| Plan Review Stops For Permit 02110308 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-02-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-13 |
Time |
09:12 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-13 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2003-02-13 00:00:00 | EQUIPMENT GRNDS STILL MISSING, | | | REDLINED. 250-122/250-24 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-24 |
Time |
06:15 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-01-24 |
Time |
06:15 |
Sent To |
P |
|
| Notes |
| 2003-01-24 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | ALL NEW SERVICE EQUIPMENT.IT IS NOTED | | | SHOWN FOR PANELS, BUT NOT FOR MAIN DISC. | | | 110-9 | | | | | | 2)NOTE: MISSING EQUIPMENT GROUNDING | | | CONDUCTORS BETWEEN MAIN DISC AND PANEL | | | "A", ALSO MISSING BETWEEN "A" AND SUB- | | | -PANEL? SIZE PER 250-122. | | | | | | 3)NOTE: PLEASE SHOW HOW SUB PANEL IS | | | BEING FED? PLEASE SEE PANEL SCHEDULE FOR | | | "A", NOTHIN SHOWN FOR SUB PANEL. PLEASE | | | SHOW OCP, AND LOAD. | | | | | | 4)NOTE: PLEASE SEE CONNECTED LOAD ON | | | WHIRLPOOL TUB. SHOWN AS 20A ON 20A BRKR, | | | PLEASE NOTE, LOAD NOT TO EXCEED 80% OF | | | BRKR. PLEASE ADJUST. | | | | | | 5)NOTE: PLEASE SEE 240-6 FOR RATINGS | | | OF OCP FOR AHU'S. SHOWN AS 65A BRKR. | | | | | | 6)NOTE: PLEASE CLARIFY, RISER DIAGRAM | | | SHOWS ONE A/C UNIT FROM SUB-PANEL AND | | | ONE FROM MAIN PANEL, WHERE AS PANEL | | | SCHEDULE FOR SUB-PANEL SHOWS BOTH?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIOEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER' | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-11-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-17 |
Time |
15:46 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2002-11-27 |
Time |
11:26 |
Sent To |
M |
|
| Notes |
| 2002-11-27 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMITAIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS, PANELS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. 110-9 | | | | | | 2)NOTE: PLEASE NOTE, THERE ARE MANY | | | ITEMS ON PANEL SCHEDULE AND LOAD CALCS | | | THAT DO NOT CORRELATE. PLEASE ADJUST. | | | THERE ARE ALSO ITEMS ON LOAD CALCS | | | NOT ON PANEL SCHEDULE? | | | PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE SEE 424-3C FOR OCP OF | | | AHU/HEAT. 125% MIN. AHU`S SHOWN AS 10KW | | | W/ #8 AND 2P45A`S. PLEASE ADJUST | | | | | | 4)NOTE: PLEASE CLARIFY LOAD CALCS. | | | LIST TWO GARAGE DOOR OPENERS AND ONLY | | | ONE SHOWN ON PLANS. | | | | | | 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | CONDUCTOR TO FOOTER STEEL ALSO PER | | | 250-50. | | | | | | 6)NOTE: PLEASE SHOW SIZE IF CONDUCTORS | | | BETWEEN MAIN AND METER.215-5/310-15 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-08-28 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-08-28 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-08-28 |
Time |
10:09 |
Sent To |
B |
|
| Notes |
| 2003-08-28 00:00:00 | TO JG DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-01-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-17 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-01-17 |
Time |
15:46 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-06 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-11-06 |
Time |
17:11 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-01-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-01-25 |
Time |
09:10 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-01-29 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2003-01-29 00:00:00 | NO PLANS SUBMITTED FOR REVIEW. | | | MANUAL J CALCS CORRECTED AS PER H. MOSER | | | COMMENTS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-12-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-27 |
Time |
11:27 |
Rev Time |
0.25 |
| Received By |
hmoser |
Date |
2002-12-02 |
Time |
18:01 |
Sent To |
R |
|
| Notes |
| 2002-12-02 00:00:00 | PLAN DENIED | | | 1) NEED EVAPORATOR MODEL NUMBER ON | | | MANUAL (J) | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT.8390 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-09-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-06 |
Time |
20:45 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-09-06 |
Time |
20:45 |
Sent To |
|
|
| Notes |
| 2003-09-06 00:00:00 | REVISION OK - SANT. RISER DIAGRAM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-01-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-09-02 |
Time |
09:37 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-01-25 |
Time |
09:09 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-11-23 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-11-13 |
Time |
08:32 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2002-11-23 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2002-11-23 00:00:00 | PROVISO; | | | REVISED RISER DIAGRAM REQUIRED. MUST | | | MEET 2001 FBC PLUMBING REQUIREMENTS. | | | SEE SEC. 909.1 WET VENTS. | | | 1.THE WET VENT FOR THE BATHROOM GROUP | | | MUST BE AT THE UP STREAM SIDE OF THE | | | FIXTURES IT SERVES. | | | 2.ONLY BATHROOM FIXTURES CAN DRAIN INTO | | | THE WET VENT FOR A BATHROOM GROUP. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT.8369 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2003-09-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-09-02 |
Time |
09:37 |
Rev Time |
0.25 |
| Received By |
jgomez |
Date |
2003-09-02 |
Time |
09:37 |
Sent To |
P |
|
| Notes |
| 2003-09-02 00:00:00 | ARCHITECT'S LETTER STATING APPROVAL FOR | | | CUTTING STEEL BUCKET. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2002-12-09 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-12-02 |
Time |
18:22 |
Rev Time |
2.50 |
| Received By |
lhatten |
Date |
2002-12-07 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2002-12-09 00:00:00 | REVIEW & STAMPED PLANS 12/07/2002 | | | PROVISO | | | 1) NEED SHUTTER LAYOUT FOR HOUSE FOR ALL | | | OPENNINGS AS TO NUMBER & SIZE | | | | | | 2)NEED TO PAY ALL FEES - IMPACT, NOC, | | | AND RADON |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-11-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-06 |
Time |
17:12 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
P |
|
| Notes |
|
|