| 2002-12-13 00:00:00 | BUILDING DENIED |
| | |
| | 1) NOTE #11 OF THE PLAN NOTES ON SHEET |
| | C1 STATES THAT HURRICANE PANELS ARE |
| | REQUIRED IN HVHZ. THEY ARE REQUIRED IN |
| | THE CITY OF WPB, WHICH IS NOT IN A HVHZ, |
| | BUT IS IN THE WIND-BORNE DEBRIS REGION. |
| | PLEASE REVISE. FBC CHAPTER 16. |
| | |
| | 2) THE FBC SECTION 1707.4.4.2 STATES |
| | THAT WHERE WOOD BUCKS ARE LESS THAN |
| | 1-1/2 INCHES THICK THE WINDOW AND DOOR |
| | ASSEMBLIES ARE REQUIRED TO BE ANCHORED |
| | THROUGH THE JAMB INTO THE STRUCTURAL |
| | SUBSTRATE. PLEASE REVISE THE SLIDING |
| | GLASS DOOR BUCK DETAIL ON A4. |
| | |
| | 3) FBC SECTION 1707.4.4.2 REQUIRES BUCKS |
| | 1-1/2 INCHES THICK OR GREATER TO EXTEND |
| | TO THE INTERIOR FACE OF THE JAMB. PLEASE |
| | REVISE DOOR HEAD/JAMB DETAIL ON A8. |
| | |
| | 4) SPECIFY THE SIZE AND SPECIES OF WOOD |
| | FOR THE WOOD POST SHOWN ON A5. |
| | |
| | 5) THE ENERGY CALC. FORM IS REQUIRED TO |
| | BE SIGNED BY THE OWNER/AGENT. |
| | |
| | 6) PROVIDE THE LISTING INFORMATION AND |
| | MANUFACTURER'S SPECIFICATIONS FOR A ONE |
| | HOUR RATED FIRE ASSEMBLY FOR THE GLASS |
| | BLOCK. |
| | |
| | 7)PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - SH WINDOWS (EXPIRED) |
| | - OUTSWING DOUBLE DOORS (EXPIRED) |
| | |
| | 8) THE PRODUCT APPROVALS FOR THE |
| | MULLIONS DO NOT HAVE DESIGN WINDLOADS |
| | FOR A MULLION LENGTH OF 144" AND AN |
| | OPENING WIDTH OF 120", WHICH IS REQUIRED |
| | AT THE SLIDING GLASS DOOR AND FIXED |
| | GLASS WINDOW ASSEMBLY. |
| | |
| | 9) THE SITE SPECIFIC PRODUCT APPROVAL |
| | FORM FOR THE OVERHEAD GARAGE DOORS IS |
| | NOT ACCEPTABLE. IT MUST REFERENCE THE |
| | THE 2001 FBC, BE SIGNED, SEALED AND |
| | DATED BY THE PRODUCT ENGINEER AND THE |
| | DESIGNER OF RECORD, AND THE LOCATION OF |
| | THE JOB IS REQUIRED. SUBMIT THE SBCCI |
| | PRODUCT EVALUATION REPORT #9606C THAT |
| | ACCOMPANIES THE DRAWING. |
| | |
| | 10)THE STORM PANEL INSTALLATION SCHEDULE |
| | IS NOT CORRECT FOR THE VERTICAL |
| | INSTALLATION ON THE MULLED WINDOWS. THE |
| | SHUTTERS MUST SPAN THE ENTIRE OPENING |
| | PLUS THE REQUIRED EDGE DISTANCE. PLEASE |
| | CORRECT. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |