Plan Review Details - Permit 02110308
Plan Review Stops For Permit 02110308
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-02-13 Cont ID  
Sent By dpalmer Date 2003-02-13 Time 09:12 Rev Time 0.50
Received By dpalmer Date 2003-02-13 Time 09:12 Sent To  
Notes
2003-02-13 00:00:00EQUIPMENT GRNDS STILL MISSING,
 REDLINED. 250-122/250-24

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-01-24 Cont ID  
Sent By dpalmer Date 2003-01-24 Time 06:15 Rev Time 0.33
Received By dpalmer Date 2003-01-24 Time 06:15 Sent To P
Notes
2003-01-24 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL NEW SERVICE EQUIPMENT.IT IS NOTED
 SHOWN FOR PANELS, BUT NOT FOR MAIN DISC.
 110-9
  
 2)NOTE: MISSING EQUIPMENT GROUNDING
 CONDUCTORS BETWEEN MAIN DISC AND PANEL
 "A", ALSO MISSING BETWEEN "A" AND SUB-
 -PANEL? SIZE PER 250-122.
  
 3)NOTE: PLEASE SHOW HOW SUB PANEL IS
 BEING FED? PLEASE SEE PANEL SCHEDULE FOR
 "A", NOTHIN SHOWN FOR SUB PANEL. PLEASE
 SHOW OCP, AND LOAD.
  
 4)NOTE: PLEASE SEE CONNECTED LOAD ON
 WHIRLPOOL TUB. SHOWN AS 20A ON 20A BRKR,
 PLEASE NOTE, LOAD NOT TO EXCEED 80% OF
 BRKR. PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 240-6 FOR RATINGS
 OF OCP FOR AHU'S. SHOWN AS 65A BRKR.
  
 6)NOTE: PLEASE CLARIFY, RISER DIAGRAM
 SHOWS ONE A/C UNIT FROM SUB-PANEL AND
 ONE FROM MAIN PANEL, WHERE AS PANEL
 SCHEDULE FOR SUB-PANEL SHOWS BOTH??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIOEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER'
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-27 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:46 Rev Time 0.50
Received By dpalmer Date 2002-11-27 Time 11:26 Sent To M
Notes
2002-11-27 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMITAIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS, PANELS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110-9
  
 2)NOTE: PLEASE NOTE, THERE ARE MANY
 ITEMS ON PANEL SCHEDULE AND LOAD CALCS
 THAT DO NOT CORRELATE. PLEASE ADJUST.
 THERE ARE ALSO ITEMS ON LOAD CALCS
 NOT ON PANEL SCHEDULE?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE 424-3C FOR OCP OF
 AHU/HEAT. 125% MIN. AHU`S SHOWN AS 10KW
 W/ #8 AND 2P45A`S. PLEASE ADJUST
  
 4)NOTE: PLEASE CLARIFY LOAD CALCS.
 LIST TWO GARAGE DOOR OPENERS AND ONLY
 ONE SHOWN ON PLANS.
  
 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 CONDUCTOR TO FOOTER STEEL ALSO PER
 250-50.
  
 6)NOTE: PLEASE SHOW SIZE IF CONDUCTORS
 BETWEEN MAIN AND METER.215-5/310-15
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-08-28 Cont ID  
Sent By csiegber Date 2003-08-28 Time 10:10 Rev Time 0.00
Received By csiegber Date 2003-08-28 Time 10:09 Sent To B
Notes
2003-08-28 00:00:00TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-17 Cont ID  
Sent By btrobaug Date 2003-01-17 Time 15:46 Rev Time 0.00
Received By btrobaug Date 2003-01-17 Time 15:46 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 17:11 Rev Time 0.00
Received By btrobaug Date 2002-11-06 Time 17:11 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-29 Cont ID  
Sent By kstevens Date 2003-01-25 Time 09:10 Rev Time 0.25
Received By pkrauss Date 2003-01-29 Time 15:32 Sent To  
Notes
2003-01-29 00:00:00NO PLANS SUBMITTED FOR REVIEW.
 MANUAL J CALCS CORRECTED AS PER H. MOSER
 COMMENTS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By dpalmer Date 2002-11-27 Time 11:27 Rev Time 0.25
Received By hmoser Date 2002-12-02 Time 18:01 Sent To R
Notes
2002-12-02 00:00:00PLAN DENIED
 1) NEED EVAPORATOR MODEL NUMBER ON
 MANUAL (J)
 PLAN REVIEW BY HAROLD MOSER
 (561)659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-09-06 Cont ID  
Sent By kstevens Date 2003-09-06 Time 20:45 Rev Time 0.50
Received By kstevens Date 2003-09-06 Time 20:45 Sent To  
Notes
2003-09-06 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-01-25 Cont ID  
Sent By jgomez Date 2003-09-02 Time 09:37 Rev Time 0.33
Received By kstevens Date 2003-01-25 Time 09:09 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-11-23 Cont ID  
Sent By sgraham Date 2002-11-13 Time 08:32 Rev Time 0.50
Received By jleech Date 2002-11-23 Time 07:56 Sent To  
Notes
2002-11-23 00:00:00PROVISO;
 REVISED RISER DIAGRAM REQUIRED. MUST
 MEET 2001 FBC PLUMBING REQUIREMENTS.
 SEE SEC. 909.1 WET VENTS.
 1.THE WET VENT FOR THE BATHROOM GROUP
 MUST BE AT THE UP STREAM SIDE OF THE
 FIXTURES IT SERVES.
 2.ONLY BATHROOM FIXTURES CAN DRAIN INTO
 THE WET VENT FOR A BATHROOM GROUP.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT.8369

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2003-09-02 Cont ID  
Sent By jgomez Date 2003-09-02 Time 09:37 Rev Time 0.25
Received By jgomez Date 2003-09-02 Time 09:37 Sent To P
Notes
2003-09-02 00:00:00ARCHITECT'S LETTER STATING APPROVAL FOR
 CUTTING STEEL BUCKET.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2002-12-09 Cont ID  
Sent By hmoser Date 2002-12-02 Time 18:22 Rev Time 2.50
Received By lhatten Date 2002-12-07 Time 17:47 Sent To  
Notes
2002-12-09 00:00:00REVIEW & STAMPED PLANS 12/07/2002
 PROVISO
 1) NEED SHUTTER LAYOUT FOR HOUSE FOR ALL
 OPENNINGS AS TO NUMBER & SIZE
  
 2)NEED TO PAY ALL FEES - IMPACT, NOC,
 AND RADON

Review Stop Z ZONING
Rev No 1 Status P Date 2002-11-13 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 17:12 Rev Time 0.25
Received By sgraham Date   Time   Sent To P
Notes
***NONE***