Plan Review Details - Permit 02111251
Plan Review Stops For Permit 02111251
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2003-09-11 Cont ID  
Sent By hpiskura Date 2003-09-11 Time 08:38 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-09-11 00:00:00REVISIONS DATED 9/5/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-07-29 Cont ID  
Sent By hpiskura Date 2003-07-29 Time 10:51 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-07-29 00:00:00SHEET A100 DATED 7/16/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-06-19 Cont ID  
Sent By hpiskura Date 2003-06-19 Time 11:33 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2003-06-19 00:00:00REVISONS DATED 6/2/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-02-10 Cont ID  
Sent By hpiskura Date 2003-02-10 Time 08:35 Rev Time 0.00
Received By hpiskura Date 2003-02-10 Time 08:15 Sent To  
Notes
2003-02-10 00:00:00REVISIONS DATED 1/28/03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-16 Cont ID  
Sent By hpiskura Date 2002-12-16 Time 14:42 Rev Time 0.00
Received By hpiskura Date 2002-12-16 Time 14:18 Sent To  
Notes
2002-12-16 00:00:00THE EXITS AS SHOWN DO NOT MEET THE
 MINIMUM 1/3 DIAGONAL DISTANCE FOR
 SEPARATION IN ACCORDANCE WITH FBC
 1004.1.4.PLEASE REVISE AS NECESSARY.
 (EGRESS IS NOT PERMITTED THROUGH
 KITCHENS FBC 1001.1.3.)
  
 SHOW THE COUNTER AS COMPYING WITH THE
 HANDICAP REQUIREMENTS OF FBC 11-5.2.
  
 SHOW THE COMPONENT AND CLADDING
 PRESSURES FOR THE NEW STOREFRONT
 SYSTEM.SEE FBC 1606.1.7.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2003-09-15 Cont ID  
Sent By dpalmer Date 2003-09-15 Time 13:55 Rev Time 0.33
Received By dpalmer Date 2003-09-15 Time 13:55 Sent To  
Notes
2003-09-15 00:00:00REDLINED POSSIBLE EQUIPMENT GRND
 FROM MAINS TO PANELS.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-07-23 Cont ID  
Sent By dpalmer Date 2003-07-23 Time 09:18 Rev Time 0.33
Received By dpalmer Date 2003-07-23 Time 09:18 Sent To  
Notes
2003-07-23 00:00:00NOTE REDLINED FOR EQUIPMENT GROUNDING
 CONDUCTOR AND SPACE FOR PANELS 110-26

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-07-09 Cont ID  
Sent By dpalmer Date 2003-07-09 Time 07:51 Rev Time 0.33
Received By dpalmer Date 2003-07-09 Time 07:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-06-19 Cont ID  
Sent By shernand Date 2003-06-30 Time 16:37 Rev Time 0.50
Received By dpalmer Date 2003-06-19 Time 09:05 Sent To  
Notes
2003-06-19 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE 700-12E. PLEASE
 CIRCUIT EXT AND EM LT AND CORRELATE
 W/ A SUBMIT REVISED PANEL SCHEDULE.
 PLEASE NOTE, THIS WAS NOTED AND REDLINED
 ON PREVIOUS TWO REVIEWS.
  
 2)NOTE: PLEASE ALSO SUBMIT REVISED
 RISER DIAGRAM W/ EQUIPMENT GROUNDING
 CONDUCTOR BETWEEN MAIN AND PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEYPALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected].

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 07:22 Rev Time 0.50
Received By dpalmer Date 2003-02-11 Time 07:22 Sent To  
Notes
2003-02-11 00:00:00NOTED FOR 700-12E, 2ND TIME.
 MISSING EQUIPMENT GROUNDING BETWEEN "E"
 AND "LP".

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-25 Cont ID  
Sent By dpalmer Date 2002-11-25 Time 06:19 Rev Time 0.50
Received By dpalmer Date 2002-11-25 Time 06:19 Sent To  
Notes
2002-11-25 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, PLANS MUST CONTAIN
 ORIG SIGNATURE FROM THE ENGINEER/ARCH
 OF RECORD. AN INK STAMP IS NOT ACCEPTED
 BY FS 471.025/481.221.
  
 2)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 NEED TO BE SHOWN, PLEASE NOTE ALL
 CONTINUOUS LOADS ARE TO BE SHOWN AT
 125% 230-42/215-3
  
 3)NOTE: PLEASE NOTE, ALL CIRCUITING
 NEEDS TO BE SHOWN, PLEASE NOTE, CIRCUITS
 FOR EM/EXT LTS PER 700-12E.
  
 4)NOTE: PLEASE NOTE, SHOW WINDOW RECEPTS
 REQ`D 210-62.
  
