Plan Review Details - Permit 02110117
Plan Review Stops For Permit 02110117
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-01-15 Cont ID  
Sent By lmartine Date 2003-01-15 Time 18:36 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-06 Cont ID  
Sent By btrobaug Date 2003-01-13 Time 07:42 Rev Time 0.00
Received By hpiskura Date 2002-12-05 Time 14:23 Sent To Z
Notes
2002-12-06 00:00:00SHEET A4 SHOWS DETAIL 1/A6 TAKEN IN
 FOURSEPARATE PLACES OF DIFFERING
 CONDITIONS AND IS NOT DETAILED ON THE
 PLAN.PLEASE CLARIFY AS NECESSARY.THE
 INFORMATION FOR THE TRANSITION OF THE
 NEW CONCRETE BEAM TO THE OLD, THE
 GIRDER CONNECTIONS TO THE CMU, AND
 OTHER DETAILS ARE IMPORTANT.
  
 SECTION 1/A8 SHOWS A CONTINUOUS 2"
 SCREENED SOFFIT VENT.PROVIDE AN
 ANALYSIS, INCLUDING THE FREE AREA OF
 THE VENT THAT DEMONSTRATES COMPLIANCE
 WITH FBC 2309.7, ALSO SHOW THE ATTIC
 ACCESS IN ACCORDANCE WITH FBC 2309.6.
  
 SECTION 2/A8 AND ELSEWHERE, SHOW THE
 SPEICIFICATION FOR THE GUARD RAIL AND
 HAND RAILS.SEE FBC 1007.5 AND FBC
 1015.
  
 PLEASE MARK THE COMPONENTS TO BE USED
 FOR THE HURRICANE SHUTTERS IN SBCCI
 REPORT
 2211.
  
 IF TEST AND OR NOTICE OF ACCEPTANCE
 REPORTS FOR THE WINDOWS, DOORS AND ROOF
 COVERING ARE NOT INCLUDED WITH THIS
 PERMIT APPLICATION, SEPARATE PERMITS
 AND FEES WILL BE REQUIRED.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-253-5025 FOR
 MORE INFORMATION.
  
 A COPY OF A RECORDED NOTICE OF
 COMMENCEMENT MUST BE PROVIDED TO THE
 CITY PRIOR TO THE PERMIT BEING ISSUED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-06-14 Cont ID  
Sent By btrobaug Date 2004-06-14 Time 15:43 Rev Time 0.50
Received By btrobaug Date 2004-06-14 Time 15:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-01-13 Cont ID  
Sent By csiegber Date 2004-06-11 Time 12:48 Rev Time 0.53
Received By btrobaug Date 2003-01-13 Time 06:35 Sent To B
Notes
2003-01-13 00:00:00TO LUIS M./WRT

Review Stop E ELECTRICAL
Rev No 2 Status I Date 2002-12-16 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 13:41 Rev Time 0.50
Received By btrobaug Date 2002-12-16 Time 13:17 Sent To  
Notes
2002-12-16 00:00:00CALLED SMITH & MOORE FOR A SECOND SET OF
 PLANS AND A PERMIT APPLICATION./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-12-18 Cont ID  
Sent By btrobaug Date 2002-11-04 Time 12:23 Rev Time 1.50
Received By btrobaug Date 2002-11-04 Time 12:25 Sent To P
Notes
2002-11-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION, MAKE ANY NECESSARY CHANGES
 ON PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} THE #6 EQUIPMENT GROUND RAN BETWEEN
 THE METER AND THE PANEL IS CREATING A
 PARALLEL GROUND PATH WITH THE GROUNDED
 CONDUCTOR (NEUTRAL) AND CANNOT BE
 INSTALLED PER 250-24(A)(1).
  
 3} PLEASE NOTE THE GEC SYSTEM MUST
 COMPLY WITH 250-50,SHOW SAME ON PLANS.
  
 4} THE WATER HEATER ON CIRCUITS 18 & 20
 DOES NOT HAVE THE CORRECT OVERCURRENT
 FOR THE LOAD SERVED.
  
 5} PLEASE NOTE THAT THE LAUNDRY CIRCUIT
 MUST COMPLY WITH 220-16(B).SHOW SAME IN
 CALCS & SCHEDULES.
  
 6} PLEASE NOTE THE DRYER MUST COMPLY
 WITH 220-18,IT IS SHOWN AS 1200VA ON
 THE SCHEDULE.
  
 7} THE WATER HEATER LISTED ON CIRCUITS
 9 & 11 @ 5000VA HAS AN OCP OF 40
 AMPS,PLEASE CLARIFY.
  
 8} AHU #1,CIRCUITS 15 & 17 LISTS THE OCP
 AND THE WIRE SIZE INCORRECTLY.
  
 9} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.LIST SAME ON
 SCHEDULE.
  
 10} NOTE THAT SERVICE RECEPTACLES ARE
 REQUIRED IN ATTICS PER 210-63.
  
 11} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 12} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 13} PLEASE NOTE THAT FAN SUPPORTS MUST
 COMPLY WITH 422-18.
  
