Plan Review Details - Permit 02110771
Plan Review Stops For Permit 02110771
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-15 Cont ID  
Sent By btrobaug Date 2003-01-15 Time 16:05 Rev Time 0.75
Received By btrobaug Date   Time   Sent To B
Notes
2003-01-15 00:00:00TO LUIS ./WRT

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 17:06 Rev Time 1.00
Received By btrobaug Date 2002-12-10 Time 16:39 Sent To P
Notes
2002-12-10 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS,AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 3} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E.
  
 4} PLEASE NOTE KITCHEN COUNTER-
 SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 6} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210-52.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-06-26 Cont ID  
Sent By shernand Date 2003-06-26 Time 13:39 Rev Time 0.00
Received By shernand Date 2003-06-26 Time 13:39 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-13 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2002-11-13 Time 14:48 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-17 Cont ID  
Sent By shernand Date 2003-06-26 Time 13:39 Rev Time 0.40
Received By pkrauss Date 2003-01-17 Time 11:40 Sent To  
Notes
2003-01-17 00:00:00PROVISO ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-11 Cont ID  
Sent By kstevens Date 2002-12-10 Time 17:58 Rev Time 0.35
Received By pkrauss Date 2002-12-11 Time 08:59 Sent To R
Notes
2002-12-11 00:00:00NO PLANS SUBMITTED FOR REVIEW.
 MANUAL J CALCS INDICATE A 12 SEER
 EFFICIENCY RATING & ENERGY CALCS ONLY
 CALL FOR 11 SEER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-12-10 Cont ID  
Sent By btrobaug Date 2002-12-10 Time 17:08 Rev Time 0.25
Received By kstevens Date 2002-12-10 Time 17:58 Sent To M
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-01-16 Cont ID  
Sent By rmcdouga Date 2003-01-16 Time 16:15 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-01-16 00:00:00BUILDING PROVISO
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GLAZED OUTSWING DOUBLE DOORS
 - STRUCTURAL WINDOW MULLIONS
  
 2) PROVIDE A SIGNED AND SEALED DRAWING
 OF THE MASONRY PARAPET WALLS INDICATING
 THE STEEL REINFORCEMENT (VERTICAL AND
 HORIZONTAL) THAT IS CAPABLE OF RESISTING
 A 140 MPH WINDLOAD.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2003-01-09 Cont ID  
Sent By pkrauss Date 2002-12-11 Time 09:10 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-16 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE (2) COPIES OF SITE PLAN
 INDICATING THE LOCATION OF THE STRUCTURE
 ON THE LOT SIGNED AND SEALED BY THE
 DESIGNER OF RECORD OR (2) COPIES OF A
 SIGNED AND SEALED SURVEY SHOWING THE
 STRUCTURES LOCATION.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) INDICATE THE NEGATIVE AND POSITIVE
 WINDLOAD PRESSURES FOR ALL EXTERIOR
 WINDOW AND DOOR OPENINGS. CLARIFY THE
 DESIGN WIND PRESSURES ON A4. ARE THESE
 WORST CASE DESIGN PRESSURES?
  
 5) SPECIFY THE ROOF SHEATHING THICKNESS
 AND NAILING REQUIREMENTS.SEE CITY OF WPB
 AMENDMENTS TO FBC TABLE 2306.1.
  
 6) PROVIDE BUCK ATTACHMENT DETAILS FOR
 WINDOWS AND DOORS. SEE FBC 1707.4.4.2.
  
 7)INDICATE ATTIC VENTILATION. FBC 2309.7
  
 8) INDICATE ACCESS TO ATTIC SPACE.
 FBC 2309.6.
  
 9) PROVIDE A WALL/CEILING SECTION
 SHOWING FURRING, INSULATION, FIREBLOCK-
 ING, INTERIOR FINISH, TIE BEAM, ETC.
  
 10) SPECIFY WINDOW TYPES AND SIZES ON
 THE PLANS. BEDROOM WINDOWS ARE REQUIRED
 TO PROVIDE EMERGENCY EGRESS AND HAVE
 SPECIFIC CLEAR OPENING SIZES AND AREA
 SEE FBC 1005.4.
  
 11) SAFETY GLASS IS REQUIRED IN THE BATH
 ROOM WINDOWS THAT ARE IN THE TUB AND ARE
 WITHIN 3 FEET HORIZONTALLY OF THE SHOWER
 PER FBC 2405.2.1.
  
 12) SAFETY GLASS IS REQUIRED IN THE
 WINDOWS BESIDE THE FRONT DOOR, WHICH ARE
 WITHIN 2 FEET OF THE DOOR. SEE FBC
 2405.2.1.
  
 13) INDICATE ON THE PLANS THAT THE
 FINISH FLOOR ELEVATION IS A MINIMUM OF
 4"ABOVE FINISH GRADE AND THE BOTTOM OF
 THE FOOTING IS A MINIMUM OF 12" BELOW
 GRADE. SEE CITY AMENDMENTS 1804.1.7 AND
 FBC 1804.1.3.
  
 14) PROVIDE A DETAIL OF THE BOND BEAM
 INDICATING THE SIZE AND NUMBER OF
 HORIZONTAL REINFORCEMENT.
  
 15) SPECIFY THE SIZE AND NUMBER OF
 VERTICAL REINFORCEMENT IN EACH FILLED
 CELL.
  
 16) SPECIFY THE LINTELS ABOVE THE DOORS
 AND WINDOWS. PROVIDE A LINTEL SCHEDULE.
  
 17) PROVIDE DETAILS FOR CONSTRUCTING
 ARCH OPENING ABOVE FRENCH DOORS,PARAPET
 WALLS, ETC.
  
 18) SPECIFY CONNECTORS FOR ROOF TRUSSES.
  
 19) SPECIFY THE CEILING HEIGHTS, BEAM
 HEIGHTS, ROOF HEIGHT, ETC.
  
 20) INDICATE THE ROOF SLOPE, SCUPPER
 LOCATION, GUTTER & DOWN SPOUT LOCATIONS,
 ETC. SEE FBC 1804.1.6
  
 21) INDICATE TERMITE TREATMENT ON PLANS
 PER FBC 1816.1.
  
 22) INDICATE ON PLANS THAT WWM IN THE
 SLAB WILL BE SUPPORTED AS REQUIRED BY
 FBC 1909.3.
  
 24) THE ENERGY CALCULATION FORM IS
 REQUIRED TO BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 25) SHEETS ONE AND TWO OF THE DRAWINGS
 SUBMITTED WITH THE PRODUCT APPROVAL FOR
 THE STANLEY OUTSWING OPAQUE STEEL DOOR
 DO NOT BELONG WITH THIS PRODUCT APPROVAL
 THE NOA NUMBER, DATE, DRAWING NUMBERS
 ARE DIFFERENT. SUBMIT THE COMPLETE
 PACKAGE WITH THE CORRECT DRAWINGS.
  
 26) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - CIRCLE TOP FIXED GLASS WINDOWS
 - FRENCH DOORS
 - HORIZONTAL & VERTICAL STRUCTURAL
 MULLIONS
 - FRONT DOOR
  
 27) IF YOU ARE USING IMPACT GLAZING,
 SPECIFY THIS ON THE PLANS AND HIGHLIGHT
 OR CIRCLE IT ON THE PRODUCT APPROVAL.
  
 28)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-10 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 14:48 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
***NONE***