Plan Review Details - Permit 02110313
Plan Review Stops For Permit 02110313
Review Stop E ELECTRICAL
Rev No 4 Status F Date 2003-04-07 Cont ID  
Sent By shernand Date 2003-04-30 Time 15:31 Rev Time 0.50
Received By dpalmer Date 2003-04-07 Time 09:16 Sent To B
Notes
2003-04-07 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS. PLANS WERE
 SUBMITTED AS A RE-STAMP AND THEY HAVE
 BEEN REVISED. SERVICE IS NOW SHOWN AS
 200A?
 PLEASE ALSO SEE THAT THERE IS NO AIC
 RATINGS SHOWN ANYMORE AS SHOWN ON LAST
 SET.??
 PLEASE ALSO SEE, EQUIPMENT GROUNDING
 CONDUCTOR IS STILL MISSING BETWEEN MAIN
 DISC AND PANEL.
  
  
 2)NOTE: PLEASE SUBMIT TWO SETS OF PLANS
 FOR REVIEW. PLEASE PAY FEES FOR REVISION
 -S. PLEASE SHOW REVISIONS BY CLOUDS AND/
 /OR TRIANGLES AND DATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By sthyng Date 2003-03-14 Time 13:57 Rev Time 0.50
Received By dpalmer Date 2003-02-13 Time 08:49 Sent To  
Notes
2003-02-13 00:00:00REDLINED EQUIP GRND. 250-122/250-24

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 06:37 Rev Time 0.50
Received By dpalmer Date 2003-01-24 Time 06:37 Sent To P
Notes
2003-01-24 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT, IT IS NOTED
 FOR PANELS MAIN AND SUB-PANEL, BUT NOT
 FOR MAIN DISCONNECT. 110-9
  
 2)NOTE: PLEASE MISSING EQUIPMENT GROUND-
 ING CONDUCTORS BETWEEN MAIN DISC AND
 PANEL "A" AND TO SUB PANEL. SIZE PER
 250-122.
  
 3)NOTE: PLEASE SHOW HOW SUB PANEL IS
 BEING FED. PLEASE SEE MAIN PANEL,PLEASE
 NOTE NOTHING SHOWN FOR FEED TO SUB PANEL
  
  
 4)NOTE: PLEASE SEE CONNECTED LOAD ON
 WHIRLPOOL TUB. SHOWN AS 20A ON 20A BRKR
 PLEASE NOTE LOAD NOT TO EXCEED 80% OF
 BRKR RATING.PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 240-6 FOR STANDARD
 OCP FOR AHU'S.
  
 6)NOTE: PLEASE CLARIFY RISER SHOWING
 ONE A/C UNIT FROM MAIN PANEL AND ONE
 FROM SUB PANEL, PLEASE SEE PANEL SCHED--
 ULE AND NOTE BOTH ARE SHOWN FROM SUB-
 -PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-27 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:45 Rev Time 0.50
Received By dpalmer Date 2002-11-27 Time 08:16 Sent To M
Notes
2002-11-27 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW EQUIPMENT BEING INSTALLLED. PLEASE
 NOTE, MAINS/PANELS/BRKRS ARE TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 110-9/215-5
  
 2)NOTE: PLEASE NOTE; THERE ARE MANY
 ITEMS ON LOAD CALCULATIONS THAT DO
 NOT CORRELATE WITH PANEL SCHEDULE.
 ALSO,ITEMS ON PANEL SCHEDULE THAT ARE
 NO IN LOAD CALCS.
  
 3)NOTE: PLEASE SEE 424-3C FOR MIN 125%
 FOR OCP OF AHU`S. PLEASE SEE LOAD CALCS,
 AHU`S SHOWN AT 10KW EACH. MIN OCP SHOULD
 NOT BE 45A AND #8.
  
 4)NOTE: PLEASE CLARIFY, LOAD CALCS SHOW
 TWO GRARGE DOOR OPENERS AND PLANS ONLY
 SHOW ONE?
  