 14} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ'D PER 210-52(E).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 12:48 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 12:48 Sent To E
Notes
2004-06-11 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-08-11 Cont ID  
Sent By alange Date 2003-08-11 Time 09:27 Rev Time 0.00
Received By alange Date 2003-08-11 Time 09:27 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-01-23 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 08:50 Rev Time 0.00
Received By dpalmer Date 2003-01-23 Time 08:50 Sent To P
Notes
2003-01-23 00:00:00TO PLUMB INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2003-01-13 Time 07:42 Rev Time 0.00
Received By btrobaug Date 2002-12-04 Time 15:17 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2002-11-04 Time 12:23 Rev Time 0.00
Received By btrobaug Date 2002-11-04 Time 12:23 Sent To E
Notes
2002-11-04 00:00:00TO WRT./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-08 Cont ID  
Sent By pkrauss Date 2003-01-08 Time 15:45 Rev Time 0.55
Received By pkrauss Date 2003-01-08 Time 14:52 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-11-18 Cont ID  
Sent By kstevens Date 2002-11-09 Time 10:58 Rev Time 0.40
Received By pkrauss Date 2002-11-18 Time 15:25 Sent To B
Notes
2002-11-18 00:00:00PROVISO:
  
 AS PER 2001 FBC CHAPTER 13 SECTION
 610.1.ABC.3.6, DUCT INSTALLED IN THE
 CAVATIY OF THE WALL SHALL BE INSULATED
 IN ACCORDANCE WITH SECTION 610.1.ABC.2.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-08-15 Cont ID  
Sent By kstevens Date 2003-08-15 Time 15:39 Rev Time 0.50
Received By kstevens Date 2003-08-15 Time 15:39 Sent To  
Notes
2003-08-15 00:00:00REVISION OK W/PROVISO - SANITARY RISER
 TO REFLECT CHANGES THIS REVISION AND
 CHANGE REQUIRED FOR PROVISO ON STAMPED
 SET OF PLANS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-24 Cont ID  
Sent By alange Date 2003-08-11 Time 09:27 Rev Time 0.90
Received By kstevens Date 2003-01-24 Time 15:26 Sent To  
Notes
2003-01-24 00:00:00PASSED - PROVISO - REVISION REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-01-13 Cont ID  
Sent By dpalmer Date 2003-01-23 Time 08:50 Rev Time 0.50
Received By kstevens Date 2003-01-13 Time 13:27 Sent To  
Notes
2003-01-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 A) PREVIOUS PLAN REVIEW COMMENTS NOT
 ADDRESSED.
 1) SHT D-1 ALL PLUMMBING, SANITARY/WATER
 LINES CAPPED SHALL BE INSPECTED PRIOR TO
 COVERING.
 2) SHT M/E-1 PLUMBING NOTES #1, CODE IN
 EFFECT IS FBC-2001 PLUMBING NOT STANDARD
 PLEASE CHANGE REFERENCE.
 3) SHT M/E-1 PLUMBING RISER SHALL RE-
 FLECT THE FLOOR PLAN. THE LAUNDRY ROOM
 IS TO THE LEFT OF THE KITCHEN, NOT BE-
 TWEEN THE KITCHEN AND BATH RISERS. ALSO
 THE LAUNDRY TRAY IS NOT SHOWN ON THE
 RISER. A CLEANOUT IS REQUIRED ON RISER
 ABOVE THE WASH MACHINE MINIMUM OF 4'
 ABOVE FINISHED FLOOR.
 4) SHT M/E-1 PLUMBING RISER, ISLAND VENT
 DOES NOT MEET CODE. (SUGGEST AN AIR AD-
 MITTENCE VALVE)
 5) PER BLDG OFFICIAL, ONCE A PLAN COMES
 IN FOR REVIEW WITH A RISER DIAGRAM, A
 RISER DIAGRAM SHALL BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-11-09 Cont ID  
Sent By btrobaug Date 2002-12-18 Time 12:25 Rev Time 0.50
Received By kstevens Date 2002-11-09 Time 10:57 Sent To M
Notes
2002-11-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT D-1 ALL PLUMBING, SANITARY/WATER
 LINES CAPPED SHALL BE INSPECTED PRIOR TO
 COVERING.
 2) SHT M/E-1 PLUMBING NOTES #1, CODE TO
 READ FBC-2001 PLUMBING NOT STANDARD.
 3) SHT M/E-1 PLUMBING RISER SHALL RE-
 FLECT THE FLOOR PLAN. THE LAUNDRY ROOM
 IS TO THE LEFT OF THE KITCHEN, NOT BE-
 TWEEN THE KITCHEN AND BATH RISERS. ALSO
 LAUNDRY TRAY IS NOT SHOWN ON RISER.
 CLEAN OUT REQUIRED ON RISER ABOVE WASH
 MACHINE MINIMUM OF 4' AFF.
 4) SHT M/E-1 PLUMBING RISER, ISLAND VENT
 DOES NOT MEET CODE. (SUGGEST AN AIR AD-
 MITTENCE VENT)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-12-23 Cont ID  
Sent By hpiskura Date 2002-12-06 Time 08:50 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
***NONE***