Plan Review Details - Permit 02110243
Plan Review Stops For Permit 02110243
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-04-08 Cont ID  
Sent By shernand Date 2003-05-27 Time 16:27 Rev Time 0.05
Received By pkrauss Date 2003-04-08 Time 11:28 Sent To  
Notes
2003-04-08 00:00:00APPROVED PER HAROLD PISKURA 4-1-03

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-11-21 Cont ID  
Sent By hpiskura Date 2002-11-21 Time 09:41 Rev Time 0.00
Received By hpiskura Date 2002-11-20 Time 10:16 Sent To  
Notes
2002-11-21 00:00:00PROVISO:THE ADJACENT SPACE TO THE EAST
 TO BE DEMISED MUST MEET MINIMUM EGRESS
 REQUIREMENTS.
  
 PROVIDE AN ENGINEER'S SHOP DRAWING AND
 OR SPECIFICATION FOR THE ATTACHMENT OF
 THE EXTERIOR WALL SHEATHING.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2003-04-16 Cont ID  
Sent By btrobaug Date 2003-04-16 Time 10:56 Rev Time 1.00
Received By btrobaug Date 2003-04-16 Time 10:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2003-04-03 Cont ID  
Sent By shernand Date 2003-04-11 Time 14:04 Rev Time 0.25
Received By dpalmer Date 2003-04-03 Time 16:31 Sent To  
Notes
2003-04-03 00:00:00******** UNSAT *******
  
 PLEASE SEE NOTES ON PREVIOUS REVIEW.
 ENTERED AS PROVISO AND SHOULD BE UNSAT.
 PLEASE SEE NOTES AND MAKE NESS CHANGES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-03-24 Cont ID  
Sent By btrobaug Date 2003-03-24 Time 14:49 Rev Time 1.00
Received By btrobaug Date 2003-03-24 Time 14:49 Sent To  
Notes
2003-03-24 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTICE THAT THE TOTAL KVA ON
 PANELS RP4 & HA DID NOT CHANE WITH THE
 ADDED LOADS.PLEASE CORRECT THE LOADS
 AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-01-13 Cont ID  
Sent By btrobaug Date 2003-01-13 Time 08:50 Rev Time 0.25
Received By btrobaug Date   Time   Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-07 Cont ID  
Sent By dpalmer Date 2003-01-07 Time 19:09 Rev Time 1.50
Received By dpalmer Date 2003-01-07 Time 18:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-12-18 Cont ID  
Sent By dpalmer Date 2003-01-07 Time 18:23 Rev Time 2.00
Received By dpalmer Date 2002-12-18 Time 06:50 Sent To  
Notes
2002-12-18 00:00:00****************UNSAT ****************
  
 1)NOTE: PLEASE NOTE, SOME NOTES FROM
 FIRST REVIEW WERE NOT ADDRESSED.
  
 2)NOTE: PLEASE SEE 230-95, PLEASE
 CLARIFY WHERE PLANS/RISER ARE SHOWING
 GFI PROTECTION FOR SERVICE.
  
 3)NOTE: PLEASE SEE 240-3C
 FOR SIZING OF SERVICE ENTRANCE CONDUCTOR
 -S.
  
 4)NOTE: PLEASE SHOW LOAD CALCS, PLANS
 NOW SHOW LOADS ON PANELS X 125%??
 PLEASE CLARIFY WHERE LOAD CALCS ARE
 SHOWN PER 220,,,
 ALSO 220-12.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-19 Cont ID  
Sent By dpalmer Date 2002-11-19 Time 07:05 Rev Time 1.00
Received By dpalmer Date 2002-11-19 Time 07:05 Sent To  
Notes
2002-11-19 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE CLARIFY CIRCUITS TO
 RECEPTS SHOWN W/ #8 CONDUCTORS? PLEASE
 NOTE CONDUIT FILL ,SHOWN W/ 4-#8 IN
 3/4 "CONDUIT.5-#8`S ALSO IN 3/4"
 NEC TABLE 9
  
 2)NOTE: PLEASE NOTE BRANCG CIRCUITS
 FOR EM LT AND EX LTS TO MEET 700-12E
  
 3)NOTE: PLEASE CLARIFY GFI PROTECTION
 FOR SERVICE 230-95.
  
 4)NOTE: PLEASE CLARIFY ATTACHMENT FOR
 TRANSFORMER PER 250-30
  
  
  
  
  
  
  
 6)NOTE: PLEASE SHOW ALL LOAD CALCULATION
 -S PER 215-,220-3,220-10,220-11,220-13
 PLEASE SHOW ALL CONTINUOUS LOADS AT
 125%. 215-3/233-42
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-04-03 Cont ID  
Sent By mcarsill Date 2003-04-03 Time 14:57 Rev Time 0.00
Received By mcarsill Date 2003-04-03 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-01-02 Cont ID  
Sent By btrobaug Date 2003-01-13 Time 08:50 Rev Time 0.00
Received By mcarsill Date 2003-01-02 Time 18:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-11-22 Cont ID  
Sent By mcarsill Date 2002-11-22 Time 11:19 Rev Time 0.00
Received By mcarsill Date 2002-11-22 Time 11:19 Sent To  
Notes
2002-11-22 00:00:001) BUILDING ADDRESS REQUIRED ON PROPER
 BUILDING ELEVATION.
  