 5)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN MAIN DISC AND
 PANEL "E".EQUIP GRND, SIZE PER 250-122
  
 6)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN DISCONNECT SHOWN.
 MAINS/PANELS/BREAKERS ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER
 110-9.
  
 7)NOTE: PLEASE PROVIDE LOAD FOR EXISTING
 MAIN. PLEASE NOTE, THIS SERVICE IS
 SHOWN ADDING 197A`S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2003-09-10 Cont ID  
Sent By mcarsill Date 2003-09-10 Time 15:37 Rev Time 0.00
Received By mcarsill Date 2003-09-10 Time 15:37 Sent To  
Notes
2003-09-10 00:00:00FIRE ALARM EQUIPMENT IS REQUIRED. COULD
 NOT LOCATE FIRE ALARM EQUIPMENT ON
 THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2003-07-24 Cont ID  
Sent By mcarsill Date 2003-07-24 Time 16:02 Rev Time 0.00
Received By mcarsill Date 2003-07-24 Time 16:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-07-07 Cont ID  
Sent By nmccray Date 2003-07-07 Time 14:07 Rev Time 0.00
Received By nmccray Date 2003-07-07 Time 14:07 Sent To  
Notes
2003-07-07 00:00:00REVISION 6-09-03NAM

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-02-06 Cont ID  
Sent By mcarsill Date 2003-02-06 Time 11:23 Rev Time 0.00
Received By mcarsill Date 2003-02-06 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-05 Cont ID  
Sent By mcarsill Date 2002-12-05 Time 14:05 Rev Time 0.00
Received By mcarsill Date 2002-12-05 Time 14:05 Sent To  
Notes
2002-12-05 00:00:001) PLANS DO NOT INDICATE ANY INTERIOR
 FINISH CLASSIFICATION FOR THE WALLS
 AND CEILINGS.
  
 2) TABLES AND CHAIRS APPEAR TO BE TOO
 CLOSE TOGETHER IN SOME LOCATIONS.
  
 3) AN EXIT SIGN IS PRESENT DIRECTING
 PERSONS TO EXIT THU KITCHEN. THIS IS
 NOT ALLOWED. PLEASE REVISE PLANS AS
 NECESSARY.
  
 4) NO FIRE ALARM EQUIPMENT SHOWN IN
 TENANT SPACE. PLEASE DISPLAY FIRE
 ALARM EQUIPMENT ON THE PLANS.
  
 5) PLEASE EXPLAIN HOW THE TWO EXITS
 LOCATED AWAY FROM THE KITCHEN ARE
 PROPERLY SEPARATED FROM ONE ANOTHER.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY HOOD, DUCT, AND FIRE SUPPRESSION
 SYSTEMS PLANNED FOR THE LOCATION.
  
 7) SEPARATE PLANS AND PERMITS FOR FIRE
 ALARM EQUIPMENT.
  
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER MODIFICATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-09-09 Cont ID  
Sent By csiegber Date 2003-09-09 Time 10:02 Rev Time 0.00
Received By csiegber Date 2003-09-09 Time 10:02 Sent To  
Notes
2003-09-09 00:00:00ON COMM BD#28

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-09-04 Time 09:34 Rev Time 0.00
Received By csiegber Date 2003-09-04 Time 09:34 Sent To P
Notes
2003-09-04 00:00:009/4/03 REV DRAWINGS/P

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 15:39 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 15:38 Sent To M
Notes
2003-08-25 00:00:00TO PK DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 11:19 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 11:19 Sent To  
Notes
2003-07-17 00:00:00COMM BOARD #12

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-06-30 Cont ID  
Sent By shernand Date 2003-06-30 Time 16:37 Rev Time 0.00
Received By shernand Date 2003-06-30 Time 16:37 Sent To E
Notes
2003-06-30 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-06-09 Cont ID  
Sent By shernand Date 2003-06-09 Time 16:20 Rev Time 0.00
Received By shernand Date 2003-06-09 Time 16:20 Sent To  
Notes
2003-06-09 00:00:00COMM BOARD #58

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-31 Cont ID  
Sent By sthyng Date 2003-03-31 Time 15:55 Rev Time 0.00
Received By sthyng Date 2003-03-31 Time 15:55 Sent To P
Notes
2003-03-31 00:00:00TO PLUMBING IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-02-04 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 12:58 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 12:58 Sent To  
Notes
2003-02-04 00:00:00TO COMM BOARD # 25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 17:52 Rev Time 0.00
Received By btrobaug Date 2002-11-19 Time 17:53 Sent To  
Notes
2002-11-20 00:00:00TO COMM BOARD# 50./WRT

