Plan Review Details - Permit 02111239
Plan Review Stops For Permit 02111239
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-14 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 13:10 Rev Time 0.00
Received By btrobaug Date 2003-01-14 Time 12:29 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-16 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 12:22 Rev Time 0.50
Received By btrobaug Date 2002-12-16 Time 11:57 Sent To M
Notes
2002-12-16 00:00:00SENT TO HAROLD MOSER./WRT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:53 Rev Time 0.00
Received By btrobaug Date 2003-01-17 Time 15:52 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-14 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 12:22 Rev Time 0.00
Received By btrobaug Date 2003-01-13 Time 12:22 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-12-26 Cont ID  
Sent By btrobaug Date 2002-11-19 Time 14:28 Rev Time 0.00
Received By jgomez Date 2002-11-19 Time 14:28 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-17 Cont ID  
Sent By hmoser Date 2002-12-17 Time 18:26 Rev Time 0.50
Received By hmoser Date 2002-12-17 Time 18:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-12-14 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 12:34 Rev Time 0.33
Received By hmoser Date 2002-12-14 Time 07:39 Sent To E
Notes
2002-12-14 00:00:00NO MECHANICAL PLANS
 PLAN REVIEW BY H.M.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-17 Cont ID  
Sent By kstevens Date 2003-01-17 Time 17:47 Rev Time 0.50
Received By kstevens Date 2003-01-17 Time 17:46 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:53 Rev Time 1.00
Received By kstevens Date 2002-12-10 Time 16:54 Sent To Z
Notes
2002-12-10 00:00:00PLAN REVIEW FOR PLUMBING ONLY - GAS TO
 BE SUBMITTED BY L&R GAS COMPANY SEPAR-
 ATELY.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-01-23 Cont ID  
Sent By jgomez Date 2003-01-23 Time 13:04 Rev Time 1.50
Received By jgomez Date 2003-01-23 Time 11:51 Sent To  
Notes
2003-01-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-ROOF ZONE #3 DOESN'T APPLY GABLE ENDS
 ONLY. IT APPLIES TO CORNERS AS WELL
 FOR FASTENER TYPE AND SPACING. SEE
 SEC. 2306.1 CITY AMENDMENTS TO FBC/01.
 2-SUPPORTS FOR WWM IN CONCRETE SLAB TO
 COMPLY WITH SECTION 1909.3 FBC 2001.
 3-PROVIDE COMPLETE FRAMING DETAIL FOR
 ARCHED OPENINGS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-PROVIDE COMPLETE SECTION/DETAIL FOR
 CONSTRUCTION OF KNEE WALL AT ENTRY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-SPECIFY CONNECTORS AT TOP AND BOTTOM
 OF WOOD COLUMNS THAT RESIST THE UPLIFT
 LOADS CALCULATED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 6-CLARIFY ROOF FRAMING AT REAR PORCH.
 WHERE ARE TRUSSES RESTING ON IF THERE
 IS NOT BEAM THERE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7-PROVIDE UPDATED PRODUCT APPROVAL FOR
 ROOF TILE.
 8-PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOWS WITH THE SIZES SHOWN ON PLANS.
 9-PROVIDE UL LISTING AND SPECS FOR BBQ.
 10-PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS WITH SIDELITES AND TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 PRODUCT APPROVAL SUBMITTED IS TO BE
 USED WITH WINDOWS ONLY, NOT DOORS.
 11-PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-12-26 Cont ID  
Sent By jgomez Date 2002-12-26 Time 12:21 Rev Time 3.00
Received By jgomez Date 2002-12-26 Time 12:21 Sent To  
Notes
2002-12-26 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE SIZE OF NAIL FOR ROOF SHEATHING
 AT ZONE 3. SEE TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001.
 2-SPECIFY CONCRETE SLAB JOINTS. SEE SEC.
 1909.3 FBC 2001.
 3-PROVIDE COMPLETE STRUCTURAL DETAIL FOR
 HANGING OF A/C UNITS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 4-PROVIDE COMPLETE FRAMING DETAIL FOR
 ARCHED OPENINGS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 5-PROVIDE COMPLETE SECTION/DETAIL FOR
 CONSTRUCTION OF KNEE WALL AT ENTRY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-CONNECTORS SPECIFIED FOR WOOD COLUMN
 AT MASTER BEDROOM DOESN'T RESIST THE
 CALCULATED UPLIFT LOADS. REVISEAS
 REQUIRED. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7-CLARIFY ROOF FRAMING AT REAR PORCH.
 WHERE ARE TRUSSES RESTING ON IF THERE
 IS NOT BEAM SHOWN. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-PRODUCT APPROVAL FOR ROOF TILE IS
 EXPIRED. RESUBMIT UPDATED ONE.
 9-PROVIDE PRODUCT APPROVAL FOR FIXED
 WINDOWS WITH THE SIZES SHOWN ON PLANS.
 10-PROVIDE UL LISTING AND SPECS FOR BBQ.
 11-A)PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS WITH SIDELITES AND TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS.
 (NOTE: PRODUCT APPROVAL IS FOR WINDOW
 ASSEMBLIES ONLY, NOT FOR DOORS)
 B)PROVIDE PRODUCT APPROVAL FOR SLIDING
 GLASS DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 (NOTE: HEAD RECEPTOR IS NOT ALLOWED ON
 PRODUCT APPROVAL SUBMITTED. SEE THE
 LIMITATIONS ON PAGE 2 OF PRODUCT APPRO
 VAL).
 12-GLASS BLOCK TO BE SAFETY GLASS IF THE
 UNIFORM FACE THICKNESS IS LESS THAN
 0.25". SEE SEC. 2405.2.2 FBC 2001.

Review Stop Z ZONING
Rev No 2 Status P Date 2003-01-17 Cont ID  
Sent By sgraham Date 2003-01-17 Time 12:24 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-11 Cont ID  
Sent By btrobaug Date 2003-01-14 Time 13:10 Rev Time 0.25
Received By sgraham Date   Time   Sent To M
Notes
***NONE***