Plan Review Details - Permit 02110524
Plan Review Stops For Permit 02110524
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-21 Cont ID  
Sent By hpiskura Date 2002-11-21 Time 13:34 Rev Time 0.00
Received By hpiskura Date 2002-11-21 Time 10:22 Sent To  
Notes
2002-11-21 00:00:00THIS IS A GROUP M OCCUPANCY, SEE FBC
 310.1 AND REQUIRES TWO INDEPENDENT
 EXITS.SEE FBC 1004.2.1
  
 EGRESS IS NOT PERMITTED THROUGH THE
 KITCHEN AND SIMILAR AREAS, AS SHOWN ON
 THE PLANS.SEE FBC 1001.1.3.PLEASE
 REVISE AS NECESSARY.
  
 THE PLANS MAKE REFERENCE TO THE SBC,
 FLORIDA IS CURRENTLY UNDER THE 2001
 FLORIDA BUILDING CODE.PLEASE REVISE
 AS NECESSARY AND ENSURE COMPLIANCE WITH
 SAME.
  
 DO NOT QUOTE THE CODE AS A SUBSTITUTE
 FOR SPECIFIC DESIGN INFORMATION.SEE
 FBC 104.2.1.
  
 SHOW THE WIND LOAD PRESSURES FOR THE
 STORE FRONT SYSTEM.SEE FBC 1606.1.7.
  
 PLEASE PROVIDE A CLEAR SCOPE OF WORK
 THAT IS TO BE ACCOMPLISHED WITH THESE
 PLANS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-11-20 Cont ID  
Sent By dpalmer Date 2002-11-20 Time 10:22 Rev Time 0.75
Received By dpalmer Date 2002-11-20 Time 10:22 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-11-22 Cont ID  
Sent By mcarsill Date 2002-11-22 Time 11:46 Rev Time 0.00
Received By mcarsill Date 2002-11-22 Time 11:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-08 Cont ID  
Sent By btrobaug Date 2002-11-08 Time 16:37 Rev Time 0.00
Received By btrobaug Date 2002-11-08 Time 16:37 Sent To  
Notes
2002-11-08 00:00:00TO BOARD#1./WRT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-12-05 Cont ID  
Sent By pkrauss Date 2002-12-05 Time 08:15 Rev Time 0.00
Received By pkrauss Date 2002-12-02 Time 09:35 Sent To  
Notes
2002-12-05 00:00:00SIGNED OFF ON PLANS 12-2-02
 PREVIOUS PERMIT 01080557 (EXPIRED)

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-05 Cont ID  
Sent By kstevens Date 2002-12-05 Time 10:37 Rev Time 1.25
Received By kstevens Date 2002-12-05 Time 10:37 Sent To  
Notes
2002-12-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. ALSO SEE 410.1, IF A WATER
 COOLER IS SUBSTITUTED IT SHALL BE ARI-
 1010 COMPLIANT AND MANUF. INFO IS REQD.
 2) SEPARATE GAS PERMIT IS REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 APPLICATION OF GAS PERMIT.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC. 402.2
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***