| 2002-11-25 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARY CHANGES |
| | TO PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG,LIST SAME ON |
| | SCHEDULE. |
| | |
| | 3} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| | DWELLING UNIT. ROOMS WITH BATHS AND OR |
| | CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| | PER NFPA-72 2-2.1.1.1. |
| | IN THE VICINITY OF BEDROOMS AND CLOSE |
| | PROXIMITY OF STAIRWAYS. 2-5.2.1.3 |
| | 3'FT FROM BATHS/KITCHENS.2-5.2.1.6 |
| | |
| | 4} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | 5} PLEASE NOTE PANEL LOCATION |
| | NEEDS TO MEET 110-26,LOCATION ON PLANS |
| | IN RELATIONSHIP WITH W/D IS IN VIOLAION. |
| | |
| | 6} PLEASE NOTE KITCHEN COUNTER- |
| | -SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5. |
| | |
| | 7} PLEASE SHOW GROUNDING ELECTRODE |
| | GOING TO BUILDING STEEL AND COLD WATER |
| | PER 250-50. SIZE PER 250-66 |
| | |
| | 8} PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2',6',12' RULE PER 210-52. |
| | |
| | 9} PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECT--ED PER 210-8-A-6. |
| | INCLUDES KITCHEN ISLANDS. |
| | |
| | 10} PLEASE NOTE FRONT AND REAR |
| | RECEPTS REQ'D PER 210-52E. |
| | |
| | 11} SHOW LOCATION OF METER & DISCONNECT |
| | ON PLAN. |
| | |