Plan Review Details - Permit 02110511
Plan Review Stops For Permit 02110511
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 06:17 Rev Time 0.50
Received By dpalmer Date 2003-01-06 Time 06:17 Sent To P
Notes
2003-01-06 00:00:00************** NOTES REDLINED *********
  
 1)NOTE: PLEASE VERFIY AHU KW LOAD.
 PANEL SCHEDULE AND LOAD CALCS DO NOT
 CORRELATE. PLEASE CORRELATE OCP/KW/AWG.
  
 2)NOTE: PLEASE SEE WALL/PENINSULAR.
 EITHER MISSING RECEPT FOR WALL SPACE
 (210-52) OR RECEPT FOR PENINSULAR
 COUNTERTOP. 210-52-C-3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 BEFORE ROUGH INSPECTION. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVEIW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-06 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 11:36 Rev Time 1.00
Received By dpalmer Date 2002-12-06 Time 14:24 Sent To P
Notes
2002-12-06 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW LOCATION OF PANEL
 ON PLANS.215-5
  
 2)NOTE: PLEASE NOTE, BATH CIRCUITS ARE
 SHOWN AT 15A #14 AWG. PLEASE SEE 210-52D
 210-11-C3. MUST BE 20A #12.
  
 3)NOTE: PLEASE INCLUDE FOOTER STEEL AS
 PART OF THE GROUNDING ELECTRODE SYSTEM
 AS REQ`D PER 250-50.
  
 4)NOTE: PLEASE NOTE, ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO BE SHOWN AS
 GFI/GFI PROTECTED. 210-8-A-6
  
 5)NOTE: PLEASE NOTE MISSING GFI RECEPT
 FOR PENINSULAR IN KITCHEN. 210-52-C-3
  
 6)NOTE: PLEASE NOTE, SD IN HALL TO BE
 A MIN OF 3' FROM BATH. NFPA-72 8-1.4.1.6
  
 7)NOTE: PLEASE NOTE, MECH PLANS SHOW
 EXHAUST FANS IN EACH OF THE TWO BATHS,
 BUT NOT SHOWN ON ELECTRICAL PLANS.
  
 8)NOTE: PLEASE NOTE, DISC FOR AHU TO BE
 SHOWN PER 440-11.215-5
  
 PLEASE VERIFY HEATSTRIP FOR HOUSE. SHOWN
 AS 5KW AND MAY BE TOO SMALL FOR A HOUSE
 THIS SIZE.
  
 JUST A NOTE,, PLEASE NOTE IF THERE IS
 GOING TO BE ANY LOW VOLTAGE, CATV OR
 TELEPHONES, PLEASE SHOW LOCATION AT THIS
 TIME IN ORDER TO BE INCLUDED ON THIS
 PERMIT. IF NONE SHOWN, A SEPARATE PERMIT
 APPLICATION/FEES/LAYOUT WILL BE REQ`D AT
 A LATER DATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-26 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 09:11 Rev Time 0.00
Received By dpalmer Date 2003-02-26 Time 09:11 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-31 Cont ID  
Sent By dpalmer Date 2002-12-31 Time 11:36 Rev Time 0.00
Received By dpalmer Date 2002-12-31 Time 11:36 Sent To E
Notes
2002-12-31 00:00:00TO DV PALMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-08 Cont ID  
Sent By btrobaug Date 2002-11-08 Time 16:59 Rev Time 0.00
Received By btrobaug Date 2002-11-08 Time 16:59 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-01-17 Cont ID  
Sent By pkrauss Date 2003-01-17 Time 11:07 Rev Time 0.35
Received By pkrauss Date 2003-01-17 Time 11:07 Sent To  
Notes
2003-01-17 00:00:00MECHANICAL PERMIT 02110533
  
 PROVISO:R/A REQUIRED FROM BEDROOM
 AREAS AS PER 2001 FBC(M) 601.4.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-01-10 Cont ID  
Sent By pkrauss Date 2003-01-10 Time 12:33 Rev Time 0.30
Received By pkrauss Date 2003-01-10 Time 12:03 Sent To R
Notes
2003-01-10 00:00:00DENIED:MECHANICAL PERMIT 02110533
  
 PLANS INDICATE EQUIPMENT AS JANITROL
 MOD CK24 & AC24.ENERGY & MAUNAL J
 CALCS INIDCATE A MINIMUM OF A 3 TON
 UNIT, SQ FTG IS 1774 CONDITIONED FLOOR
 AREA.PLEASE SUBMIT MANUFACTURER
 SUBMITTAL FOR THE EQUIPMENT.IT WOULD
 APPEAR THE EQUIPMENT LISTED ON THE
 PLAN IS NOT THE PROPER CAPACITY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-12 Cont ID  
Sent By kstevens Date 2003-01-10 Time 11:35 Rev Time 0.35
Received By pkrauss Date 2002-12-12 Time 11:49 Sent To R
Notes
2002-12-12 00:00:00DENIED:MECHANICAL PERMIT 02110533
  
 1.PLEASE PROVIDE 2 SETS OF ENERGY &
 AND MANUAL J CALCULATIONS.
  
