Plan Review Details - Permit 02110220
Plan Review Stops For Permit 02110220
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-06-20 Cont ID  
Sent By shill Date 2006-06-20 Time 18:08 Rev Time 0.00
Received By shill Date 2006-06-20 Time 18:08 Sent To  
Notes
2006-06-20 00:00:00REVISED A2, A3, A5 DATED 6/14/06

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-06-07 Cont ID  
Sent By shill Date 2006-06-07 Time 16:13 Rev Time 0.00
Received By shill Date 2006-06-07 Time 16:13 Sent To  
Notes
2006-06-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE PERMIT WAS ISSUED WITH A
 PROVISO TO REVISE A3 (MANEUVERING
 CLEARANCE FOR THE DOOR AT OFFICE #4 TO
 COMPLY WITH FBC11 FIGURE 25).THE PLAN
 AS DRAWN IS NOT CODE COMPLIANT.WAS
 THIS CLOSET/DOOR AREA BUILT AS DRAWN?
 PLEASE ADVISE AS TO FIELD CONDITIONS AND
 REVISE PLAN AS REQUIRED ON 7/20/2004.
  
 PROVISOS ARE ISSUED AS A COURTESY TO
 AVOID DELAYS IN PERMITTING (THE OTHER
 OPTION IS TO FAIL THE PLAN, HAVE THE
 DESIGNER CHANGE THE PLAN, AND RESUBMIT).
 THIS PROVISO IS WRITTEN UNDER THE BLOCK
 STAMP ON THE COVER SHEET, REDLINED ON
 A3, WAS DISCUSSED WITH THE CONTRACTOR,
 AND WAS ENTERED IN THE PLAN REVIEW
 NOTES.IN THE FUTURE, PLEASE ADDRESS
 PROVISOS IN A TIMELY MANNER TO AVOID
 DELAYS IN THE FIELD.
  
 2.)THE PLANS APPEAR CODE COMPLIANT.
 HOWEVER, REVISE THE AFFECTED SHEETS.
 SKETCHES ARE TYPICALLY USED TO PROVIDE
 CLARIFICATION OR ADDITIONAL DETAILS NOT
 INCLUDED ON THE PLANS.YOU ARE CHANGING
 THE DETAILS ON THE PLAN.TO AVOID
 CONFUSION, AND FOR OUR RECORD KEEPING
 PURPOSES, PLEASE CHANGE THE AFFECTED
 SHEETS.
  
 WHEN SUBMITTING THE REVISION, YOU WILL
 BE CHARGED A REVISION FEE OF $60 FOR
 SHEET A3.AS THESE DETAILS HAVE ALREADY
 BEEN REVIEWED, NO FEE WILL BE CHARGED
 FOR INCORPORATING THE DETAILS INTO THE
 SHEETS (UNLESS OTHER CHANGES ARE MADE).
 PLEASE ADVISE THE FRONT COUNTER STAFF
 (BY SHOWING THIS CORRECTION LIST) OR
 CONTACT ME. PROVIDE THE 8 1/2X11
 SKETCHES FOR REFERENCE WHEN
 RESUBMITTING.
  
 3.) THE ARCHITECT'S SKETCHES LACK THE
 PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT, FAC61G1-16.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-09-21 Cont ID  
Sent By shill Date 2004-09-21 Time 08:35 Rev Time 1.50
Received By shill Date 2004-09-21 Time 08:35 Sent To  
Notes
2004-09-21 00:00:00****CORRECTIONS****
 FAX DATED 8/30/2004 PREPARED BY SLA
 ARCHITECTS AND PLANNERS INC.
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 THIS LETTER SERVES AS A CURSORY REVIEW
 OF THE SKETCH AND LETTER SUBMITTED
 REGARDING THE USE OF A PLATFORM LIFT
 RATHER THAN AN ELEVATOR.ONLY FBC2001
 COMPLIANCE WAS TAKEN INTO CONSIDERATION;
 FOR A MORE COMPLETE REVIEW INCLUDING
 OTHER TRADES, INCLUDING FIRE, PLEASE
 SUBMIT AS A REVISION.
  
