Plan Review Details - Permit 02111234
Plan Review Stops For Permit 02111234
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-28 Cont ID  
Sent By jwitmer Date 2003-02-28 Time 09:25 Rev Time 2.55
Received By jwitmer Date 2003-02-28 Time 07:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-02-24 Cont ID  
Sent By dpalmer Date 2003-02-27 Time 18:32 Rev Time 1.25
Received By jwitmer Date 2003-02-24 Time 14:52 Sent To  
Notes
2003-02-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02111234
 ADD: 616 CLEARWATER PARK RD
 CONT: FINFROCK
 TEL: (407)293-4000
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) COMMENT # (4) PLEASE PROVIDE THE VERT
 ICAL CLEARENCE FOR ACCESSIBLE VAN AND
 THE PASSENGER LOADING ZONE. INFORMATION
 SUBMITTED IS FOR VAN ACCESS ONLY. NO
 INFORMATION ON THE PASSENGER LOADING
 ZONE?
 JIM WITMER
 PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-08 Cont ID  
Sent By jwitmer Date 2003-01-08 Time 16:18 Rev Time 5.50
Received By jwitmer Date 2003-01-08 Time 16:18 Sent To  
Notes
2003-01-08 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT:02111234
 ADD: 616 CLEARWATER PARK RD
 CONT: FINFROCK CONSTRUCTION
 TEL: (407)293-4000
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) 105.3 INSPECTION SERVICE, RESIDENT
 INSPECTOR REQUIRED FOR BUILDINGS 3 STOR-
 IES AND MORE.
  
 3) TABLE 600 ISSUES NORTH FACE OVER THE
 ALLOWABLE 20%. EXAMPLE 10.5'X 122.66=
 1287.93 FTX20%= ALLOWABLE OPENINGS OF
 257.58 SQ FT. SECOND FLOOR
 THIRD FLOOR OVER BY 10 SQ FT , 1ST FLOOR
 OK! IN DECREASING THE ALLOWABLE AREA ON
 THE SECOND FLOOR THE % OF OPENINGS IS
 21.34 %
  
 4) 11-4.6.5 PLEASE PROVIDE THE VERTICAL
 CLEARENCE FOR ACCESSIBLE VAN AND THE
 PASSENGER LOADING ZONE.
  
 5)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 MISSING INFORMATION?
  
 6) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 7)3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE
 AND HOT GASES TO THE OUTER AIR IN CASE
 OF FIRE.
  
 8)3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 9)3003.6.3 THE AREA OF THE VENTS
 SHALL BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 10)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2003-07-18 Cont ID  
Sent By dpalmer Date 2003-07-18 Time 09:14 Rev Time 0.25
Received By dpalmer Date 2003-07-18 Time 09:14 Sent To  
Notes
2003-07-18 00:00:00WAITING FOR SECOND SIGNED AND SEALED
 COPY.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-04-21 Cont ID  
Sent By shernand Date 2003-07-17 Time 13:30 Rev Time 0.33
Received By dpalmer Date 2003-04-21 Time 07:35 Sent To  
Notes
2003-04-21 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT REVISED PLANS
 DONE BY THE ENGINEER OF RECORD.
 PLEASE HAVE SIGNED, DATED AND SEALED
 AS REQ`D UNDER FS 471.025
  
 2)NOTE: PLEASE ALSO INCLUDE TITLE BLOCK
 FOR ENGINEER OF RECORD AS REQ`D UNDER
 FS/FAC 61G15-23.002
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-27 Cont ID  
Sent By shernand Date 2003-04-16 Time 13:43 Rev Time 0.50
Received By dpalmer Date 2003-02-27 Time 18:32 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-19 Time 10:07 Rev Time 1.50
Received By dpalmer Date 2003-02-19 Time 10:07 Sent To  
Notes
2003-02-19 00:00:00**************** UNSAT ****************
  
 PLEASE NOTE, WHILE LOOKING FOR MORE
 INFORMATION ON FIRE PUMP SIZE, A CALL
 WAS PLACED TO THE ELECTRICAL DESIGNER
 OF RECORD. AFTER A SHORT CONVERSATION
 IT WAS BROUGHT TO OUR ATTENTION THE
 FIRE PUMP WAS NO LONGER GOING TO BE
 ELEC. PLEASE SUBMIT REVISED PLANS AND
 SUBMIT ANY INFORMATION FOR FIRE PLAN
 REVIEW FOR DISEL FIRE PUMP.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-09 Cont ID  
Sent By dpalmer Date 2002-12-09 Time 07:48 Rev Time 1.00
Received By dpalmer Date 2002-12-09 Time 07:48 Sent To  
Notes
2002-12-09 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE CLARIFY LIGHTING IN
 ELEV / ELC RM TO MEET 700-16
  
 2)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 TO FOOTER STEEL AN COLD WATER(IF ANY)
 PER 250-50.
  
 3)NOTE: PLEASE CLARIFY OCP FOR FIRE
 PUMP, PLEASE SEE 695-4. RATED FOR LOCK
 ROTOR.
  
 4)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUNDING BETWEEN MAIN DISC AND
 PANEL/FIRE PUMP. 250-24/250-122
  
 5)NOTE: PLEASE CLARIFY GROUND FOR
 TRANSFORMER PER 250-30
  
 6)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT ON MAIN SERVICE ALSO/ BETWEEN MAIN
 /DISC`S , PANEL A AND PANEL B. ETC.
 SIZE PER 250-122.
  
 7)NOTE: PLEASE NOTE, ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.(LIGHTING
 ). 215-3/230-42 ETC.
  
 8)NOTE; PLEASE NOTE, AS PER LOCAL AMEND-
 -MENTS, NO ALUM CONDUCTORS MAY BE USED
 FOR GROUNDING OR BONDING. PLEASE ALSO
 NOTE, NO ALUM CONDUCTORS ARE PERMITTED
 FOR ANY PURPOSE SMALLER THAN #2.
 250-62/310-2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-02-13 Cont ID  
Sent By mcarsill Date 2003-02-13 Time 13:06 Rev Time 0.00
Received By mcarsill Date 2003-02-13 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 10:24 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 10:23 Sent To  
Notes
2002-12-18 00:00:001) IF FS 553.895 (2) IS BEING REFERENCED
 THEN THE PLANS SHOULD ALSO MAKE
 REFERENCE THAT A 20 FOOT SEPARATION
 IS REQUIRED BETWEEN THE BUILDING AND
 PARKING GARAGE THUS ALLOWING THE
 EXCEPTION TO THE STATUE FOR OPEN PARKING
 GARAGES NOT BEING SPRINKLER PROTECTED.
  
 2) ALL SHAFTS THAT ARE LARGE ENOUGH FOR
 PERSONS TO FALL INTO MUST BE IDENTIFIED
 WITH SIGNAGE INDICATING "SHAFTWAY" IN
 SIX INCH HIGH RED LETTERS ON A WHITE
 BACKGROUND.
  
 3) PLEASE INDICATE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR 43"CHAIN LINK
 FENCE INSIDE WALL AT OPENINGS.
  
 4) TITLE PAGE AND ELECTRICAL PAGES DO
 NOT MATCH. TITLE PAGE INDICATES NO
 FIRE ALARM SYSTEM BUT ELECTRICAL PAGES
 DISPLAYS A FIRE ALARM SYSTEM.
  
 5) PLANS DO NOT REFLECT STANDPIPE
 SYSTEM INSTALLATION. ONLY CALCULATIONS
 FOR THE STANDPIPE HAS BEEN PROVIDED.
 ONLY ONE SET OF PLANS WERE LOCATED.
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2003-07-17 Cont ID  
Sent By shernand Date 2003-07-17 Time 13:30 Rev Time 0.00
Received By shernand Date 2003-07-17 Time 13:30 Sent To E
Notes
2003-07-17 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2003-05-09 Cont ID  
Sent By shernand Date 2003-05-09 Time 09:24 Rev Time 0.00
Received By shernand Date 2003-05-09 Time 09:24 Sent To  
Notes
2003-05-09 00:00:00COMM BOARD #49

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-04-16 Cont ID  
Sent By shernand Date 2003-04-16 Time 13:43 Rev Time 0.00
Received By shernand Date 2003-04-16 Time 13:43 Sent To E
Notes
2003-04-16 00:00:00DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:23 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 08:23 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-02-11 Cont ID  
Sent By dpalmer Date 2003-02-11 Time 13:33 Rev Time 0.00
Received By dpalmer Date 2003-02-11 Time 13:32 Sent To  
Notes
2003-02-11 00:00:00TO COMM BOARD #45

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-02-04 Cont ID  
Sent By sgraham Date 2003-02-11 Time 09:48 Rev Time 0.00
Received By dpalmer Date 2003-02-04 Time 12:45 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 17:31 Rev Time 0.00
Received By btrobaug Date 2003-01-17 Time 17:30 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 18:16 Rev Time 0.00
Received By btrobaug Date 2002-11-26 Time 18:15 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-19 Cont ID  
Sent By btrobaug Date 2002-11-19 Time 14:49 Rev Time 0.00
Received By btrobaug Date 2002-11-19 Time 14:49 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-02-18 Cont ID  
Sent By pkrauss Date 2003-02-18 Time 10:32 Rev Time 0.55
Received By pkrauss Date 2003-02-18 Time 09:32 Sent To  
Notes
2003-02-18 00:00:00PROVISO:
 1.PENETRATIONS THRU WALLS HAVING 1HR
 FIRE RESISTANCE RATING REQUIRE
 PROTECTION BY MEANS OF FIRE DAMPER
  
 2.EXHAUST AIR SHALL NOT BE DIRECTED
 ONTO WALKWAY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-11 Cont ID  
Sent By pkrauss Date 2002-12-11 Time 11:38 Rev Time 1.25
Received By pkrauss Date 2002-12-11 Time 10:15 Sent To  
Notes
2002-12-11 00:00:00DENIED:MECHANICAL PERMIT 02120745
  
 STRUCTURAL DWGS NOT SEALED IN ACCORDANCE
 WITH F.S. 471.025.
  
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 PLEASE PROVIDE INFORMATION ON THE MEANS
 OF VENTILATION FOR THE ELEVATOR MACHINE
 ROOM, FIRE PUMP ROOM, AND ELECTRICAL
 ROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-24 Cont ID  
Sent By kstevens Date 2003-03-24 Time 13:23 Rev Time 0.50
Received By kstevens Date 2003-03-24 Time 13:23 Sent To  
Notes
2003-03-24 00:00:00REVISION OK - RWL CHANGED WHERE IT EXITS
 BLDG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-27 Cont ID  
Sent By sthyng Date 2003-03-24 Time 08:23 Rev Time 2.50
Received By kstevens Date 2002-12-27 Time 09:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-02-11 Cont ID  
Sent By sgraham Date 2003-02-11 Time 09:48 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2003-02-04 Time 12:45 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-11-21 00:00:00DENIED, NEED MINOR AMENDMENT