Plan Review Details - Permit 02110594
Plan Review Stops For Permit 02110594
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2003-05-22 Cont ID  
Sent By jwitmer Date 2003-05-22 Time 13:37 Rev Time 0.11
Received By jwitmer Date 2003-05-22 Time 13:37 Sent To  
Notes
2003-05-22 00:00:00REVISION: BALCONYOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2003-04-25 Cont ID  
Sent By shernand Date 2003-05-08 Time 13:12 Rev Time 0.33
Received By jwitmer Date 2003-04-25 Time 14:20 Sent To  
Notes
2003-04-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02110594
 ADD: 1310GREENWOOD DR
 CONT: CONSTRUCTION ENTERPRISES
 TEL: (561)719-7673
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 REVISION:
 ACTION : DENIED
  
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8 1/2X11 PLANS NOT SIGNED/ SEALED BY
 THE DESIGN PROFESSIONAL.
  
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-03-18 Cont ID  
Sent By shernand Date 2003-04-22 Time 15:53 Rev Time 0.33
Received By jwitmer Date 2003-03-18 Time 12:51 Sent To  
Notes
2003-03-18 00:00:00REV 3/17/03 TOP OF SLAB TO BE ABOVE
 7'-6"N.G.V.D.JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-20 Cont ID  
Sent By jwitmer Date 2003-02-20 Time 11:59 Rev Time 0.75
Received By jwitmer Date 2003-02-20 Time 11:58 Sent To  
Notes
2003-02-20 00:00:00 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 02110594
 ADDRESS: 131 GREENWOOD DR
 CONT: CONSTRUCTION ENTERPRISES
 TELL # (561) 689-9433
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OF
 PLANS.104.2.1.2 ADMINISTRATIVE CODE.
  
 *****PROVISO*****
  
 A SEPERATE PERMIT SHALL BE REQUIRED FOR
 STORM SHUTTERS, WAS MISSING THE KEY
 PLAN AND INSTALLATION ANCHOR SCHEDULE.
 A COPY PROVIDED WITH FIELD SET OF PLANS
 WITH COMMENTS.
 BUILDING PLAN REVIEW
 JIM WITMER

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-02-19 Cont ID  
Sent By btrobaug Date 2003-02-20 Time 11:48 Rev Time 1.44
Received By jwitmer Date 2003-02-19 Time 11:24 Sent To  
Notes
2003-02-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02110594
 ADD: 131 GREENWOOD DR
 CONT: O/B GRIFFIN, MELISSA
 TEL: (561)719-7673
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 DENIED
  
 1) MISSING ORIGINAL APPLICATION AND
 O/B DISCLOSURE STATEMENT
  
 2) RADON FEES DUE $13.96
  
 3) NOTICE OF COMMENCEMENT REQUIRED BE-
 FORE ISSUANCE OF PERMIT, RECORDED COPY
  
 4)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5) COMMENT # 5 FROM PREVIOUS REVIEW:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 THE PRODUCT APPROVAL REPORT IS ONLY
 PART OF WHAT IS REQUIRED, A SAMPLE SHEET
 IS ATTACHED FOR AN INSTALATION SCHEDULE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-12 Cont ID  
Sent By btrobaug Date 2003-02-12 Time 10:16 Rev Time 2.25
Received By jwitmer Date 2002-12-12 Time 13:15 Sent To  
Notes
2002-12-12 00:00:00BUILDING PLAN REVIEW
 PERMIT: 02110594
 ADD: 131 GREENWOOD DR
 CONT: O/B GRIFFIN, DAVID
 TEL: (561) 689-9433
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) CHAPTER 12 OF THE CITY CODE, FLOOD-
 ZONE A5 ADDITIONS TO EXISTING BUILDINGS
 ARE TO BE SET FINISH FLOOR @ 7'-6", NOT
 18" ABOVE CROWN OF THE ROAD. NOTE ANY
 A/C PAD OR POOL EQUIPMENT ARE TO BE SET
 AT THE 7'-6" (SLAB) HEIGHT.
  
 2) SHEET A-1 INDICATES THAT THE CITY IS
 LOCATED IN A HIGH VELOCITY HURRICANE
 ZONE, THIS IS INCORRECT, ONLY DADE &
 BROWARD COUNTIES ARE LOCATED IN THIS
 ZONE, CORRECT.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 MISSING THE (4) INTERNAL PRESSURE
 COEFFICIENT.
  