 VERTICAL ACCESSIBILITY IS REQUIRED FBC
 11-4.1.3.THE EXCEPTIONS IN 11-4.1.3(5)
 DO NOT APPEAR TO APPLY TO THIS JOB.
 RELIEF FROM THIS REQUIREMENT MAY BE
 REQUESTED FROM THE BUILDING OFFICIAL
 IN WRITING; PLEASE ADDRESS TO NEIL K.
 MELICK.
  
 FIRE RESISTANCE OF THE PROPOSED LIFT
 WOULD BE DETERMINED BY FBC704.2.1.2 AND
 FBC TABLE 705.1.2.YOUR APPROVED PLAN
 INDICATES A 1 HR FLOOR/CEILING ASSEMBLY
 RATING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-07-20 Cont ID  
Sent By shill Date 2004-07-20 Time 08:05 Rev Time 0.50
Received By shill Date 2004-07-20 Time 08:05 Sent To  
Notes
2004-07-20 00:00:00***PROVISO***
 REVISE SHEET A3 AS NOTED ON PLAN -
 DOOR FOR OFFICE #4 IS TO COMPLY WITH
 FBC11 FIGURE 25
 SUBMITTED ON 8 1/2 X 11 - OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-07-15 Time 09:14 Rev Time 2.50
Received By shill Date 2004-06-22 Time 17:03 Sent To  
Notes
2004-06-23 00:00:00***PROVISO***
 ***IMPACT FEES MUST BE PAID BEFORE
 PERMITTING****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE IMPACT FEE STAMP DOES NOT
 REFLECT THE ADDITIONAL SQUARE FOOTAGE.
 PLEASE SEE WILLIE SWOPE, PALM BEACH
 COUNTY IMPACT FEES, 233-5025.THIS
 APPEARS TO INVOLVE A CHANGE OF USE
 (WAREHOUSE TO BUSINESS) AS WELL AS AN
 INCREASE IN SQUARE FOOTAGE (NEW 2ND
 FLOOR AREA).THE IMPACT FEE STAMP
 SHOULD REFLECT THIS EVEN IF NO FEES ARE
 DUE.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 3.)REVISE SHEET A3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-04-07 Cont ID  
Sent By hpiskura Date 2004-04-07 Time 06:45 Rev Time 0.00
Received By hpiskura Date 2004-04-07 Time 06:45 Sent To FIRE
Notes
2004-04-07 00:00:00PLAN REVIEW NOT A PERMIT APPLICATION.
 THIRD PLAN REVIEW. PLANS BY SLA
 ARCHITECTS DATED 1/29/04.
  
 DETAILS 2/A1 AND 3/A1 DEPICT BEVELED
 WINDOW BUCKS.SEE FBC 1707.4.4.2
 REGARDING FULL SUPPORT.
  
 SHEET A2.PROVIDE A DETAIL FOR THE
 WINDOWS TO BE CUT IN TO HAVE HEADERS OR
 LINTELS.SEE FBC 104.2 AS AMENDED
  
 SHEET A3, THE 42" HIGH STAIR GUARD RAIL.
 THE BOTTOM RAIL MUST BE 2" OR LESS ABOVE
 THE FLOOR.SEE FBC 1015.3.
  
 SHEET A3 SHOWS A 45 MIN RATED DOOR ON
 THE FIRST FLOOR FOR THE STAIR SHAFT.A
 ONE HOUR RATING IS REQUIRED AND THE
 SHAFT WALL CONTINUOUS.SEE FBC
 704.2.1.2 AND FBC TABLE 705.1.2.
  
 THE A/C PLAN STILL SHOWS A DUCT
 PENETRATING THE EXIT STAIR ENCLOSURE.
 SEE FBC 1006.1.3.1 AND NFPA 101
 7.1.3.2.1 (E).THE REFERENCE TO DUCTS
 IS FOR STAIR PRESSURIZATION NOT AIR
 CONDITIONING.
  
 THE A/C SHEET IS NOT SEALED BY THE
 ARCHITECT.
  
 SHEET A3 CONTAINS A NOTE REFERENCING
 ACCESSIBILITY.THE 11.1.6 (I) (F)
 SECTION CITED IS NOT FOUND IN THE FBC.
 PLEASE SEE FBC 11-4.1.3 (5) AND FBC
 11-4.1.6 (1), VERTICAL ACCESIBILITY IS
 REQUIRED.
  