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-09-17 Cont ID  
Sent By pkrauss Date 2003-09-17 Time 06:46 Rev Time 0.35
Received By pkrauss Date 2003-09-17 Time 06:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-08-27 Cont ID  
Sent By pkrauss Date 2003-08-27 Time 14:29 Rev Time 0.40
Received By pkrauss Date 2003-08-27 Time 14:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-06-23 Cont ID  
Sent By csiegber Date 2003-08-25 Time 15:39 Rev Time 0.45
Received By pkrauss Date 2003-06-23 Time 10:48 Sent To  
Notes
2003-06-23 00:00:00PROVISO:
  
 CONDENSER UNIT STANDS SHALL COMPLY WITH
 2001 FBC 1511.7.SEE ATTACHED
  
 DUCT SMOKE DETECTOR SHALL BE ACTIVATE
 ALARM/STROBE IN NORMALLY OCCUPIED AREAS
 OR ACTIVATE ALARM STROBE AT A CONSTANTLY
 ATTENDED LOCATION. 2001 FBC(M) 606.4.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-12 Cont ID  
Sent By pkrauss Date 2003-02-12 Time 14:08 Rev Time 0.35
Received By pkrauss Date 2003-02-12 Time 13:52 Sent To  
Notes
2003-02-12 00:00:00PROVISO:
 PROVIDE SUBMITTAL FOR THE CONDENSER
 UNIT ROOF STANDS.SHOW COMPLIANCE
 WITH 2001 FBC 1511.7 FOR CLEARANCE
 REQUIREMENTS ABOVE FINISHED ROOF.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION & WALK-IN COOLERS.
 PROVIDE PLANS AND MANUFACTURER SUBMITTAL
 DATA WITH PERMIT APPLICATIONS.PROVIDE
 AIR BALANCE SCHEDULE FOR HOOD
 EXHAUST/MAKEUP.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-17 Cont ID  
Sent By hmoser Date 2002-12-17 Time 17:01 Rev Time 0.75
Received By hmoser Date 2002-12-17 Time 17:00 Sent To  
Notes
2002-12-17 00:00:00PLAN DENIED
 1) PLANS SHOW SPLIT SYSTEM.EQUIPMENT
 SCHEDULE CALLS FOR ROOF TOP PACKAGE
 UNITS.
 2) ONE FLEX DUCT SIZE NOT MARKED ON
 A/C #3
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 7 Status P Date 2003-09-17 Cont ID  
Sent By kstevens Date 2003-09-17 Time 10:29 Rev Time 1.50
Received By kstevens Date 2003-09-17 Time 10:29 Sent To  
Notes
2003-09-17 00:00:00PASSED/PROVISO - RED LINE CORRECTIONS

Review Stop P PLUMBING
Rev No 6 Status P Date 2003-09-17 Cont ID  
Sent By kstevens Date 2003-09-17 Time 10:03 Rev Time 1.50
Received By kstevens Date 2003-09-09 Time 11:45 Sent To  
Notes
2003-09-17 00:00:00PASSED/PROVISO - REVISION TO GAS SYSTEM
 SEE RED LINE CORRECTIONS BECAUSE OF INFO
 FROM MANUF. INFORMATION AND GAS CONTR.

Review Stop P PLUMBING
Rev No 5 Status F Date 2003-07-26 Cont ID  
Sent By csiegber Date 2003-09-04 Time 09:35 Rev Time 1.00
Received By kstevens Date 2003-07-23 Time 18:06 Sent To  
Notes
2003-07-26 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1) SLEEVE IN CONCRETE NOT APPROVED.
 APPROVED METHOD FOR INSTALLING PIPE IN
 CONCRETE FLOOR SHALL COMPLY WITH SECTION
 404.6.1(2). CONCRETE SHALL BE CUT OUT,
 PIPE INSTALLED, PAINTED WITH A BITUMIN-
 OUS PAINT AND COVERED WITH A LIGHTWEIGHT
 CONCRETE SO THAT THE PIPE CAN BE REMOVED
 IF REQUIRED.
 2) SEE PROVISO FOR APPLICATION FOR GAS
 PERMIT ON SHEET P-101 OF THE APPROVED
 PLANS. AT THIS TIME NO GAS PERMIT HAS
 BEEN APPLIED FOR.
 3) THE HOOD SHUT DOWN SHALL BE BELOW THE
 CEILING, BUT DOES NOT HAVE TO BE AT
 CEILING HEIGHT. (INFORMATIONAL)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-07-01 Cont ID  
Sent By kstevens Date 2003-07-01 Time 08:42 Rev Time 0.75
Received By kstevens Date 2003-06-30 Time 18:56 Sent To  
Notes
2003-07-01 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THESE
 VALVES AND UNION ARE NOT SHOWN ON RISER.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-04-01 Cont ID  
Sent By kstevens Date 2003-04-01 Time 13:08 Rev Time 0.75
Received By kstevens Date 2003-04-01 Time 13:08 Sent To  
Notes
2003-04-01 00:00:00PASSED/PROVISO
  
 PER DEPT. OF BUSINESS AND PROFESSIONAL
 REGULATION REVIEW, A DIPPERWELL IS REQ-
 UIRED. A REVISION IS REQUIRED FOR THE
 FLOOR PLAN, SANT. RISER AND WATER RISER
 SHOWING DIPPERWELL.
  