 2.APPLIANCES IN GARAGE SHALL BE
 PROTECTED FROM DAMAGE AS PER 2001 FBC(M)
 303.4.
  
 3.CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" FROM THE BUILDING STRUCTURE, 2001
 FBC 1503.4.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-10 Cont ID  
Sent By kstevens Date 2003-01-10 Time 11:35 Rev Time 0.50
Received By kstevens Date 2003-01-10 Time 11:34 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 06:17 Rev Time 0.50
Received By kstevens Date 2002-12-06 Time 16:40 Sent To M
Notes
2002-12-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 3 OF 4, SANITARY RISER DIAGRAM,
 DOES NOT REFLECT FLOOR PLAN AND DOES NOT
 MEET CODE. PLEASE SEE RED LINE CORRECT-
 IONS AND MAKE CHANGES, AND RESUBMIT
 PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-01-13 Cont ID  
Sent By rmcdouga Date 2003-01-13 Time 07:52 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2003-01-13 00:00:00BUILDING PROVISO
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) PROVIDE (2) COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS,
 PRIOR TO INSTALLATION.
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR DOORS
 - OVERHEAD GARAGE DOOR
 - STRUCTURAL WINDOW MULLIONS
 - ROOF COVERING
 THE PRODUCT APPROVALS FOR THESE ITEMS
 ARE REQUIRED TO BE SUBMITTED FOR REVIEW
 BEFORE THEY ARE INSTALLED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By pkrauss Date 2003-01-10 Time 12:42 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-12-18 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 INDICATE THE IMPORTANCE FACTOR AND THE
 INTERNAL PRESSURE COEFFICIENT ON THE A
 PLANS.
  
 3) INDICATE ACCESS TO ATTIC SPACE AS
 REQUIRED BY FBC 2309.6.
  
 4) REVISE NOTE 1 ON SHEET 1 TO COMPLY
 WITH CITY OF WPB AMENDMENTS TO FBC TABLE
 2306.1 FOR ROOF SHAETHING NAILING
 REQUIREMENTS.
  
 5) REVISE NOTE 2 ON SHEET 1, 3/8" RIB
 LATH IS REQUIRED TO BE NAILED AT EVERY
 RIB (4") PER FBC 2504.2.2 AND ASTM C1063
 710.1.1.
  
 6) CLARIFY WALL SECTION ON SHEET 2 TO
 INDICATE THE BOTTOM OF FOOTING TO BE A
 MINIMUM OF 12" BELOW FINAL GRADE AND THE
 FINISH FLOOR TO BE A MINIMUM OF 4" ABOVE
 FINAL GRADE. SEE FBC 1804.1.3 AND CITY
 AMENDMENTS 1804.1.7.
  
 7) INDICATE FIREBLOCKING ON THE WALL
 SECTION ON SHEET 2 WHERE THE FURRED
 SPACE ON THE WALL MEETS THE CEILING.
 SEE FBC 2305.1.4.
  
 8) THE FOUNDATION PLAN ON SHEET 3 IS
 MISSING THE VERTICAL REINFORCEMENT AT
 THE LEFT SIDE OF THE GARAGE. PLEASE
 CORRECT.
  
 9) PROVIDE SECTION THROUGH SLAB AT AT
 THE 6" STEP IN GARAGE.
  
 10) PROVIDE A DETAIL OF THE ARCHES AT
 THE FRONT PORCH INDICATING HOW THEY ARE
 TO BE CONSTRUCTED.
  
 11) THE OWNER/AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALC. FORM. PROVIDE
 TWO COPIES OF ENERGY CALCULATIONS.
  
 12)PROVIDE (2) COPIES OF A KEY PLAN AND
 INSTALLATION SCHEDULE FOR STORM PANELS
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 AND SPACING.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - EXTERIOR DOORS
 - OVERHEAD GARAGE DOOR
 - ROOF COVERING
  
 14)STRUCTURE IS LOCATED ON ALAMANDA ROAD
 NOT AVENUE. PLEASE CORRECT SITE PLAN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 2 Status P Date 2003-01-13 Cont ID  
Sent By dpalmer Date 2003-02-26 Time 09:11 Rev Time 0.00
Received By sgraham Date   Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-06 Cont ID  
Sent By btrobaug Date 2002-11-08 Time 16:59 Rev Time 0.00
Received By mmclean Date 2002-12-06 Time 08:13 Sent To P
Notes
2002-12-06 00:00:00ERROR IN ENTRY.IT WAS DENIED BY
 SHIRLEY NEEDS SITE PLAN.
 OK WITH PLANS. PASSING TO ELECTRICAL MM