 THE TRACO WINDOW NOA HAS ILLEGIBLE
 DRAWINGS.
  
 THE PLANS DO NOT SHOW THE PRESSURES FOR
 THE WINDOW DESIGN.SEE FBC 1606.1.7 #5.
  
 SEE PREVIOUS NOTES REGARDING IMPACT
 FEES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-22 Cont ID  
Sent By hpiskura Date 2003-10-22 Time 17:05 Rev Time 0.00
Received By hpiskura Date 2003-10-22 Time 14:38 Sent To  
Notes
2003-10-22 00:00:00PLAN REVIEW ONLY NOT A PERMIT
 APPLICATION.PLANS PREPARED BY SLA
 ARCHITECTS DATED 7/16/03.
  
 THE NEW WINDOWS MUST COMPLY WITH THE
 FBC1606.1.4 FOR HURRICANE MISSILE
 IMPACT PROTECTION.AT TIME OF PERMIT
 APPLICATIONPROVIDE NOTICE OF ACCEPTANCE
 AND/OR TEST REPORTS.
  
 INCLUDE FLORIDA ENERGY CODE CALCULATIONS
 WITH THE PERMIT APPLICATION.SEE FBC
 13-101.1.
  
 THE MIXED OCCUPANCY RATING BETWEEN THE
 OFFICE AND WAREHOUSE AREA IS REQUIRED
 TO BE A MINIMUM OF 2 HOURS NOT THE 1
 HOUR SHOWN.SEE FBC 704.1 FOR S2 AND B
 OCCUPANCIES.THE U906 MASONRY DESIGN
 USES ONLY UL LISTED MANUFACTURED BLOCKS
 THAT ARE NOT COMMON IN THIS AREA.THE
 DESIGN IS ACCEPTABLE BUT THE BLOCK
 VENDORS MUST PROVIDE THEIR LISTING.
  
 SHOW THE METHOD(S) FOR PROTECTION OF THE
 PENETRATIONS OF THE FIRE RATED
 ASSEMBLIES.SEE FBC 705.
  
 THE A/C DUCT PENETRATING THE STAIR SHAFT
 IS NOT ALLOWED BY FBC 1006.1.3.1.
  
 THE NEW STAIRS AS SHOWN ON SHEET A3 DO
 NOT DISCHARGE DIRECTLY TO THE OUTSIDE.
 SEE FBC 1006.1.3 AS REGARDS THE HC LIFT
 AND DOOR RATING.
  
 SHOW EXISTING OR PROVIDE HANDICAP
 ACCESS FROM THE BUILDING EXTERIOR.
  
 SECTION D/A5 SHOWS A RISER HEIGHT
 GREATER THAN THE 7" PERMITTED BY FBC
 1007.3.1.REVIEW THE HEIGHT DIMENSIONS
 SHOWN.ALSO, SEE FBC 1007.3.3 FOR
 TOLERANCES.1/64" IS NOT A COMMON
 FIELD DIMENSION.
  
 THE FLOOR CEILING DESIGN UL G 236 DOES
 NOT PROVIDE FOR PENETRATIONS OR
 INTERSTIAL MECHANICAL EQUIPMENT.
 PLEASE REVISE AS NECESSARY AT PERMIT
 TIME.
  
 THE CHANGE IN USE AND ADDITIONAL FLOOR
 AREA TO BE ADDED IS SUBJECT TO IMPACT
 FEES BY THE COUNTY.BEFORE A PERMIT TO
 CONSTRUCT MAY BE ISSUED THE PERMIT
 PLANS MUST BE STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. CALL
 561-233-5025 FOR MORE INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By hpiskura Date 2002-12-02 Time 11:17 Rev Time 0.00
Received By hpiskura Date 2002-12-02 Time 09:13 Sent To  
Notes
2002-12-02 00:00:00THE MINIMUM CONSTRUCTION TYPE FOR THIS
 BULDING IS TYPE V 1 HOUR PROTECTED OR
 TYPE V FIRE SPRINKLERED.PLEASE NOTE
 THE PARTICULAR EXISTING CONDITION AT
 TIME OF PERMIT APPLICATION OR METHOD OF
 COMPLIANCE TO BE ESTABLISHED.
  
