Plan Review Details - Permit 02110061
Plan Review Stops For Permit 02110061
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-12-20 Cont ID  
Sent By jwitmer Date 2002-12-20 Time 16:03 Rev Time 0.75
Received By jwitmer Date 2002-12-20 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-11-20 Cont ID  
Sent By hpiskura Date 2002-11-20 Time 10:00 Rev Time 0.00
Received By hpiskura Date 2002-11-19 Time 15:26 Sent To  
Notes
2002-11-20 00:00:00SECTIONS 3/A4 AND 4/A4. PLEASE PROVIDE
 SPECIFIC CONNECTION DETAILS FOR THE
 SUSPENDED CEILING INCLUDING ATTACHMENT
 TO THE EXISTING STRUCTURE.SEE FBC
 104.2.1.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-12-06 Cont ID  
Sent By dpalmer Date 2002-12-06 Time 06:37 Rev Time 0.30
Received By dpalmer Date 2002-12-06 Time 06:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-05 Cont ID  
Sent By dpalmer Date 2002-11-05 Time 06:04 Rev Time 0.25
Received By dpalmer Date 2002-11-05 Time 06:04 Sent To  
Notes
2002-11-05 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A SUBMITTED PANEL
 SCHEDULE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-12-18 Cont ID  
Sent By mcarsill Date 2002-12-18 Time 09:38 Rev Time 0.00
Received By mcarsill Date 2002-12-18 Time 09:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-11-07 Cont ID  
Sent By mcarsill Date 2002-11-07 Time 13:21 Rev Time 0.00
Received By mcarsill Date 2002-11-07 Time 13:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-04 Cont ID  
Sent By btrobaug Date 2002-12-04 Time 17:23 Rev Time 0.00
Received By btrobaug Date 2002-12-04 Time 17:22 Sent To  
Notes
2002-12-04 00:00:00TO COMM BOARD #22./WRT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-04 Cont ID  
Sent By btrobaug Date 2002-11-04 Time 09:34 Rev Time 0.00
Received By btrobaug Date 2002-11-01 Time 09:34 Sent To  
Notes
2002-11-04 00:00:00TO COMM. BOARD # 11./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-12-17 Cont ID  
Sent By hmoser Date 2002-12-17 Time 15:59 Rev Time 0.50
Received By hmoser Date 2002-12-17 Time 15:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By pkrauss Date 2002-11-26 Time 15:57 Rev Time 0.40
Received By pkrauss Date 2002-11-26 Time 15:54 Sent To  
Notes
2002-11-26 00:00:00DENIED:
  
 PROVIDE OUTSIDE AIR CALCS AS PER 2001
 FBC(M) TABLE 403.3.
  
 NO COMBUSTIBLES ABOVE THE CEILING IN THE
 RETURN AIR PLENUM 2001 FBC(M) 602.2.1.
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-12-16 Cont ID  
Sent By kstevens Date 2002-12-16 Time 17:23 Rev Time 0.50
Received By kstevens Date 2002-12-16 Time 17:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By kstevens Date 2002-12-02 Time 11:32 Rev Time 0.50
Received By kstevens Date 2002-12-02 Time 11:32 Sent To  
Notes
2002-12-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-2 TOILET ROOM #206, OTHER
 TOILET ROOMS PROVIDED FOR THE OCCUPANTS
 OF SPECIFIC SPACES (I.E., A PRIVATE
 TOILET ROOM FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE.
 PLEASE SUBMIT A DETAIL. SHOW TOILET OPEN
 ING, BACKING FOR W/C AND SHOWER, LAV
 HEIGHT, CURB FOR SHOWER, SEAT (IF PRO-
 VIDED, ECT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved