Plan Review Details - Permit 02110846
Plan Review Stops For Permit 02110846
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-12-13 Cont ID  
Sent By jgomez Date 2002-12-12 Time 14:42 Rev Time 0.50
Received By btrobaug Date 2002-12-13 Time 13:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 09:54 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 09:54 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-07 Cont ID  
Sent By hmoser Date 2002-12-07 Time 14:17 Rev Time 0.33
Received By hmoser Date 2002-12-07 Time 14:17 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-02 Cont ID  
Sent By jleech Date 2002-12-02 Time 17:40 Rev Time 0.25
Received By jleech Date 2002-12-02 Time 17:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By sgraham Date 2002-11-18 Time 13:42 Rev Time 0.33
Received By jleech Date 2002-12-02 Time 17:11 Sent To  
Notes
2002-12-02 00:00:00PAGE MP2 IS MISSING. NO PLUMBING RISER
 DIAGRAM.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-12-12 Cont ID  
Sent By jgomez Date 2002-12-12 Time 14:42 Rev Time 0.00
Received By jgomez Date 2002-12-12 Time 14:31 Sent To E
Notes
2002-12-12 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 2-FLOOD ZONE A8. NEED THE ELEVATION
 CERTIFICATE.
 3-2ND FLOOR FRAMING PLAN:
 PROVIDE DRAFSTOPPING AT AREAS NOT TO
 EXCEED 500 S.F. SEC. 2305.2.2 FBC 2001
 4-SPECIFY SIZE OF ANCHOR BOLT AND WASHER
 FOR GARAGE STRUCTURAL BUCK DETAIL.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-34SH WINDOWS DON'T PROVIDE THE 24" MIN
 CLEAR HEIGHT. ALSO, MAKE SURE THAT
 24+5 SH WINDOWS PROVIDE THE 5.7 S.F.
 MIN. CLEAR OPENING REQUIRED BY SECTION
 105.4.4 FBC 2001.
 6-DETAIL S21 DOESN'T WORK FOR WOOD COL.
 P1 LOCATED AT GARAGE CORNER. REVISE/
 CLARIFY AS REQUIRED. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-REVISE CONNECTOR TC-1 SPECIFIED ON
 ROOF FRAMING PLAN AT FRONT ELEVATION.
 NEED WOOD TO WOOD HURRICANE CONNECTOR.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-18 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 09:54 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***