 THE PERMIT PLANS MUST HAVE THE MINIMUM
 DESIGN INFORMATION CONTAINED IN FBC
 104. 3.1.1 AND FBC 1606.1.7.
  
 SHEET A1 DOES NOT SHOW THE SPACING OF
 THE 4X4 STEEL COLUMNS.
  
 SECTIONS TAKEN AS B AND C ON SHEET A1
 ARE NOT INCLUDED WITH THE PLANS.
  
 SHOW A DETAIL FOR THE INSTALLATION OF
 THE NEW PAD FOOTINGS IN RELATION TO THE
 EXISTING WALL FOOTINGS, PARTICLARLY THE
 ONES THAT WILL BE ECCENTRICALLY LOADED.
 INCLUDE THE HEIGHT OF THE TOP OF THE
 PADS RELATIVE TO THE FINISH FLOOR.
  
 SHEET A2, SHOW A DETAIL FOR THE
 TRANSITION OF THE W12X27 BEAM TO THE
 8X8X1 ANGLE. ALSO, THE STEEL COLUMN
 DETAIL DOES NOT PROVIDE FOR ATTACHMENT
 TO THE W12X27 BEAM.
  
 SHEET A3.SHOW HOW HANDICAP VERTICAL
 ACCESSIBILITY WILL BE ACCOMPLISHED.
 SEE FBC 11-4.1.6 (1) (F)
  
 SHOW A CONSTRUCTION DETAIL FOR THE
 INTERIOR STAIRS.
  
 SHOW ALL OF THE STRUCTURAL DESIGN LOADS
 ASSUMED, IE FLOOR, STAIRS, HAND AND
 GUARD RAILS.
  
 PROVIDE A BEARING CONNECTION DETAIL FOR
 THE BAR JOISTS.
  
 SECTION D/3.SHOW THE REINFORCING
 DETAIL FOR THE CANTILEVERED LANDING.
  
 SHOW HOW THE EXTERIOR GLAZING WILL
 RESIST HURRICANE MISSILE IMPACT.SEE
 FBC 1606.1.4
  
 THE INTERIOR STAIRS ARE REQUIRED BY FBC
 1006.1.1 TO BE ENCLOSED WITH FIRE RATED
 CONSTRUCTION AND TO PROVIDE A PROTECTED
 PATH OF EGRESS TO THE EXTERIOR OF THE
 BUILDING AS PROVIDED FOR IN FBC 1010.
  
 THE EXTERIOR STAIRS MUST MEET ALL OF THE
 REQUIREMENTS OF FBC 1006.2.
  
 SHOW THE FLOOR TO CEILING HEIGHTS OF THE
 FIRST AND SECOND FLOORS.
  
 WHAT IS THE NATURE AND QUANTITY OF THE
 COMMODITIES TO BE STORED IN THIS SPACE?
  
 THE ADDITIONAL BUILDING AREA TO BE
 ADDED IS SUBJECT TO IMPACT FEES
 COLLECTED BY THE COUNTY.BEFORE A
 PERMIT TO CONSTRUCT MAY BE ISSUED
 IMPACT FEES MUST BE PAID TO THE COUNTY,
 THE PERMIT PLANS STAMPED BY THAT OFFICE
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.
  
 ALL PLANS SUBMITTED FOR PUBLIC RECORD,
 INCLUDING THE SURVEY/SITE PLAN, MUST BE
 SIGNED AND SEALED BY THE DESIGNER OF
 RECORD.SEE FBC 104.2.2.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 19:36 Rev Time 0.33
Received By dpalmer Date 2004-06-17 Time 19:30 Sent To  
Notes
2004-06-17 00:00:00NEW ELECTRICAL SHEETS.
  
 ** REDLINED **
 INSPECTOR TO VERIFRY EXSITING GROUNDING
 ELECTRODE SYSTEM. 250.50

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-03-23 Cont ID  
Sent By btrobaug Date 2004-03-23 Time 15:20 Rev Time 0.75
Received By btrobaug Date 2004-03-23 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2003-10-14 Time 18:01 Rev Time 0.50
Received By dpalmer Date 2003-10-14 Time 18:01 Sent To  
Notes
2003-10-14 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. 215.5
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/ EXT LTS.
  