 2) NEW FABRIC AWNINGS ARE TO BE FIRE
 RETARDANT.
  
 3) FIRE SPRINKLER PROTECTION IS REQUIRED
 UNDER LOADING DOCK CANOPIES WHERE
 COMBUSTIBLE MATERIALS ARE EXPECTED.
  
 4) EGRESS DOORS SHALL ALLOW FOR FREE
 EGRESS FROM THE INTERIOR SIDE OF THE
 STORE. EXITING SHALL NOT REQUIRE "THE
 USE OF KEY, TOOL, SPECIAL KNOWLEDGE
 OR EFFORT".
  
 5) SECURITY DEVICES OR LOCKS ON EXIT
 DOORS SHALL COMPLY WITH SPECIAL
 LOCKING DEVICES OR ACCESS CONTROLLED
 LOCKS.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM AND FIRE
 SPRINKLER SYSTEM.
  
 7) A MAIN AISLE OF AT LEAST 5 FEET
 WIDE SHALL BE PROVIDED TO EXITS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-05-27 Cont ID  
Sent By shernand Date 2003-05-27 Time 16:27 Rev Time 0.00
Received By shernand Date 2003-05-27 Time 16:27 Sent To B
Notes
2003-05-27 00:00:00HP DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-04-11 Cont ID  
Sent By shernand Date 2003-04-11 Time 14:04 Rev Time 0.00
Received By shernand Date 2003-04-11 Time 14:04 Sent To E
Notes
2003-04-11 00:00:00DPALMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-03-24 Cont ID  
Sent By sthyng Date 2003-03-24 Time 11:14 Rev Time 0.00
Received By sthyng Date 2003-03-24 Time 11:14 Sent To  
Notes
2003-03-24 00:00:00TO COMM BOARD #37

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 18:23 Rev Time 0.00
Received By dpalmer Date 2003-01-06 Time 18:23 Sent To E
Notes
2003-01-07 00:00:00TO DV PALMER`S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-11-15 Cont ID  
Sent By dpalmer Date 2002-11-15 Time 15:34 Rev Time 0.00
Received By dpalmer Date 2002-11-15 Time 15:34 Sent To  
Notes
2002-11-15 00:00:00SUBMITTALS PLACED W/ PLANS ON #14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-05 Cont ID  
Sent By dpalmer Date 2002-11-05 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2002-11-05 Time 15:33 Sent To  
Notes
2002-11-15 00:00:00TO COMM BOARD #14

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-04-08 Cont ID  
Sent By pkrauss Date 2003-04-08 Time 11:22 Rev Time 0.45
Received By pkrauss Date 2003-04-08 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-27 Cont ID  
Sent By pkrauss Date 2002-12-27 Time 14:24 Rev Time 0.35
Received By pkrauss Date 2002-12-27 Time 14:24 Sent To  
Notes
2002-12-27 00:00:00MECHANICAL PERMIT REQUIRED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-27 Cont ID  
Sent By pkrauss Date 2002-11-27 Time 07:09 Rev Time 0.45
Received By pkrauss Date 2002-11-27 Time 07:09 Sent To  
Notes
2002-11-27 00:00:00DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status N Date 2003-04-03 Cont ID  
Sent By kstevens Date 2003-04-03 Time 16:18 Rev Time 0.33
Received By kstevens Date 2003-04-03 Time 16:18 Sent To  
Notes
2003-04-03 00:00:00NO PLUMBING REVISIONS SUBMITTED

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-30 Cont ID  
Sent By kstevens Date 2002-12-30 Time 10:17 Rev Time 0.25
Received By kstevens Date 2002-12-30 Time 10:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-05 Cont ID  
Sent By kstevens Date 2002-12-05 Time 09:01 Rev Time 1.50
Received By kstevens Date 2002-12-05 Time 09:01 Sent To  
Notes
2002-12-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) SHT A1.1 PER TABLE 403.1, TWO DRINK-
 ING FOUNTAINS ARE REQUIRED. HIGH/LOW
 DRINKING FOUNTAINS WITH ONE HOOK-UP ARE
 CONSIDERED ONE UNIT. WATER COOLERS ARE
 PERMITTED PER 410.1 AND SHALL BE
 ARI-1010 COMPLIANT. PLEASE SHOW MANUF.
 INFO IF USING WATER COOLER.
 2) SHT P0.1 INDICATES THAT FUEL GAS IS
 BEING USED FOR ROOFTOP A/C UNIT. FOLLOW-
 ING INFORMATION FOR APPLICATION OF GAS
 PERMIT REQUIRED.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 FBC-2001 FUEL GAS CODE SEC. 401.8 THRU
 402.5.2 & TABLES 402(1) THRU 402(34).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE FBC-
 2001 FUEL GAS CODE SEC 402.2.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377