 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 CONDUCTOR GOING TO COLD WATER AND
 FOOTER STEEL. PER 250-50
  
 6)NOTE: PLEASE SHOW CONDUCTOR SIZE
 BETWEEN METER AND MAIN.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVOEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-28 Cont ID  
Sent By csiegber Date 2003-08-28 Time 10:07 Rev Time 0.00
Received By csiegber Date 2003-08-28 Time 10:07 Sent To B
Notes
2003-08-28 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-04-30 Cont ID  
Sent By shernand Date 2003-04-30 Time 15:31 Rev Time 0.00
Received By shernand Date 2003-04-30 Time 15:31 Sent To B
Notes
2003-04-30 00:00:00LHATTEN FOR PLANS TO BE RESTAMPED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-27 Cont ID  
Sent By sthyng Date 2003-03-27 Time 08:50 Rev Time 0.00
Received By sthyng Date 2003-03-27 Time 08:50 Sent To P
Notes
2003-03-27 00:00:00RESTAMP ONLY; SENT TO KS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-03-14 Cont ID  
Sent By sthyng Date 2003-03-14 Time 13:57 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 13:57 Sent To  
Notes
2003-03-14 00:00:00SET NOT SEALED BY ARCHITECT, CALLED
 DAVID WILSON (CONTACT PERSON)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:45 Rev Time 0.00
Received By btrobaug Date 2003-01-17 Time 15:45 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 17:11 Rev Time 0.00
Received By btrobaug Date 2002-11-06 Time 17:10 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-29 Cont ID  
Sent By kstevens Date 2003-04-01 Time 17:29 Rev Time 0.30
Received By pkrauss Date 2003-01-29 Time 14:44 Sent To B
Notes
2003-01-29 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 MANUAL J CALCS CORRECTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By dpalmer Date 2002-11-27 Time 08:16 Rev Time 0.25
Received By hmoser Date 2002-12-02 Time 18:12 Sent To R
Notes
2002-12-02 00:00:00PLAN DENIED
 1) NEED EVAPORATOR MODEL NUMBER ON
 MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-09-06 Cont ID  
Sent By kstevens Date 2003-09-06 Time 21:01 Rev Time 0.50
Received By kstevens Date 2003-09-06 Time 21:01 Sent To  
Notes
2003-09-06 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 3 Status F Date 2003-04-01 Cont ID  
Sent By jgomez Date 2003-09-02 Time 11:14 Rev Time 0.50
Received By kstevens Date 2003-04-01 Time 17:17 Sent To M
Notes
2003-04-01 00:00:00DENIED
  
 RESTAMP DENIED - THE SANITARY RISER DIA-
 GRAM DOES NOT MEET CODE REQUIREMENTS.
 PLEASE SUBMIT A RISER DIAGRAM THAT WAS
 APPROVED ON 1-25-3
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-25 Cont ID  
Sent By sthyng Date 2003-03-27 Time 08:50 Rev Time 0.33
Received By kstevens Date 2003-01-25 Time 09:17 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-23 Cont ID  
Sent By sgraham Date 2002-11-13 Time 08:33 Rev Time 0.50
Received By jleech Date 2002-11-23 Time 08:24 Sent To  
Notes
2002-11-23 00:00:00PROVISO;
 REVISED RISER DIAGRAM REQUIRED. MUST
 MEET 2001 FBC PLUMBING REQUIREMENTS. SEE
 SEC. 909.1 WET VENTS.
 1.THE WET VENT FOR THE BATHROOM GROUP
 MUST BE AT THE UPSTREAM SIDE OF THE
 FIXTURE IT SERVES.
 2.ONLY BATHROOM FIXTURES CAN DRAIN INTO
 THE WET VENT FOR A BATHROOM GROUP.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-09-02 Cont ID  
Sent By jgomez Date 2003-09-02 Time 11:14 Rev Time 0.25
Received By jgomez Date 2003-09-02 Time 11:14 Sent To P
Notes
2003-09-02 00:00:00ARCHITECT'S APPROVAL FOR CUTTING TOP
 OF STEEL BUCKET.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-12-09 Cont ID  
Sent By hmoser Date 2002-12-02 Time 18:13 Rev Time 2.50
Received By lhatten Date 2002-12-07 Time 17:36 Sent To  
Notes
2002-12-09 00:00:00REVIEW & STAMPED PLANS 12/07/2002
 PROVISO
 1) NEED TO BRING IN SHUTTER LAYOUT FOR
 HOUSE TO NUMBER OF OPENNINGS AND SIZES
 OF PANELS
  
 2) PAY ALL OTHER FEES --
 IMPACT FEES, NOC,AND RADON

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-13 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 17:11 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***