| Plan Review Stops For Permit 02110313 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2003-04-07 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-30 |
Time |
15:31 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-04-07 |
Time |
09:16 |
Sent To |
B |
|
| Notes |
| 2003-04-07 00:00:00 | ************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE PLANS. PLANS WERE | | | SUBMITTED AS A RE-STAMP AND THEY HAVE | | | BEEN REVISED. SERVICE IS NOW SHOWN AS | | | 200A? | | | PLEASE ALSO SEE THAT THERE IS NO AIC | | | RATINGS SHOWN ANYMORE AS SHOWN ON LAST | | | SET.?? | | | PLEASE ALSO SEE, EQUIPMENT GROUNDING | | | CONDUCTOR IS STILL MISSING BETWEEN MAIN | | | DISC AND PANEL. | | | | | | | | | 2)NOTE: PLEASE SUBMIT TWO SETS OF PLANS | | | FOR REVIEW. PLEASE PAY FEES FOR REVISION | | | -S. PLEASE SHOW REVISIONS BY CLOUDS AND/ | | | /OR TRIANGLES AND DATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-02-13 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-14 |
Time |
13:57 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-13 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2003-02-13 00:00:00 | REDLINED EQUIP GRND. 250-122/250-24 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-24 |
Time |
06:37 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-01-24 |
Time |
06:37 |
Sent To |
P |
|
| Notes |
| 2003-01-24 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT, IT IS NOTED | | | FOR PANELS MAIN AND SUB-PANEL, BUT NOT | | | FOR MAIN DISCONNECT. 110-9 | | | | | | 2)NOTE: PLEASE MISSING EQUIPMENT GROUND- | | | ING CONDUCTORS BETWEEN MAIN DISC AND | | | PANEL "A" AND TO SUB PANEL. SIZE PER | | | 250-122. | | | | | | 3)NOTE: PLEASE SHOW HOW SUB PANEL IS | | | BEING FED. PLEASE SEE MAIN PANEL,PLEASE | | | NOTE NOTHING SHOWN FOR FEED TO SUB PANEL | | | | | | | | | 4)NOTE: PLEASE SEE CONNECTED LOAD ON | | | WHIRLPOOL TUB. SHOWN AS 20A ON 20A BRKR | | | PLEASE NOTE LOAD NOT TO EXCEED 80% OF | | | BRKR RATING.PLEASE ADJUST. | | | | | | 5)NOTE: PLEASE SEE 240-6 FOR STANDARD | | | OCP FOR AHU'S. | | | | | | 6)NOTE: PLEASE CLARIFY RISER SHOWING | | | ONE A/C UNIT FROM MAIN PANEL AND ONE | | | FROM SUB PANEL, PLEASE SEE PANEL SCHED-- | | | ULE AND NOTE BOTH ARE SHOWN FROM SUB- | | | -PANEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-11-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-17 |
Time |
15:45 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-11-27 |
Time |
08:16 |
Sent To |
M |
|
| Notes |
| 2002-11-27 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | NEW EQUIPMENT BEING INSTALLLED. PLEASE | | | NOTE, MAINS/PANELS/BRKRS ARE TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | 110-9/215-5 | | | | | | 2)NOTE: PLEASE NOTE; THERE ARE MANY | | | ITEMS ON LOAD CALCULATIONS THAT DO | | | NOT CORRELATE WITH PANEL SCHEDULE. | | | ALSO,ITEMS ON PANEL SCHEDULE THAT ARE | | | NO IN LOAD CALCS. | | | | | | 3)NOTE: PLEASE SEE 424-3C FOR MIN 125% | | | FOR OCP OF AHU`S. PLEASE SEE LOAD CALCS, | | | AHU`S SHOWN AT 10KW EACH. MIN OCP SHOULD | | | NOT BE 45A AND #8. | | | | | | 4)NOTE: PLEASE CLARIFY, LOAD CALCS SHOW | | | TWO GRARGE DOOR OPENERS AND PLANS ONLY | | | SHOW ONE? | | | | | | 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | CONDUCTOR GOING TO COLD WATER AND | | | FOOTER STEEL. PER 250-50 | | | | | | 6)NOTE: PLEASE SHOW CONDUCTOR SIZE | | | BETWEEN METER AND MAIN.215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVOEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-08-28 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-08-28 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-08-28 |
Time |
10:07 |
Sent To |
B |
|
| Notes |
| 2003-08-28 00:00:00 | TO JG DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-04-30 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-30 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-30 |
Time |
15:31 |
Sent To |
B |
|
| Notes |
