| Plan Review Stops For Permit 02110511 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-01-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-06 |
Time |
06:17 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-01-06 |
Time |
06:17 |
Sent To |
P |
|
| Notes |
| 2003-01-06 00:00:00 | ************** NOTES REDLINED ********* | | | | | | 1)NOTE: PLEASE VERFIY AHU KW LOAD. | | | PANEL SCHEDULE AND LOAD CALCS DO NOT | | | CORRELATE. PLEASE CORRELATE OCP/KW/AWG. | | | | | | 2)NOTE: PLEASE SEE WALL/PENINSULAR. | | | EITHER MISSING RECEPT FOR WALL SPACE | | | (210-52) OR RECEPT FOR PENINSULAR | | | COUNTERTOP. 210-52-C-3. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | BEFORE ROUGH INSPECTION. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVEIW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-12-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-31 |
Time |
11:36 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2002-12-06 |
Time |
14:24 |
Sent To |
P |
|
| Notes |
| 2002-12-06 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW LOCATION OF PANEL | | | ON PLANS.215-5 | | | | | | 2)NOTE: PLEASE NOTE, BATH CIRCUITS ARE | | | SHOWN AT 15A #14 AWG. PLEASE SEE 210-52D | | | 210-11-C3. MUST BE 20A #12. | | | | | | 3)NOTE: PLEASE INCLUDE FOOTER STEEL AS | | | PART OF THE GROUNDING ELECTRODE SYSTEM | | | AS REQ`D PER 250-50. | | | | | | 4)NOTE: PLEASE NOTE, ALL OUTLETS SERVING | | | KITCHEN COUNTERSPACE ARE TO BE SHOWN AS | | | GFI/GFI PROTECTED. 210-8-A-6 | | | | | | 5)NOTE: PLEASE NOTE MISSING GFI RECEPT | | | FOR PENINSULAR IN KITCHEN. 210-52-C-3 | | | | | | 6)NOTE: PLEASE NOTE, SD IN HALL TO BE | | | A MIN OF 3' FROM BATH. NFPA-72 8-1.4.1.6 | | | | | | 7)NOTE: PLEASE NOTE, MECH PLANS SHOW | | | EXHAUST FANS IN EACH OF THE TWO BATHS, | | | BUT NOT SHOWN ON ELECTRICAL PLANS. | | | | | | 8)NOTE: PLEASE NOTE, DISC FOR AHU TO BE | | | SHOWN PER 440-11.215-5 | | | | | | PLEASE VERIFY HEATSTRIP FOR HOUSE. SHOWN | | | AS 5KW AND MAY BE TOO SMALL FOR A HOUSE | | | THIS SIZE. | | | | | | JUST A NOTE,, PLEASE NOTE IF THERE IS | | | GOING TO BE ANY LOW VOLTAGE, CATV OR | | | TELEPHONES, PLEASE SHOW LOCATION AT THIS | | | TIME IN ORDER TO BE INCLUDED ON THIS | | | PERMIT. IF NONE SHOWN, A SEPARATE PERMIT | | | APPLICATION/FEES/LAYOUT WILL BE REQ`D AT | | | A LATER DATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-02-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-26 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-26 |
Time |
09:11 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-12-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-12-31 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-12-31 |
Time |
11:36 |
Sent To |
E |
|
| Notes |
| 2002-12-31 00:00:00 | TO DV PALMER'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-08 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-08 |
Time |
16:59 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-17 |
Time |
11:07 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2003-01-17 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2003-01-17 00:00:00 | MECHANICAL PERMIT 02110533 | | | | | | PROVISO:R/A REQUIRED FROM BEDROOM | | | AREAS AS PER 2001 FBC(M) 601.4. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2003-01-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-10 |
Time |
12:33 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-01-10 |
Time |
12:03 |
Sent To |
R |
|
| Notes |
| 2003-01-10 00:00:00 | DENIED:MECHANICAL PERMIT 02110533 | | | | | | PLANS INDICATE EQUIPMENT AS JANITROL | | | MOD CK24 & AC24.ENERGY & MAUNAL J | | | CALCS INIDCATE A MINIMUM OF A 3 TON | | | UNIT, SQ FTG IS 1774 CONDITIONED FLOOR | | | AREA.PLEASE SUBMIT MANUFACTURER | | | SUBMITTAL FOR THE EQUIPMENT.IT WOULD | | | APPEAR THE EQUIPMENT LISTED ON THE | | | PLAN IS NOT THE PROPER CAPACITY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-12-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-10 |
Time |
11:35 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-12-12 |
Time |
11:49 |
Sent To |
R |
|
| Notes |
| 2002-12-12 00:00:00 | DENIED:MECHANICAL PERMIT 02110533 | | | | | | 1.PLEASE PROVIDE 2 SETS OF ENERGY & | | | AND MANUAL J CALCULATIONS. | | | | | | 2.APPLIANCES IN GARAGE SHALL BE | | | PROTECTED FROM DAMAGE AS PER 2001 FBC(M) | | | 303.4. | | | | | | 3.CONDENSATE SHALL DISCHARGE A MINIMUM | | | OF 12" FROM THE BUILDING STRUCTURE, 2001 | | | FBC 1503.4.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-01-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-10 |
