| Plan Review Stops For Permit 02111442 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2004-05-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-05-12 |
Time |
15:31 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-05-04 |
Time |
18:15 |
Sent To |
E |
|
| Notes |
| 2004-05-04 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PROVIDE A HURRICANE SHUTTER | | | INSTALLATION SCHEDULE OR A SEPARATE | | | PERMIT WILL BE REQUIRED. | | | | | | 2.)SEE PREVIOUS LISTS.A SITE PLAN | | | IS REQUIRED.YOU CANNOT USE THE | | | SITE PLAN (WHICH WAS NOT STAMPED BY | | | ZONING) PREPARED BY ANOTHER DESIGN | | | PROFESSIONAL. | | | | | | 3.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION. | | | | | | 4.)PROVIDE THE PERMIT APPLICATION AND | | | THE OWNER/BUILDER AFFIDAVIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-01-29 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-16 |
Time |
16:37 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2004-01-29 |
Time |
12:00 |
Sent To |
|
|
| Notes |
| 2004-01-29 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SUBMIT TWO COPIES OF LEGIBLE, | | | COMPLETE PRODUCT APPROVALS.SEPARATE | | | PERMITS WILL BE REQUIRED FOR ANY ITEMS | | | NOT PROPERLY SUBMITTED BEFORE ISSUANCE. | | | PRODUCT APPROVALS MAY BE AVAILABLE AT | | | WWW.MIAMIDADE.GOV (FIND A DEPARTMENT, | | | BUILDING CODE COMPLIANCE, PRODUCT | | | CONTROL SEARCH). | | | | | | 2.)PROVIDE A HURRICANE SHUTTER | | | INSTALLATION SCHEDULE AS PER MISSILE | | | IMPACT POLICY, SEE ATTACHED. | | | | | | 3.)THE APPROVED ZONING SITE PLAN | | | IS NOT IN THE PACKAGE.PLEASE PROVIDE. | | | | | | 4.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 5.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 6.)SINGLE HUNG 24 AND 34 WINDOWS DO | | | NOT COMPLY WITH FBC1005.4. | | | | | | 7.)THE WINDOWS AT THE BATH TUBS ARE | | | TO COMPLY WITH FBC2405.1 (SAFETY GLASS). | | | | | | 8.)AS PER A CONVERSATION WITH THE | | | HOMEOWNER, THE PLAN SHOWS TWO WINDOWS | | | IN THE EXISTING BEDROOM ADJACENT TO THE | | | ADDITION, BUT THERE IS ONLY ONE.PROVIDE | | | A NEW WINDOW TO COMPLY WITH FBC1005.4 | | | TO PROVIDE EMERGENCY EGRESS FOR THE | | | EXISTING BEDROOM. | | | | | | 9.)TWO COPIES OF ENERGY CALCS | | | REQUIRED, SIGN OWNER/AGENT LINE | | | FBC13-101.2. | | | | | | 10.) THE TITLE BLOCK FOR THE ENGINEER | | | IS TO BE ON EVERY PAGE, INCLUDE THE | | | LICENSE NUMBER FAC61G15-23.002. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-07-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-01-28 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-07-09 |
Time |
14:22 |
Sent To |
P |
|
| Notes |
| 2003-07-10 00:00:00 | SHEET 1 DATED 6/30/03 SIGNED AND SEALED | | | BY LESLIE E. COLBY, PE STILL HAS | | | INFORMATION FOR 130 MPH WIND ZONE.AS | | | PREVIOUSLY NOTED, THE CITY OF WEST PALM | | | BEACH IS IN A 140 MPH WIND ZONE.ALSO, | | | CUT AND PASTING OF THE CODE IS NOT A | | | SUBSTITUTE FOR SPECIFIC DESIGN | | | INFORMATION OR SOUND ENGINEERING | | | PRACTICE.SEE FBC 104.2.1. | | | | | | SHEET 3 HAS A CUT AND PASTE OF SECTION | | | 2309.7 OF THE FBC.HOW WILL THE 4'X4' | | | VENT SHOWN IN THE GABLE END ON SHEET 2 | | | PROVIDE CROSS VENTILATION?WHAT WILL | | | BECOME OF THE EAVE VENTS ON THE | | | EXISTING BUILDING WHEN THE ADDITION IS | | | ATTACHED? | | | | | | SHEET 3 ROOFING LOADS.WHERE ARE THE | | | LOAD COMBINATIONS FROM FBC 1609?HOW | | | WAS THE WIND PRESSURE AND COEFFICIENTS | | | DETERMINED?HOW DO THEY RELATE TO THE | | | DECLARED "DESIGN CRITERIA" TABLE ON | | | SHEET 2 WHICH HAS VARYING PRESSURES FOR | | | COMPONENTS AND CLADDING, ROOF AND WALLS | | | ANOTHER LABELED UPLIFT, PSF, ENDS, INT. | | | AND STILL OTHER FIGURES ON THE SLIDING | | | GLASS DOOR OF THE SOUTH ELEVATION? | | | THE SAME TABLE HAS AN INTERNAL PRESSURE | | | COEFFICIENT AS - 1.8.PLEASE EXPLAIN. | | | | | | SHEET 4 HAS COPIES OF ROBBINS TRUSS | | | PLATE ENGINEERING, ONE DECLARING 110 | | | MPH 1994 SBCCI AND THE OTHER DECLARING | | | ASCE 7-98 AND 130 MPH.WHAT MANNER OF | | | DESIGN OR ENGINEERING IS INTENDED TO BE | | | COMMUNICATED WITH THIS? | | | | | | THE PREVIOUSLY REQUESTED DESIGN FOR THE | | | ATTACHMENT OF THE NEW TRUSSES TO THE | | | EXISTING ROOF HAS NOT BEEN PROVIDED. | | | | | | IN VIEW OF THE ABOVE GLARING DESIGN | | | DISCREPANCIES, PLEASE REVIEW THE | | | RESPONSIBILITY RULES COMMON TO ALL | | | ENGINEERS AND RULES CONCERNING THE | | | DESIGN OF STRUCTURES CONTAINED IN | | | CHAPTERS 61G15-30 AND 61G15-31 OF THE FL | | | ADMINISTRATIVE CODE. | | | | | | AS NOTED ON THE PREVIOUS LIST, IMPACT | | | FEES MUST BE PAID TO THE COUNTY, | | | ADDITIONAL PERMIT FEES ARE DUE TO THE | | | CITY AND IFPRODUCT APPROVALS FOR THE | | | ROOF COVERING, WINDOWS, DOORS AND | | | SHUTTERS WHERE APPICABLE, ARE NOT | | | INCLUDED HERE, A SEPARATE PERMIT, PLANS | | | AND FEES WILL BE REQUIRED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-16 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-12-20 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2002-12-20 00:00:00 | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, THE PERMIT PLANS STAMPED | | | BY THAT OFFICE AND A COPY OF THE PAID | | | RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION.CALL 561-253-5025 FOR | | | MORE INFORMATION. | | | | | | THE NOTES ON SHEET 2 AND ELSEWHERE | | | REFERENCE THE WRONG WINDSPEED.WEST | | | PALM BEACH IS IN A 140 MPH WIND ZONE. | | | PLEASE REVISE AND ENSURE COMPLIANCE | | | WITH SAME. | | | | | | HOW WERE THE ROOF LOADS ON SHEET 3 | | | DETERMINED?SEE FBC 1609.3.2 FOR LOAD | | | COMBINATIONS. | | | | | | SOME PORTIONS OF THE PAGES TITLED "2002 | | | STRUCTURAL DETAILS" ARE ILLEGIBLE AND | | | NOT FOR THE 140 MPH ZONE.WPB IS NOT | | | INCLUDED IN THE HVHZ. | | | | | | PLEASE PROVIDE A BETTER FRAMING DETAIL | | | FOR THE ROOF.SHOW THE TRANSITION OF | | | THENEW TRUSSES TO THE EXISTING. | | | CONNECTIONSAT THE EXISTING BEARING | | | POINTS.SEE FBC 104.2 | | | | | | PROVIDE A DETAIL FOR THE GABLE END | | | DETAIL IN ACCORDANCE WITH FBC 2313.4. | | | | | | SHOW THE ATTIC ACCESS, FBC 2309.6. | | | | | | SHOW THE ATTIC VENTILATION, INCLUDING | | | ASSUMED FREE AREA OF THE SCREEN VENTS | | | TO BE USED.SEE FBC 2309.7. | | | | | | THE WINDOWS IN THE BATH TUB AREAS MUST | | | COMPLY WITH FBC 2405.2.1 #2. | | | | | | IF PRODUCT APPROVALS FOR THE DOORS | | | WINDOWS SHUTTERS AND ROOF COVERING ARE | | | NOT INCLUDED WITH THIS PERMIT | | | APPLICATION, A SEPARATE PERMIT AND FEES | | | WILL BE REQUIRED. | | | | | | THE DECLARED PERMIT VALUATION OF | | | $11,750.00 IS TOO LOW FOR THIS SCOPE OF | | | WORK. | | | PLEASE PAY THE CITY AN ADDITIONAL | | | $893.39 BASED ON A CONSTRUCTION VALUE | | | OF $60840.00 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-05-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-05-12 |
Time |
16:43 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-05-05 |
Time |
06:06 |
Sent To |
P |
|
| Notes |
| 2004-05-05 00:00:00 | *********** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE FAC/ FS, PLANS SIGNED | | | AND SEALED BY AN ARCH/ ENG MUST CONTAIN | | | A TITLE BCLOCK W/ ALL INFORMATION AS | | | SET FORTH IN FAC 61G1-16.004, 61G15-23. | | | 002. | | | | | | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | SERVICE NEW? | | | | | | 3)) NOTE: PLEASE SEE MISSING RECEPTS FOR | | | FRONT AND/OR REAR OF DWELLING. | | | 210.52E | | | | | | 4) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | | MASTER BEDROOM. | | | | | | 5 )NOTE: PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CURCUIT(S) ON PANEL | | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | | IN BEDROOMS ARE TO BE PROTECTED , | | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | 2002 NEC 210.12 | | | | | | 6)NOTE: PLEASE SEE MAX OCP FOR WATER | | | HEATER IS 150%, MIN 125%/ SHOWN AS 2P30A | | | FOR 3.5 KW. | | | | | | 7)NOTE; PLEASE SEE FBC, ADDITIONS TO | | | EXISTING DWELLINGS OF 25% OR MORE. | | | PLEASE SHOW ALL EXISITING ELECTRICAL | | | THAT MEETS CODE AND/OR NEW ELECTRICAL | | | THAT IS REQ'D TO BROUGHT UP TO CODE | | | IN EXSITING BLDG. RECEPT/LTS/SD'S ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-12-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-05-04 |
Time |
18:20 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-12-16 |
Time |
12:41 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2004-05-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-05-10 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2004-05-10 |
Time |
15:26 |
Sent To |
Z |
|
| Notes |
| 2004-05-10 00:00:00 | OWNER BROUGHT IN SITE PLAN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-04-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-16 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-16 |
