Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-11-13 Cont ID  
Sent By btrobaug Date 2003-11-13 Time 17:59 Rev Time 0.50
Received By btrobaug Date 2003-11-13 Time 17:43 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-28 Cont ID  
Sent By dpalmer Date 2003-01-28 Time 14:27 Rev Time 1.00
Received By dpalmer Date 2003-01-28 Time 14:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-12-30 Cont ID  
Sent By dpalmer Date 2002-12-30 Time 09:34 Rev Time 0.50
Received By dpalmer Date 2002-12-30 Time 09:34 Sent To  
Notes
2002-12-30 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE NOTE, SAME PLANS WERE
 SUBMITTED BACK FOR ELECTRICAL REVIEW.
 PLEASE NOTE THAT THERE WAS A RESPONSE
 LETTER MENTIONING TO SEE NEW REVISED
 SHEETS AND NOTES, SAME SHEETS WERE
 BROUGHT BACK??
  
 PLEASE ADDRESS ORIG COMMENTS AND SUBMIT
 FOR REVIEW. IF THERE AREA ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-07 Cont ID  
Sent By dpalmer Date 2002-12-24 Time 10:08 Rev Time 0.50
Received By dpalmer Date 2002-11-07 Time 06:14 Sent To  
Notes
2002-11-07 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE NOTE, PLANS DO NOT SHOW
 WHAT SIZE OCP IS FEEDING BOTH "PEG AND
 GP"? PLEASE SHOW.
  
 2)NOTE: PLEASE NOTE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%. 215-3/230-42
 ETC.
  
 3)NOTE: PLEASE CLARIFY NEW OR EXISTING
 GFI RECEPT FOR RTU. 210-63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-16 Cont ID  
Sent By csiegber Date 2003-12-16 Time 09:55 Rev Time 0.00
Received By csiegber Date 2003-12-16 Time 09:55 Sent To M
Notes
2003-12-16 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-07 Cont ID  
Sent By csiegber Date 2003-11-07 Time 08:22 Rev Time 0.00
Received By csiegber Date 2003-11-07 Time 08:22 Sent To M
Notes
2003-11-07 00:00:00TO PK BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-24 Cont ID  
Sent By dpalmer Date 2002-12-24 Time 10:08 Rev Time 0.00
Received By dpalmer Date 2002-12-24 Time 10:08 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 17:52 Rev Time 0.00
Received By dpalmer Date 2002-11-06 Time 17:52 Sent To  
Notes
2002-11-07 00:00:00WRT PLACED ON BOARD #29.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-03-02 Cont ID  
Sent By pkrauss Date 2004-03-02 Time 11:05 Rev Time 0.30
Received By pkrauss Date 2004-03-02 Time 11:05 Sent To  
Notes
2004-03-02 00:00:00AS-BUILT DWG

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-12-22 Cont ID  
Sent By pkrauss Date 2003-12-22 Time 09:59 Rev Time 0.45
Received By pkrauss Date 2003-12-22 Time 09:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2003-01-23 Cont ID  
Sent By csiegber Date 2003-12-16 Time 09:55 Rev Time 0.15
Received By pkrauss Date 2003-01-23 Time 14:49 Sent To  
Notes
2003-01-23 00:00:00NO MECHANICAL REVISIONS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-13 Cont ID  
Sent By pkrauss Date 2002-11-13 Time 14:15 Rev Time 0.40
Received By pkrauss Date 2002-11-13 Time 14:15 Sent To  
Notes
***NONE***