Plan Review Details - Permit 02110586
Plan Review Stops For Permit 02110586
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-16 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 16:54 Rev Time 0.25
Received By btrobaug Date 2002-12-16 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-20 Cont ID  
Sent By btrobaug Date 2002-11-20 Time 13:52 Rev Time 0.25
Received By btrobaug Date 2002-11-20 Time 13:47 Sent To  
Notes
2002-11-20 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 THERE IS A HOLD ON THIS PROPERTY FOR
 IRRIGATION WORK WITHOUT A PERMIT.A
 PERMIT CAN NOT BE ISSUED FOR THIS
 PROPERTY UNTILL THAT FEE IS SATISFIED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392