Time |
16:37 |
Sent To |
B |
|
| Notes |
| 2004-04-16 00:00:00 | TO SH DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-01-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-16 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-16 |
Time |
13:40 |
Sent To |
P |
|
| Notes |
| 2004-01-16 00:00:00 | TO KS BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-07-10 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-10 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-10 |
Time |
11:35 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-07 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-07-07 |
Time |
09:24 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-27 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-27 |
Time |
10:45 |
Sent To |
Z |
|
| Notes |
| 2002-11-27 00:00:00 | CALLED OWNER FOR 2ND SET OF PLANS 11/26 | | | BROUGHT IN 11/27. /WRT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2004-01-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-01-28 |
Time |
12:52 |
Rev Time |
0.15 |
| Received By |
pkrauss |
Date |
2004-01-28 |
Time |
12:47 |
Sent To |
B |
|
| Notes |
| 2004-01-28 00:00:00 | MECHANICAL CONTRACTOR IS NOT INDICATED | | | ON BUILDING PERMIT APPLICATION. | | | MECHANICAL PERMIT REQUIRED.PLEASE | | | PROVIDE PLANS WITH MECHANICAL PERMIT | | | APPLICATION.ENERGY CALCULATIONS | | | SUBMITTED WITH BUILDING PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2003-07-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-01-24 |
Time |
10:58 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2003-07-08 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2003-07-08 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW.PLEASE PROVIDE A COMPLETED FORM | | | 600C AS PER FBC CHAPTER 13 SUB-CHAPTER | | | 6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-07-07 |
Time |
09:25 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
|
Time |
|
Sent To |
E |
|
| Notes |
| 2002-12-09 00:00:00 | DENIED:NO PLANS SUBMITTED FOR REVIEW | | | | | | PLEASE PROVIDE ENERGY & MANUAL J CALCS. | | | INDICATE MAKE, MODEL, BTU'S FOR AHU & | | | MAKE, MODEL & SEER OF THE CONDENSER | | | UNIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2004-05-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2004-05-08 |
Time |
13:31 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2004-05-08 |
Time |
13:31 |
Sent To |
B |
|
| Notes |
| 2004-05-08 00:00:00 | DENIED; | | | RISER DIAGRAM DOES NOT REFLECT FLOOR | | | PLAN. RISER DIAGRAM SHOULD SHOW WORK TO | | | BE DONE. IS ALL THE DRAINAGE PIPE TO BE | | | REPLACED? | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2004-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-05 |
Time |
06:09 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2004-01-24 |
Time |
10:58 |
Sent To |
M |
|
| Notes |
| 2004-01-24 00:00:00 | DENIED | | | REFERENCE: FLORIDA ADMIN. CODE | | | FLORIDA STATUTES | | | | | | | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS AND LICENSE NUMBER ON EACH | | | SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGIN- | | | EERS, ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. A TITLE BLOCK | | | WILL SATISFY THIS REQUIREMENT. FAC | | | 61G15-23.002(2) - FS 471.025 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2003-07-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-16 |
Time |
13:40 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-07-12 |
Time |
05:34 |
Sent To |
|
|
| Notes |
| 2003-07-12 00:00:00 | NO PLUMBING PLANS SUBMITTED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-06 |
Time |
16:15 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-12-06 |
Time |
16:15 |
Sent To |
M |
|
| Notes |
| 2002-12-06 00:00:00 | NO PLUMBING TO REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-05-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-05-10 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-05-12 |
Time |
15:31 |
Sent To |
B |
|
| Notes |
| 2004-05-12 00:00:00 | PASS RESUB. CALLED OWNER FOR P/U FILE | | | M |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-12-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-27 |
Time |
10:45 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
B |
|
| Notes |
|
|