Plan Review Details - Permit 02110484
Plan Review Stops For Permit 02110484
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-11-18 Cont ID  
Sent By pkrauss Date 2002-11-15 Time 12:38 Rev Time 0.00
Received By nmccray Date 2002-11-18 Time 10:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-15 Cont ID  
Sent By pkrauss Date 2002-11-15 Time 12:16 Rev Time 0.45
Received By pkrauss Date 2002-11-15 Time 12:01 Sent To FIRE
Notes
2002-11-15 00:00:00PROVISO:
  
 PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE 3M FIREWRAP ON THE
 JOBSITE AT THE OF INSPECTION.
  
 DUCTWORK SHALL NOT BE COVERED PRIOR TO
 INSPECTION OF WELDS.
  
 CLARIFY NOTE ON PLAN SHEET 2 OF 2
 BUILDING SECTION DETAIL #1, "ACCESS
 DOOR TO FIRE DAMPER IN MUA COLLAR".
 WILL A FIRE DAMPER BE INSTALLED IN THE
 MAKE-UP AIR DUCT?
  
 AS PER 2001 FBC(M) 506.3.14.3, EXHAUST
 OUTLETS SHALL BE LOCATED NOT LESS THAN
 10 FT FROM PARTS OF THE SAME OR
 CONTIGUOUS BUILDING OR ADJACENT PROPERTY
 LINE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.