 2)NOTE: PLEASE SEE THAT WE ARE NOW
 UNDER THE 2002 NEC. 7/1/03
  
 3)NOTE: PLEASE SEE THAT LOAD ON SERVICE
 EXCEEDS RATING OF EXISTING 200A SERVICE.
 PLEASE INCREASE SERVICE SIZE AND
 CONDUCTOR SIZES. 310.16/240.6 ETC.
  
 4)NOTE: PLEASE ADJUST GROUNDING ELEC-
 -TRODE CONDUCTOR PER 250.66
  
 5)NOTE: PLEASE SEE THAT MAX OCP FOR
 3500W OF WATER HEATER IS 150% OF LOAD.
 MIN OCP IS 125%. PLEASE ADJUST THE 2P30A
 SHOWN.
  
 6)NOTE: PLEASE SEE PLANS, PLANS SHOW
 TWO PANELS? RISER SHOWS ONLY ONE.?
 PLEASE CLARIFY?
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWERS THAT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEWING AND STAMPING.
 ONE SET OF OLD SHEETS MAYBE SUBMITTED
 FOR VERIFICATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-14 Cont ID  
Sent By dpalmer Date 2002-11-14 Time 13:03 Rev Time 0.25
Received By dpalmer Date 2002-11-14 Time 13:03 Sent To  
Notes
2002-11-14 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE NOTE, NO ELECTRICAL WAS
 SUBMITTED FOR REVIEW. EXITS LTS/ EGRESS
 LTS AND EMERGENCY LTS TO MEET THE MIN.
  
 PLEASE SUIBMIT THE ABOVE INFORMATION AND
 COMPLETE SCOPE OF ELECTRICAL WORK.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-06-18 Cont ID  
Sent By mcarsill Date 2004-06-18 Time 13:10 Rev Time 0.00
Received By mcarsill Date 2004-06-18 Time 13:10 Sent To  
Notes
2004-06-18 00:00:001) NO ITEMS ALLOWED WITHIN STAIRWELL
 EXCEPT CODE ALLOWED ONES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2004-04-08 Cont ID  
Sent By hpiskura Date 2004-04-07 Time 18:34 Rev Time 0.00
Received By mcarsill Date 2004-04-08 Time 14:04 Sent To  
Notes
2004-04-08 00:00:001) NO MECHANICAL EQUIPMENT IS ALLOWED
 IN A STAIRWAY UNLESS IT IS FOR STAIRWAY
 PRESSURIZATION EQUIPMENT NEEDED FOR THE
 STAIR.
  
 2) THE STAIR HAS A 60 MINUTE DOOR AND
 A 45 MINUTE DOOR LOCATED AT DIFFERENT
 ELEVATIONS.
  
 3) PLEASE SEE BUILDING PLAN
 REVIEWER NOTES ON RECENT EXAM ON PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-17 Cont ID  
Sent By mcarsill Date 2003-10-17 Time 16:25 Rev Time 0.00
Received By mcarsill Date 2003-10-17 Time 16:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-11-15 Cont ID  
Sent By mcarsill Date 2002-11-15 Time 15:06 Rev Time 0.00
Received By mcarsill Date 2002-11-15 Time 15:06 Sent To  
Notes
2002-11-15 00:00:001) THE BOUNDARY SURVEY IS DIFFICULT TO
 READ.
  
 2) PLANS FAILED TO DISPLAY ANY
 EMERGENCY LIGHTS OR EXIT SIGNS.
  
 3) PLEASE PROVIDE PRESCRIPTIVE CODE
 REQUIREMENTS FOR NEW HANDRAILS.
  
 4) PLEASE INDICATE INTERIOR FINISH
 INFORMATION FOR WALLS AND CEILINGS.
  