| 2003-04-30 00:00:00 | LHATTEN FOR PLANS TO BE RESTAMPED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-03-27 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-27 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-27 |
Time |
08:50 |
Sent To |
P |
|
| Notes |
| 2003-03-27 00:00:00 | RESTAMP ONLY; SENT TO KS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-03-14 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-14 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-14 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2003-03-14 00:00:00 | SET NOT SEALED BY ARCHITECT, CALLED | | | DAVID WILSON (CONTACT PERSON) |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-17 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-01-17 |
Time |
15:45 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-06 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-06 |
Time |
17:10 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-01-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-01 |
Time |
17:29 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2003-01-29 |
Time |
14:44 |
Sent To |
B |
|
| Notes |
| 2003-01-29 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR REVIEW | | | MANUAL J CALCS CORRECTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-12-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-27 |
Time |
08:16 |
Rev Time |
0.25 |
| Received By |
hmoser |
Date |
2002-12-02 |
Time |
18:12 |
Sent To |
R |
|
| Notes |
| 2002-12-02 00:00:00 | PLAN DENIED | | | 1) NEED EVAPORATOR MODEL NUMBER ON | | | MANUAL (J) | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT.8390 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2003-09-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-06 |
Time |
21:01 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-09-06 |
Time |
21:01 |
Sent To |
|
|
| Notes |
| 2003-09-06 00:00:00 | REVISION OK - SANT. RISER DIAGRAM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2003-04-01 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-09-02 |
Time |
11:14 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-04-01 |
Time |
17:17 |
Sent To |
M |
|
| Notes |
| 2003-04-01 00:00:00 | DENIED | | | | | | RESTAMP DENIED - THE SANITARY RISER DIA- | | | GRAM DOES NOT MEET CODE REQUIREMENTS. | | | PLEASE SUBMIT A RISER DIAGRAM THAT WAS | | | APPROVED ON 1-25-3 | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-01-25 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-27 |
Time |
08:50 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-01-25 |
Time |
09:17 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-11-23 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-11-13 |
Time |
08:33 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2002-11-23 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2002-11-23 00:00:00 | PROVISO; | | | REVISED RISER DIAGRAM REQUIRED. MUST | | | MEET 2001 FBC PLUMBING REQUIREMENTS. SEE | | | SEC. 909.1 WET VENTS. | | | 1.THE WET VENT FOR THE BATHROOM GROUP | | | MUST BE AT THE UPSTREAM SIDE OF THE | | | FIXTURE IT SERVES. | | | 2.ONLY BATHROOM FIXTURES CAN DRAIN INTO | | | THE WET VENT FOR A BATHROOM GROUP. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2003-09-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-09-02 |
Time |
11:14 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2003-09-02 |
Time |
11:14 |
Sent To |
P |
|
| Notes |
| 2003-09-02 00:00:00 | ARCHITECT'S APPROVAL FOR CUTTING TOP | | | OF STEEL BUCKET. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-12-02 |
Time |
18:13 |
Rev Time |
2.50 |
| Received By |
lhatten |
Date |
2002-12-07 |
Time |
17:36 |
Sent To |
|
|
| Notes |
| 2002-12-09 00:00:00 | REVIEW & STAMPED PLANS 12/07/2002 | | | PROVISO | | | 1) NEED TO BRING IN SHUTTER LAYOUT FOR | | | HOUSE TO NUMBER OF OPENNINGS AND SIZES | | | OF PANELS | | | | | | 2) PAY ALL OTHER FEES -- | | | IMPACT FEES, NOC,AND RADON |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-11-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-06 |
Time |
17:11 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
P |
|
| Notes |
|
|