 4)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) FRONT DOOR PECKY CYPRESS SITE
 SPECIFIC
 B) FRENCH DOORS W/ GLAZING
 C) FIXED WINDOWS
 D) CASEMENT WINDOWS SQUARE HEAD
 E) CASEMENT WINDOWS ARCHED HEAD (BATH)
 F) MULLION- HORIZONTAL USAGE
 G) STORM SHUTTERS / IF LARGE MISSLE
 GLAZING ISN'T USED
 H) ROOFING ASSEMBLIES
 1. FLAT ROOF
 2. CLAY TILE ASSEMBLIES
  
 5) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 6)1606.4.4 ANCHOR METHODS. PROVIDE
 INFORMATION FOR INSTALLATION OF DOOR
 AND WINDOW BUCKS.
 1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 7)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 8)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 9) SHEET A5 ROOF FRAMING PLAN & NOTES
 INDICATE USE OF HUGHES STRAPS & MODEL #.
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 HUGHES IS NO LONGER IN BUSINESS,
 NEW VALUES & MODEL # UNDER USP!
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-03-18 Cont ID  
Sent By btrobaug Date 2003-03-18 Time 12:59 Rev Time 0.50
Received By btrobaug Date 2003-03-18 Time 12:59 Sent To P
Notes
2003-03-18 00:00:00PLUMBING RISER ON ELECTRICAL SHEET./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-02-20 Cont ID  
Sent By sthyng Date 2003-03-18 Time 11:25 Rev Time 1.00
Received By btrobaug Date 2003-02-12 Time 09:32 Sent To B
Notes
2003-02-12 00:00:00PROVISO
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY CHANGES
 ON PLANS,AND RESUBMIT FOR REVIEW.
  
 1} THE FEEDERS FROM THE METER TO THE
 DISCONNECT ARE NOT RATED FOR 300 AMPS/
 310-15(B)(6).
  
 2} THE RISER DIAGRAM SHOWS 1-3 1/2"
 CONDIT WITH 2/0'S TO BOTH PANELS,PLEASE
 CLARIFY.
  
 3} THERE IS A NOTE AT THE BOTTOM OF E-1
 THAT INDICATES A 200 AMP SERVICE IS
 BEING PROVIDED, AND THE EXISTING 100
 AMP TO REMAIN,THEN SAY'S TO BE
 UPGRADED. PLEASE CORRELATE NOTES AND
 DRAWINGS.THE RISERSHOWS A 300 AMP
 SERVICE.
  
 4} PLEASE INDICATE THE DISCONNECT
 LOCATION ON THE STRUCTURE.
  
 5} THE GEC SIZE FOR THE SERVICE MUST BE
 #2 PER 250-66,THE NOTE ON THE RISER
 INDICATES #4 OR #2,PLEASE CORRECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2003-01-31 Time 16:34 Rev Time 2.00
Received By btrobaug Date 2002-12-03 Time 12:18 Sent To B
Notes
2002-12-03 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES ON
 THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} CORRECT THE WIRE SIZES ON THE RISER
 DIAGRAM.6-350 MCM WONT TERMINATE IN A
 200 AMP PANEL OR METER ENCLOSURE.
  
 3} PLEASE SUBMIT LOAD CALCAULATIONS
 PER 220,215-5.ALL NEW LOADS PLUS
 EXISTING.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3.THE "POWDER
 ROOM"MUST BE 20A AND #12AWG.ALSO.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 6} PLEASE SHOW THE METER AND PANEL
 LOCATIONS ON THE PLAN.
  
 7} INSTALL A LIGHT,210-70(A),&
 RECEPTACLE(210-63)IN THE ATTIC AT THE
 LOCATION OF THE AHU.
  
 8} THE WHIRPOOL MUST BE GFI PROTECTED
 PER 680-70.
  
 9} PLEASE CORRELATE OCP WITH
 WIRE SIZES.NOTE #10 TO DRYER ON A 2/40.
  
 10}SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 13:12 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 13:12 Sent To B
Notes
2003-05-08 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-04-22 Cont ID  
Sent By shernand Date 2003-04-22 Time 15:53 Rev Time 0.00
Received By shernand Date 2003-04-22 Time 15:53 Sent To B
Notes
2003-04-22 00:00:00JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-18 Cont ID  
Sent By sthyng Date 2003-03-18 Time 11:24 Rev Time 0.00
Received By sthyng Date 2003-03-18 Time 11:24 Sent To E
Notes
2003-03-18 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-31 Cont ID  
Sent By btrobaug Date 2003-01-31 Time 16:34 Rev Time 0.00
Received By btrobaug Date 2003-01-31 Time 16:33 Sent To E
Notes
2003-01-31 00:00:00IN BOX./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-12 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 17:27 Rev Time 0.00
Received By btrobaug Date 2002-11-08 Time 17:27 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-03-24 Cont ID  
Sent By kstevens Date 2003-03-24 Time 09:01 Rev Time 0.50
Received By kstevens Date 2003-03-24 Time 09:01 Sent To B
Notes
2003-03-24 00:00:00REVISION - SANT. RISER DIAGRAM - NO
 CHANGES - RED LINED

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-27 Cont ID  
Sent By btrobaug Date 2003-03-18 Time 13:04 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-11-27 00:00:00APPR,PES

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-18 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 17:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
***NONE***