| Plan Review Stops For Permit 02110243 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-04-08 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-27 |
Time |
16:27 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
2003-04-08 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2003-04-08 00:00:00 | APPROVED PER HAROLD PISKURA 4-1-03 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-11-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-11-21 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-11-20 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2002-11-21 00:00:00 | PROVISO:THE ADJACENT SPACE TO THE EAST | | | TO BE DEMISED MUST MEET MINIMUM EGRESS | | | REQUIREMENTS. | | | | | | PROVIDE AN ENGINEER'S SHOP DRAWING AND | | | OR SPECIFICATION FOR THE ATTACHMENT OF | | | THE EXTERIOR WALL SHEATHING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2003-04-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-04-16 |
Time |
10:56 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-04-16 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
14:04 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-04-03 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2003-04-03 00:00:00 | ******** UNSAT ******* | | | | | | PLEASE SEE NOTES ON PREVIOUS REVIEW. | | | ENTERED AS PROVISO AND SHOULD BE UNSAT. | | | PLEASE SEE NOTES AND MAKE NESS CHANGES. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-03-24 |
Time |
14:49 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-03-24 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2003-03-24 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTICE THAT THE TOTAL KVA ON | | | PANELS RP4 & HA DID NOT CHANE WITH THE | | | ADDED LOADS.PLEASE CORRECT THE LOADS | | | AND RESUBMIT FOR REVIEW PRIOR TO ROUGH | | | INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-01-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-13 |
Time |
08:50 |
Rev Time |
0.25 |
| Received By |
btrobaug |
Date |
|
Time |
|
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-01-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-07 |
Time |
19:09 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2003-01-07 |
Time |
18:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-07 |
Time |
18:23 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2002-12-18 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2002-12-18 00:00:00 | ****************UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE, SOME NOTES FROM | | | FIRST REVIEW WERE NOT ADDRESSED. | | | | | | 2)NOTE: PLEASE SEE 230-95, PLEASE | | | CLARIFY WHERE PLANS/RISER ARE SHOWING | | | GFI PROTECTION FOR SERVICE. | | | | | | 3)NOTE: PLEASE SEE 240-3C | | | FOR SIZING OF SERVICE ENTRANCE CONDUCTOR | | | -S. | | | | | | 4)NOTE: PLEASE SHOW LOAD CALCS, PLANS | | | NOW SHOW LOADS ON PANELS X 125%?? | | | PLEASE CLARIFY WHERE LOAD CALCS ARE | | | SHOWN PER 220,,, | | | ALSO 220-12. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-11-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-19 |
Time |
07:05 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2002-11-19 |
Time |
07:05 |
Sent To |
|
|
| Notes |
| 2002-11-19 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE CLARIFY CIRCUITS TO | | | RECEPTS SHOWN W/ #8 CONDUCTORS? PLEASE | | | NOTE CONDUIT FILL ,SHOWN W/ 4-#8 IN | | | 3/4 "CONDUIT.5-#8`S ALSO IN 3/4" | | | NEC TABLE 9 | | | | | | 2)NOTE: PLEASE NOTE BRANCG CIRCUITS | | | FOR EM LT AND EX LTS TO MEET 700-12E | | | | | | 3)NOTE: PLEASE CLARIFY GFI PROTECTION | | | FOR SERVICE 230-95. | | | | | | 4)NOTE: PLEASE CLARIFY ATTACHMENT FOR | | | TRANSFORMER PER 250-30 | | | | | | | | | | | | | | | | | | | | | | | | 6)NOTE: PLEASE SHOW ALL LOAD CALCULATION | | | -S PER 215-,220-3,220-10,220-11,220-13 | | | PLEASE SHOW ALL CONTINUOUS LOADS AT | | | 125%. 215-3/233-42 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-04-03 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-04-03 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-01-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-13 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-01-02 |
Time |
18:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-11-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-11-22 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-11-22 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2002-11-22 00:00:00 | 1) BUILDING ADDRESS REQUIRED ON PROPER | | | BUILDING ELEVATION. | | | | | | 2) NEW FABRIC AWNINGS ARE TO BE FIRE | | | RETARDANT. | | | | | | 3) FIRE SPRINKLER PROTECTION IS REQUIRED | | | UNDER LOADING DOCK CANOPIES WHERE | | | COMBUSTIBLE MATERIALS ARE EXPECTED. | | | | | | 4) EGRESS DOORS SHALL ALLOW FOR FREE | | | EGRESS FROM THE INTERIOR SIDE OF THE | | | STORE. EXITING SHALL NOT REQUIRE "THE | | | USE OF KEY, TOOL, SPECIAL KNOWLEDGE | | | OR EFFORT". | | | | | | 5) SECURITY DEVICES OR LOCKS ON EXIT | | | DOORS SHALL COMPLY WITH SPECIAL | | | LOCKING DEVICES OR ACCESS CONTROLLED | | | LOCKS. | | | | | | 6) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE ALARM SYSTEM AND FIRE | | | SPRINKLER SYSTEM. | | | | | | 7) A MAIN AISLE OF AT LEAST 5 FEET | | | WIDE SHALL BE PROVIDED TO EXITS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2003-05-27 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-27 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-27 |
Time |
16:27 |
Sent To |
B |
|
| Notes |
| 2003-05-27 00:00:00 | HP DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-04-11 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-04-11 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-04-11 |
Time |
14:04 |
Sent To |
E |
|
| Notes |
| 2003-04-11 00:00:00 | DPALMER DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-03-24 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-24 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-24 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2003-03-24 00:00:00 | TO COMM BOARD #37 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-01-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-01-06 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-01-06 |
Time |
18:23 |
Sent To |
E |
|
| Notes |
| 2003-01-07 00:00:00 | TO DV PALMER`S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2002-11-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-15 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-11-15 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2002-11-15 00:00:00 | SUBMITTALS PLACED W/ PLANS ON #14 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-11-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-11-05 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-11-05 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2002-11-15 00:00:00 | TO COMM BOARD #14 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2003-04-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-04-08 |
Time |
11:22 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-04-08 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-12-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-12-27 |
Time |
14:24 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-12-27 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2002-12-27 00:00:00 | MECHANICAL PERMIT REQUIRED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-11-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-27 |
Time |
07:09 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-11-27 |
Time |
07:09 |
Sent To |
|
|
| Notes |
| 2002-11-27 00:00:00 | DENIED: | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS | | | AS PER 2001 FBC(M) TABLE 403.3 OR | | | ASHRAE 62-89. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2003-04-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-04-03 |
Time |
16:18 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-04-03 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2003-04-03 00:00:00 | NO PLUMBING REVISIONS SUBMITTED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-12-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-30 |
Time |
10:17 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-12-30 |
Time |
10:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-12-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-12-05 |
Time |
09:01 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2002-12-05 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2002-12-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A1.1 PER TABLE 403.1, TWO DRINK- | | | ING FOUNTAINS ARE REQUIRED. HIGH/LOW | | | DRINKING FOUNTAINS WITH ONE HOOK-UP ARE | | | CONSIDERED ONE UNIT. WATER COOLERS ARE | | | PERMITTED PER 410.1 AND SHALL BE | | | ARI-1010 COMPLIANT. PLEASE SHOW MANUF. | | | INFO IF USING WATER COOLER. | | | 2) SHT P0.1 INDICATES THAT FUEL GAS IS | | | BEING USED FOR ROOFTOP A/C UNIT. FOLLOW- | | | ING INFORMATION FOR APPLICATION OF GAS | | | PERMIT REQUIRED. | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | GAS CODE. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 3. TYPE OF GAS, (LP OR NATURAL) | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | FBC-2001 FUEL GAS CODE SEC. 401.8 THRU | | | 402.5.2 & TABLES 402(1) THRU 402(34). | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE FBC- | | | 2001 FUEL GAS CODE SEC 402.2. | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|