| Plan Review Stops For Permit 02111287 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-20 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-11-21 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2002-11-21 00:00:00 | 1) SPRAY BOOTH IS TO BE PROPERLY | | | GROUNDED. | | | | | | 2) SPRAY BOOTH SHALL PROVIDE FOR | | | AT LEAST THREE FEET OF CLEARANCE | | | AROUND IT TO PROVIDE FOR CLEANING. | | | | | | 3) SPRAY BOOTH TO BE PROTECTED BY | | | AN APPROVED EXTINGUISHING SYSTEM. | | | SEPARATE PLANS AND PERMITS REQUIRED. | | | | | | 4) FILTERS TO MEET UL REQUIREMENTS. | | | | | | 5) APPROVED UL FLAMMABLE OR | | | COMBUSTIBLE CABINETS ARE TO BE | | | PROVIDED FOR THE STORAGE OF FLAMMABLE | | | OR COMBUSTIBLE MATERIALS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-11-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-20 |
Time |
13:13 |
Rev Time |
1.45 |
| Received By |
pkrauss |
Date |
2002-11-20 |
Time |
13:10 |
Sent To |
FIRE |
|
| Notes |
| 2002-11-20 00:00:00 | PROVISO: | | | | | | AS PER NFPA 33 | | | 3.3.2, A CLEAR SPACE OF NOT LESS THAN 3 | | | FT SHALL BE MAINTAINED ONALL SIDES OF | | | THE SPRAY BOOTH. | | | | | | 5.4, THE EXHAUST DUCT DISCHARGE POINT | | | SHALL BE AT LEAST 6 FT FROM ANY EXTERIOR | | | WALL OR ROOF. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|