 5) PLEASE INDICATE ANY OTHER FIRE
 SAFETY EQUIPMENT OR DEVICES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 14:59 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 14:59 Sent To B
Notes
2006-06-19 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 15:13 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 15:13 Sent To B
Notes
2006-05-30 00:00:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-15 Cont ID  
Sent By csiegber Date 2004-07-15 Time 09:14 Rev Time 0.00
Received By csiegber Date 2004-07-15 Time 09:14 Sent To B
Notes
2004-07-15 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-16 Time 15:12 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 15:12 Sent To  
Notes
2004-06-16 00:00:00TO COMM BD#3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-08 Time 16:10 Rev Time 0.00
Received By csiegber Date 2004-03-08 Time 16:10 Sent To  
Notes
2004-03-08 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-10 Cont ID  
Sent By csiegber Date 2003-10-10 Time 11:21 Rev Time 0.00
Received By csiegber Date 2003-10-10 Time 11:21 Sent To  
Notes
2003-10-10 00:00:00TO COMM BD#30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-05 Cont ID  
Sent By btrobaug Date 2002-11-05 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2002-11-05 Time 14:39 Sent To  
Notes
2002-11-05 00:00:00TO COMM BOARD # 20./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-06-24 Cont ID  
Sent By pkrauss Date 2004-06-24 Time 07:17 Rev Time 0.40
Received By pkrauss Date 2004-06-24 Time 07:17 Sent To  
Notes
2004-06-24 00:00:00PROVISO:
 PLEASE NOTE HVAC PLANS SUBMITTED ARE RED
 LINED BY THE A/C CONTRACTOR.FUTURE
 SUBMITTALS OR REVISIONS, PLEASE REFLECT
 THE DELETION OF DUCT PENETRATION THROUGH
 THE STAIRWELL.
  
 PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPERS ON
 THE JOBSITE AT TIME OF INSPECTION.
  
 PLAN INDICATES AHU 1 & 2 - MAXIMUM CFM
 WILL BE 1,800.PROVIDE DOCUMENTATION OF
 MANUFACTURERS ENGINEERING DATA VERIFYING
 THE UNITS CAN NOT EXCEED 2,000 CFM,
 OTHERWISE DUCT SMOKE DETECTORS WILL BE
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-03-25 Cont ID  
Sent By pkrauss Date 2004-03-25 Time 08:38 Rev Time 0.55
Received By pkrauss Date 2004-03-25 Time 08:38 Sent To  
Notes
2004-03-25 00:00:00DENIED:
 1.PLANS INDICATE 6" DUCT PENETRATING
 THROUGH THE STAIRWELL.PER FBC
 1006.1.3.1, DUCTWORK SHALL NOT
 PENETRATE OR RUN THROUGH A STAIRWAY
 ENCLOSURE UNLESS IT IS A PART OF THE
 STAIRWAY PRESSURIZATION SYSTEM.
  
 2.PLEASE NOTE THE LOCATION OF THE
 FRESH AIR INTAKE TO THE FIRST FLOOR
 AHU. FRESH AIR INTAKES SHALL BE LOCATED
 AS NOT TO RECIRCULATE HOT AIR EMITTED
 OF THE CONDENSING UNITS.
  
 3.PROVIDE SUBMITTAL DATA OR LETTER
 FROM TRANE INDICATING THAT UNDER NO
 CIRCUMSTANCE CAN THE A/C SYSTEM EXCEED
 2,000 CFM, OTHERWISE DUCT SMOKE
 DETECTORS WILL BE REQUIRED.2001
 FBC(M) 606.2.1, DUCT SMOKE DETECTORS
 SHALL BE INSTALLED IN SYSTEMS WITH THE
 "DESIGN CAPACITY" GREATER THAN 2,000
 CFM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-23 Cont ID  
Sent By pkrauss Date 2003-10-23 Time 11:58 Rev Time 0.45
Received By pkrauss Date 2003-10-23 Time 11:43 Sent To  
Notes
2003-10-23 00:00:00PROVISO:
 DUCT SMOKE DETECTORS REQUIRED FOR UNITS
 THAT HAVE A DESIGN CAPACITY GREATER THAN
 2,000 CFM. DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN THE SUPPLY AIR DUCT AS PER
 2001 FBC(M) 606.2.1. FAN SHUTDOWN BY
 DUCT SMOKE DETECTORS SHALL HAVE
 NOTIFICATION TO ALARM/STROBE AS PER
 NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-10 Cont ID  
Sent By pkrauss Date 2002-12-10 Time 16:22 Rev Time 0.40
Received By pkrauss Date 2002-12-10 Time 16:15 Sent To  
Notes
2002-12-10 00:00:00DENIED:
  
 1.PROVIDE OUTSIDE AIR CALCS AS PER
 2001 FBC(M) TABLE 403.3.
  