 SEPARATE GAS PERMIT REQUIRED. GAS REQ-
 UIREMENTS TO BE SUBMITTED AT TIME OF
 APPLICATION.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 4. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-02-05 Cont ID  
Sent By sthyng Date 2003-03-31 Time 15:55 Rev Time 0.50
Received By kstevens Date 2003-02-05 Time 17:31 Sent To  
Notes
2003-02-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) FROM PREVIOUS REVIEW: PLANS SHALL BE
 ROUTED TO DEPT. OF BUSINESS REGULATION
 HOTEL & RESTURANT DIVISION PRIOR TO RE-
 SUBMITTING TO CITY FOR REVIEW. PLANS
 SHALL BE STAMPED AND WORK SHEETS ATTACH-
 ED TO PLANS.
 2) FROM PREVIOUS REVIEW: SHT P101 WATER
 RISER DIAGRAM, WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT AT THE TOP OF THE
 DROP IN THE CEILING. PER PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 3) DELIVERY PERSSURE OF 2LBS WILL ALLOW
 11,415,000 BTU'S. ON 1-1/4" PIPE. MAY
 I SUGGEST A 1/2 LB. SYSTEM THAT WILL
 ALLOW 950,OOO BTU'S FOR 1-1/4" PIPE, AND
 YOU WILL NOT NEED REGULATORS FROM 2LBS.
 4) FROM PREVIOUS REVIEW:********
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 B. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-16 Cont ID  
Sent By kstevens Date 2002-12-14 Time 17:12 Rev Time 1.50
Received By kstevens Date 2002-12-14 Time 17:12 Sent To  
Notes
2002-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) PLANS SHALL BE ROUTED TO DEPT. OF
 BUSINESS REGULATION HOTEL & RESTURANT
 DIVISION (954) 956-5692 PRIOR TO RE-
 SUBMITTING TO CITY OF WPB FOR REVIEW.
 2) GREASE TRAP SHALL BE SIZED BY UTILITY
 DEPT., WASTE ORD. #2938-96. PLEASE CON-
 TACT RODNEY COMPO ENVIRONMENTAL COMPLI-
 ANCE (561) 837-4074.
 3) RPZ BACKFLOW IS REQUIRED FOR WATER
 SERVICE TO RESTURANT. MAX 4' ABOVE FLOOR
 FOR SERVICE AND CERTIFICATION.
 4) SHT A100 TOILET ROOMS SHALL COMPLY
 WITH SECTION 11-4.22. SHOW CLEAR FLOOR
 SPACE, AND UNOBSTRUCTED 5' TURNING RAD-
 IUS. 11-4.22.3. DOOR SHALL NOT OPEN INTO
 THE CLEAR FLOOR SPACE OR TURNING RADIUS
 OF ANY FIXTURE. SECTION 11-4.22.2.
 SEC 11-4.16 AND ALL SUBSECTIONS -
 SEC 11-4.19 AND ALL SUBSECTIONS - PLEASE
 PROVIDE DETAILS FOR COMPLIANCE.
 5) SHTS P100 & P101, FLOOR SINKS ARE RE-
 QUIRED FOR ALL INDIRECT WASTE. 802.3
 FLOOR DRAINS ARE NOT AN APPROVED INDIR-
 ECT WASTE RECEPTOR.
 6) SHTS P100 & P101 DISHWASHER SHALL
 DRAIN INTO THE SANITARY SYSTEM NOT THE
 GREASE LINE PER UTILITY DEPT.
 7) SHTS P100P101 WATER RISER DIAGRAM.
 WATER HAMMER ARRESTORS ARE REQUIRED AT
 ALL QUICK CLOSING VALVES, (ICE MACHINE,
 DISHWASHER) PER 406.9. THE LOCATION
 SHALL BE IN AN "EFFECTIVE RANGE" NEAR
 THE FIXTURE, NOT AT THE TOP OF THE DROP
 IN CEILING PER PDI-WH 201 AND MANUFACT-
 URE INSTALLATION INSTRUCTIONS.
 8) SHTS P100 & P101 VENT REQUIRED FOR
 GREASE LINE AS IT ENTERS BLDG TO VENT
 GREASE TANK.
 9) THE FOLLOWING COMMENTS ARE FOR THE
 NATURAL GAS SYSTEM. INFORMATION REQUIRED
 FOR GAS PERMIT APPLICATION. (SEPARATE
 PERMIT REQUIRED)
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE SEC. 401.8 THRU
 402.5.2 & TABLES 402(1) THRU 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC 402.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377