Plan Review Details - Permit 02110750
Plan Review Stops For Permit 02110750
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-12-19 Cont ID  
Sent By pkrauss Date 2002-12-06 Time 15:19 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-16 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 10:45 Rev Time 0.75
Received By btrobaug Date   Time   Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-25 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 08:23 Rev Time 0.00
Received By btrobaug Date 2002-11-25 Time 13:34 Sent To P
Notes
2002-11-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 TO PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG,LIST SAME ON
 SCHEDULE.
  
 3} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 4} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 5} PLEASE NOTE PANEL LOCATION
 NEEDS TO MEET 110-26,LOCATION ON PLANS
 IN RELATIONSHIP WITH W/D IS IN VIOLAION.
  
 6} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 7} PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50. SIZE PER 250-66
  
 8} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210-52.
  
 9} PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
 INCLUDES KITCHEN ISLANDS.
  
 10} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ'D PER 210-52E.
  
 11} SHOW LOCATION OF METER & DISCONNECT
 ON PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-16 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 08:22 Rev Time 0.00
Received By btrobaug Date 2003-01-15 Time 08:22 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-13 Cont ID  
Sent By dpalmer Date 2002-11-13 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2002-11-13 Time 13:40 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-12-12 Cont ID  
Sent By pkrauss Date 2002-12-12 Time 12:30 Rev Time 0.20
Received By pkrauss Date   Time   Sent To  
Notes
2002-12-12 00:00:00DAVID GOODEN (OWNER) WILL NOT BE
 INSTALLING A/C AT THIS TIME.SEPARATE
 PERMIT REQUIRED FOR HVAC

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-06 Cont ID  
Sent By pkrauss Date 2002-12-06 Time 14:28 Rev Time 0.35
Received By pkrauss Date 2002-12-06 Time 14:23 Sent To B
Notes
2002-12-06 00:00:00DENIED:
  
 NO PLANS OR ANY MECHANICAL INFORMATION
 SUBMITTED FOR REVIEW.
 INDICATE IF EQUIPMENT WILL BE NEWOR
 IS IT EXISTING?
 PROVIDE ENERGY & MANUAL J CALCULATIONS.
 PROVIDE INFORMATION ON EQUIPMENT (MAKE,
 MODEL, BTU'S & SEER OF THE CONDENSER).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-18 Cont ID  
Sent By kstevens Date 2003-01-18 Time 07:48 Rev Time 0.50
Received By kstevens Date 2003-01-18 Time 07:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-21 Cont ID  
Sent By btrobaug Date 2003-01-16 Time 10:45 Rev Time 0.33
Received By pschmitz Date   Time   Sent To  
Notes
2002-11-21 00:00:00ADD VENT TO W/M. PES