Plan Review Details - Permit 02111400
Plan Review Stops For Permit 02111400
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-12-02 Cont ID  
Sent By pkrauss Date 2002-11-25 Time 14:48 Rev Time 0.00
Received By nmccray Date 2002-12-02 Time 11:03 Sent To  
Notes
2002-12-02 00:00:001) PROVIDE FIRE SUPPRESSION SHOP DRAWING
 FOR SEPRATE PERMITTING
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT. 8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-25 Cont ID  
Sent By pkrauss Date 2002-11-25 Time 14:42 Rev Time 0.45
Received By pkrauss Date 2002-11-25 Time 14:29 Sent To FIRE
Notes
2002-11-25 00:00:00PROVISO:
  
 PLEASE PROVIDE SUBMITTAL ON THE FYREWRAP
 THAT IS BEING UTILIZED.
  
 AIR VELOCITY THRU DUCT SHALL NOT BE LESS
 THAN 1,500 FPM & NOT GREATER THAN 2,500
 FPM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.