
 FABRIC LOCATED IN THE MIDDLE TO THE
 UPPER 1/3RD OF THE SLAB SHALL BE SUP-
 PORTED BY APPROVED MATERIALS OR SUPPORTS
 AT SPACING NOT TO EXCEED 3 FT OR IN
 ACCORDANCE WITH MANUFACTURER'S SPEC.
  
 8)1814.2.4 WALL & FLOOR JOINTS AND
 PENETRATIONS SHALL BE MADE WATER TIGHT
 USING APPROVED METHODS & MATERIALS.
 SHEET AMS-3 SECTION # 3 INDICATES USAGE
 OF A WATER FEATURE( FOUNTAIN). INDICATE
 HOW WATER SEAL INTO THE BUILDING WILL
 BE ACCCOMPLISHED.
  
 9) THIS SAMEDETAIL INDICATES A DEPTH
 OF 2'-1 1/2", THIS BY DEFINITION CAN BE
 USED AS A WADING POOL BECAUSE OF THE
 DEPTH OF WATER, INVOKING 424.1 SECURITY
 REQUIREMENTS AROUND THE WADING POOL!
  
 10) SHEET AMS-5 STRUCTURAL GENERAL NOTES
 DESIGN DATA: HIGH VELOCITY HURRICANE
 ZONE, CORRECT ONLY DADE & BROWARD
 COUNTIES THIS IS APPLIABLE.
  
 11) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 CORRECT: WIND EXPOSURE & MEAN ROOF
 HEIGHT, SEE DEFINITION FOR MEAN ROOF
 HEIGHT.
  
 12)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 13)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) PAIR OF FRENCH DOORS
 B) RAQUET BALL ROOM NOT LISTED
 C) EXTERIOR LOUVER DOORS A/C CLOSET
 D) WINDOWS HORIZONTAL SLIDERS
 E) WINDOWS FIXED RECTANULAR
 F) WINDOWS FIXED HALF MOON
 G) VERTICAL MULLIONS
 H) STORM SHUUTERS
 I) ROOFING ASSEMBLIES
  
 14)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 15) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 16) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 17)1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 18) 1012.1.1. SEE DOOR# 6 EGRESS DOORS
 USED AS AN EXIT DOOR SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN THAN THE
 WIDTHS SHOWN IN TABLE 1004, 32" CLEAR.
  
 19)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY
  
 20)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-25 Cont ID  
Sent By dpalmer Date 2002-11-25 Time 14:44 Rev Time 0.50
Received By dpalmer Date 2002-11-25 Time 14:37 Sent To  
Notes
2002-11-25 00:00:00**************** UNSAT ************
  
 1)NOTE: PLEASE NOTE, DISC`S REQ`D FOR
 A/C AHU`S. 440-11. SHOWN ONLY AS J-BOX.
  
 2)NOTE: PLEASE CLARIFY RECEPT REQ`D FOR
 SERVICING EQUIPMENT. 210-63
  
 3)NOTE:PLEASE SEE NOTE AT BOTTOM OF
 PANEL DP. NOTE #1: MENTIONS GFI BRKR
 AND THERE IS ALREADY A NOTE #1?
 PLEASE CORRELATE.
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 220-3,220-10,220-11,220-13 ETC, PLEASE
 ALSO NOTE ALL CONTINUOUS LOADS ARE TO BE
 SHOWN AT 125%. 215-3,230-42.
 PLEASE SHOW TRACK LIGHTING LOADS PER
 220-12B.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-22 Cont ID  
Sent By mcarsill Date 2002-11-22 Time 15:13 Rev Time 0.00
Received By mcarsill Date 2002-11-22 Time 15:13 Sent To  
Notes
2002-11-22 00:00:001) BUILDING ADDRESS REQUIRED.
  
 2) SINCE NO FIRE SPRINKLERS ARE PLANNED,
 ALL SERVICE AND STORAGE ROOMS ARE TO
 BE AT LEAST ONE HOUR FIRE RATED WITH
 PROPER OPENING PROTECTIVES.
  
 3) PANIC HARDWARE REQUIRED ON ALL EXIT
 DOORS SINCE OCCUPANT LOADS OF 100 OR
 MORE PERSONS ARE EXPECTED.
  
 4) A KNOX-BOX WILL BE REQUIRED FOR
 ENTRY INTO THE CLUBHOUSE.
  
 5) THE FRENCH DOORS THAT ARE NEAR THE
 DIRECTIONAL EXIT SIGN DOES NOT PROVIDE
 FOR THE MINIMUM DOOR WIDTH REQUIRED.
 THE USE OF A SINGLE DOOR FOR EXITING
 DOES NOT APPEAR TO BE WIDE ENOUGH.
 PLEASE SEE NFPA 101, THE LIFE SAFETY
 CODE, SECTION 7.2.1.2.3.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-21 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 17:23 Rev Time 0.00
Received By btrobaug Date 2002-11-21 Time 17:23 Sent To  
Notes
2002-11-21 00:00:00TO COMM BOARD #13./WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-17 Cont ID  
Sent By hmoser Date 2002-12-17 Time 19:47 Rev Time 1.00
Received By hmoser Date 2002-12-17 Time 19:46 Sent To  
Notes
2002-12-17 00:00:00PASS/PROVISO
 1) NEED SMOKE DETECTORS FOR A/C 1 & 2
 606.2.1 FBC(M)
 2) NEED EXHAUST FAN FOR MOP SINK
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-14 Cont ID  
Sent By kstevens Date 2002-12-14 Time 18:21 Rev Time 0.75
Received By kstevens Date 2002-12-14 Time 18:21 Sent To  
Notes
2002-12-14 00:00:00PASSED/PROVISO
  
 THERMAL EXPANSTION CONTROL REQUIRED
 607.3.2