Plan Review Details - Permit 02110785
Plan Review Stops For Permit 02110785
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-03-07 Cont ID  
Sent By sthyng Date 2003-03-12 Time 16:48 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-07 Cont ID  
Sent By btrobaug Date 2003-03-07 Time 07:38 Rev Time 0.00
Received By btrobaug Date 2003-03-07 Time 07:38 Sent To B
Notes
2003-03-07 00:00:00TO HHP./WRT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-21 Cont ID  
Sent By dpalmer Date 2002-11-21 Time 09:11 Rev Time 0.75
Received By dpalmer Date 2002-11-21 Time 09:11 Sent To  
Notes
2002-11-21 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE SUPPLY ENGINEERING FOR
 LIGHT POLE WIND LOADING PER FBC 140MPH.
  
 2)NOTE: PLEASE NOTE, ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%.215-3,
 230-42.
  
 3)NOTE: PLEASE PROVIDE COPY OF CONTRACT
 TO VERIFY VALUE OF WORK. PLEASE NOTE,
 UNDER ADMINISTRATIVE CODE 104.6.5. VALUE
 IS ALL LABOR AND MATERIALS EVEN IF
 OWNER SUPPLIED.
  
 PLEASE NOTE, PLANS WERE ONLY SUBMITTED
 FOR PLAN REVIEW AND WOULD NEED TO HAVE
 AN ELECTRICAL CONTRACTOR SIGNED ON FOR
 ALL ELECTRICAL WORK TO BE DONE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANREVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-12 Cont ID  
Sent By sthyng Date 2003-03-12 Time 16:48 Rev Time 0.00
Received By sthyng Date 2003-03-12 Time 16:48 Sent To B
Notes
2003-03-12 00:00:00TO HP DESK