Time |
11:35 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-01-10 |
Time |
11:34 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-12-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-06 |
Time |
06:17 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-12-06 |
Time |
16:40 |
Sent To |
M |
|
| Notes |
| 2002-12-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT 3 OF 4, SANITARY RISER DIAGRAM, | | | DOES NOT REFLECT FLOOR PLAN AND DOES NOT | | | MEET CODE. PLEASE SEE RED LINE CORRECT- | | | IONS AND MAKE CHANGES, AND RESUBMIT | | | PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2003-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2003-01-13 |
Time |
07:52 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-01-13 00:00:00 | BUILDING PROVISO | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) PROVIDE (2) COPIES OF A KEY PLAN AND | | | INSTALLATION SCHEDULE FOR STORM PANELS, | | | PRIOR TO INSTALLATION. | | | | | | 3)PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - EXTERIOR DOORS | | | - OVERHEAD GARAGE DOOR | | | - STRUCTURAL WINDOW MULLIONS | | | - ROOF COVERING | | | THE PRODUCT APPROVALS FOR THESE ITEMS | | | ARE REQUIRED TO BE SUBMITTED FOR REVIEW | | | BEFORE THEY ARE INSTALLED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2003-01-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-10 |
Time |
12:42 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-12-18 00:00:00 | BUILDING DENIED | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2)FL. BLD CODE 1606.1.7 THE FOLLOWING | | | INFORMATION RELATED TO WIND SHALL BE | | | SHOWN ON THE CONSTRUCTION DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | | CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN | | | WIND PRESSURES IN TERMS OF PSF. | | | INDICATE THE IMPORTANCE FACTOR AND THE | | | INTERNAL PRESSURE COEFFICIENT ON THE A | | | PLANS. | | | | | | 3) INDICATE ACCESS TO ATTIC SPACE AS | | | REQUIRED BY FBC 2309.6. | | | | | | 4) REVISE NOTE 1 ON SHEET 1 TO COMPLY | | | WITH CITY OF WPB AMENDMENTS TO FBC TABLE | | | 2306.1 FOR ROOF SHAETHING NAILING | | | REQUIREMENTS. | | | | | | 5) REVISE NOTE 2 ON SHEET 1, 3/8" RIB | | | LATH IS REQUIRED TO BE NAILED AT EVERY | | | RIB (4") PER FBC 2504.2.2 AND ASTM C1063 | | | 710.1.1. | | | | | | 6) CLARIFY WALL SECTION ON SHEET 2 TO | | | INDICATE THE BOTTOM OF FOOTING TO BE A | | | MINIMUM OF 12" BELOW FINAL GRADE AND THE | | | FINISH FLOOR TO BE A MINIMUM OF 4" ABOVE | | | FINAL GRADE. SEE FBC 1804.1.3 AND CITY | | | AMENDMENTS 1804.1.7. | | | | | | 7) INDICATE FIREBLOCKING ON THE WALL | | | SECTION ON SHEET 2 WHERE THE FURRED | | | SPACE ON THE WALL MEETS THE CEILING. | | | SEE FBC 2305.1.4. | | | | | | 8) THE FOUNDATION PLAN ON SHEET 3 IS | | | MISSING THE VERTICAL REINFORCEMENT AT | | | THE LEFT SIDE OF THE GARAGE. PLEASE | | | CORRECT. | | | | | | 9) PROVIDE SECTION THROUGH SLAB AT AT | | | THE 6" STEP IN GARAGE. | | | | | | 10) PROVIDE A DETAIL OF THE ARCHES AT | | | THE FRONT PORCH INDICATING HOW THEY ARE | | | TO BE CONSTRUCTED. | | | | | | 11) THE OWNER/AGENT IS REQUIRED TO SIGN | | | AND DATE THE ENERGY CALC. FORM. PROVIDE | | | TWO COPIES OF ENERGY CALCULATIONS. | | | | | | 12)PROVIDE (2) COPIES OF A KEY PLAN AND | | | INSTALLATION SCHEDULE FOR STORM PANELS | | | INDICATING THE SPECIFIC TYPES OF ANCHORS | | | AND SPACING. | | | | | | 13) PROVIDE (2) CURRENT AND COMPLETE | | | COPIES OF SBCCI OR METRO-DADE PRODUCT | | | APPROVALS FOR: | | | - EXTERIOR DOORS | | | - OVERHEAD GARAGE DOOR | | | - ROOF COVERING | | | | | | 14)STRUCTURE IS LOCATED ON ALAMANDA ROAD | | | NOT AVENUE. PLEASE CORRECT SITE PLAN. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2003-01-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-26 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-12-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-08 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2002-12-06 |
Time |
08:13 |
Sent To |
P |
|
| Notes |
| 2002-12-06 00:00:00 | ERROR IN ENTRY.IT WAS DENIED BY | | | SHIRLEY NEEDS SITE PLAN. | | | OK WITH PLANS. PASSING TO ELECTRICAL MM |
|
|