Plan Review Details - Permit 02110421
Plan Review Stops For Permit 02110421
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-04 Cont ID  
Sent By nmccray Date 2002-12-04 Time 12:48 Rev Time 0.00
Received By nmccray Date 2002-12-04 Time 12:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 17:18 Rev Time 0.00
Received By mcarsill Date 2002-11-14 Time 17:52 Sent To  
Notes
2002-11-14 00:00:001) PLEASE PROVIDE A COPY OF THE CONTRACT
 FOR THE VALUE OF THE JOB. THE VALUE
 SHOULD INCLUDE WORK,PARTS,AND MATERIALS.
  
 2) ALL INITIATING DEVICES SHALL ACTIVATE
 THE REQUIRED FIRE ALARM SYSTEM. PLEASE
 REVISE THE SEQUENCE OF OPERATION NOTES
 WITH REGARDS TO MANUAL PULL STATIONS
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 A, STYLE D OR BE FULLY ADDRESSSABLE.
  
 4) THE FIRE ALARM SYSTEM SHALL BE TESTED
 PRIOR TO CALLING FOR COMPLETE INSPECTION
 FROM FIRE RESCUE.
  
 5) NO INITIATING DEVICES SHALL BE
 INSTALLED PRIOR TO TRADE CLEAN-UP
 ACTIVITIES.
  
 6) THE FIRE ALARM SYSTEM SHALL SUPERVISE
 THE FIRE PUMP, PUMP RUN, PUMP FAIL,
 AND PHASE REVERSAL.
  
 7) NO CUT SHEETS PROVIDED WITH FIRE
 ALARM DRAWINGS. PLEASE PROVIDE CUT
 SHEETS FOR ALL DEVICES PLANNED FOR USE.
  
 8) DISTANCES TO MANUAL PULL STATIONS
 SHALL NOT EXCEED 200 FEET.
  
 9) WHY ARE THERE NO AV DEVICES ON THE
 FOURTH FLOOR WALKWAY LIKE THEY ARE ON
 OTHER FLOORS OF THE BUILDING.
  
 10) PLEASE EXPLAIN ALL LIFE SAFETY
 MANUAL OVERRIDE NOTE AT THE FIRE ALARM
 CONTROL PANEL. PLEASE EXPLAIN NOTE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-21 Cont ID  
Sent By btrobaug Date 2002-11-21 Time 17:18 Rev Time 0.00
Received By btrobaug Date 2002-11-21 Time 17:18 Sent To FIRE
Notes
2002-11-21 00:00:00FIRE IN BOX./WRT.