 2.INDICATE WHAT IS BEING STORED IN
 THE LOFTS ABOVE THE OFFICE SPACE.
  
 3.PROVIDE INFORMATION ON THE
 VENTILATION IN THE LOFT STORAGE
 AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-07-03 Cont ID  
Sent By kstevens Date 2004-07-03 Time 09:49 Rev Time 0.33
Received By kstevens Date 2004-07-03 Time 09:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-03-22 Cont ID  
Sent By kstevens Date 2004-03-22 Time 09:07 Rev Time 0.50
Received By kstevens Date 2004-03-22 Time 09:07 Sent To  
Notes
2004-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) FROM PREVIOUS REVIEW: A WATER RISER
 DIAGRAM IS REQUIRED PER SEC 104.3.1.1.
 AIR CHAMBERS ARE NOT APPROVED - IF USING
 WATER HAMMER ARRESTORS, THEY SHALL BE
 LOCATED NEAR THE FIXTURES, IN AN "EFFECT
 IVE RANGE" NOT IN THE CEILING PER PDI-WH
 201 AND MANUF. INSTALL. INSTRUCTIONS.
 SECTION 604.9
 2) CERTIFICATE OF AUTHORIZATION REQUIRED
 ON TITLE BLOCK. FS 481.219
 3) FAC 61G1-16.004 PRINTED NAME OF PER-
 SON SEALING PLANS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-23 Cont ID  
Sent By kstevens Date 2003-10-23 Time 14:30 Rev Time 0.33
Received By kstevens Date 2003-10-23 Time 14:30 Sent To  
Notes
2003-10-23 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) 104.3.1.1 A WATER RISER DIAGRAM IS
 REQUIRED. - AIR CHAMBERS ARE NOT APPROV-
 ED - IF USING WATER HAMMER ARRESTORS,
 THEY SHALL BE LOCATED NEAR THE FIXTURES,
 IN AN "EFFECTIVE RANGE" NOT IN THE CEIL-
 ING PER PDI-WH 201 AND MANUF. INSTALL.
 INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By kstevens Date 2002-12-02 Time 14:47 Rev Time 1.00
Received By kstevens Date 2002-12-02 Time 14:47 Sent To  
Notes
2002-12-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 HDCP TOILET ROOMS, PLEASE
 SHOW DETAIL FOR TOILET ROOMS PER SEC.
 11-4.22. 11-4.2.2 DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. 11-4.22.3 SHOW CLEAR FLOOR
 SPACE FOR FIXTURES. 11-4.22.4 WATER CLO-
 SETS SHALL COMPLY WITH 11-4.16 (18" OFF
 WALL TO CENTER OF FIXTURE - GRAB BARS -
 FLUSH CONTROLS - HEIGHT ECT.) 11-4.22.6
 LAVS SHALL COMPLY WITH 11-4.19.
 2) SHT A-2 DRINKING FOUNTAIN, SHOW DE-
 TAIL PER SECTION 11-4.25. 11-4.15.2
 HEIGHT, AND SECTION 11-4.1.3(10)(A) SHOW
 PROVISIONS FOR THOSE WHO HAVE TROUBLE
 BENDING OR STOOPING. (EITHER A HIGH/LOW
 D.F. OR SUPPLY DRINKING CUP DISPENSOR AT
 D.F.
 3) SHT A-3 IF VERTICAL ACCESSIBLITY IS
 REQUIRED THAN ALL TOILET ROOMS SHALL BE
 REQUIRED TO BE ACCESSIBLE.
 4) PLEASE INDICATE TYPE OF MATERIALS TO
 BE WAREHOUSED AT SPACE. ANSWER MAY RE-
 QUIRE ADDITIONAL REVIEW COMMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377