Plan Review Details - Permit 02102207
Plan Review Stops For Permit 02102207
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2003-06-10 Cont ID  
Sent By rbrown Date 2003-06-06 Time 15:20 Rev Time 0.00
Received By rbrown Date 2003-06-06 Time 15:20 Sent To  
Notes
2003-06-06 00:00:00SEE COMMENTS UNDER THE INDIVIDUAL
 COTTAGE BUILDING PERMIT NUMBERS 03050050
 TO 03050057.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-24 Cont ID  
Sent By rbrown Date 2003-04-24 Time 08:58 Rev Time 0.00
Received By rbrown Date 2003-04-24 Time 08:57 Sent To  
Notes
2003-04-24 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/3/03:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES.). THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???).
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH CONSTRUCTION SERVICES
 DEPARTMENT BEFORE A BUILDING PERMIT CAN
 BE ISSUED.
  
 5) FBC 11-4.1.2EACH OF THE BUILDINGS
 SHALL BE SERVED BY AT LEAST ONE
 ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING AND THE BUS STOP.ACCEPTABILITY
 OF THESE PLANS IS CONTINGENT UPON THE
 CIVIL/SITE PLANS, PERMIT# 02102208,
 BEING PERMITTED. NOTE THAT THE SUBMITTED
 SITE PLAN (SHEET A6-1.1) DOES NOT SHOW
 A PATH TO THE ENTRANCE OF COTTAGE #7.
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) PRODUCT APPROVALS: DOOR, WINDOW, ROOF
 (A) ASPHALT SHINGLE PRODUCT APPROVAL
 NOA# 00-0105.02 EXPIRED ON 4/22/03.
 SUBMIT A VALID PRODUCT APPROVAL.
 (B) THE SUBMITTED COPY OF STEELCRAFT
 MANUF. 98/99 RIM EXIT STEEL DOOR PRODUCT
 APPROVAL NOA# 01-1203.11 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (C) THE SUBMITTED COPY OF STEELCRAFT
 MANUF. F, M FRAME STEEL DOOR PRODUCT
 APPROVAL NOA# 01-0129.12 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (D) NOT USED
 (E) THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM STOREFRONT DOOR
 PRODUCT APPR. NOA# 01-0919.02 ARE POORLY
 REPRODUCED.SUBMIT LEGIBLE COPIES.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (F) THE SUBMITTED 2 PAGE COPY EXTRACT OF
 THE 48 PAGE GAF MODIFIED BITUMEN ROOF
 PRODUCT APPROVAL NOA# 00-0331.09 DOES
 NOT INCLUDE A STATEMENT OF THE MAXIMUM
 DESIGN PRESSURE AND STATES THAT "ALL
 GENERAL AND SYSTEM LIMITATIONS SHALL
 APPLY".SUBMIT COPIES OF THE SHEETS
 WHICH STATE THE GENERAL AND SYSTEM
 LIMITATIONS AND THE MAX DESIGN PRESSURE.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
  
 10) FBC* TABLE 2306.1STRUCTURAL NOTES,
 SHEET STR-GN, PLYWOOD ROOF DECKING
 NOTE 3B.THE REVISION MADE , PER THE G.
 D. KLIEGER COMMENT RESPONSE LETTER, IS
 NOTED.THE * FOLLOWING THE REFERENCE TO
 FBC MEANS CITY OF WPB AMENDMENTS TO THE
 FLORIDA BUILDING CODE (SEE KEY ABOVE).
 THE AMENDED TABLE REQUIRES THE PERIMETER
 ZONE AT THE GABLE END TO HAVE NAILS
 SPACED AT 4"O.C. MAXIMUM, FOR A DISTANCE
 OF 5 FT (NOT 4 FT) FROM THE EDGE OF THE
 ROOF.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-06 Cont ID  
Sent By rbrown Date 2003-01-06 Time 10:09 Rev Time 0.00
Received By rbrown Date 2003-01-06 Time 10:09 Sent To  
Notes
2003-01-06 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4A SIGNED AND SEALED
 SURVEY DRAWING IS REQUIRED.
  
 2) FL. ADMIN. CODE 61G1-16.003EACH
 ARCHITECTURAL PLAN SHEET SHALL BE SIGNED
 PERSONALLY, NOT SIGNATURE STAMPED.
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES SHALL BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMET BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2EACH OF THE BUILDINGS
 SHALL BE SERVED BY AT LEAST ONE
 ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING.ACCEPTABILITY OF THESE PLANS
 IS CONTINGENT UPON UPON THE CIVIL/SITE
 PLANS, PERMIT# 02102208, BEING PERMITTED
 NOTE THAT THE SUBMITTED SITE PLAN (SHEET
 A7-1.1) DOES NOT SHOW A PATH TO THE
 ENTRANCE OF COTTAGE #7.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, EXTERIOR DOORS AND WINDOWS.
  
 8) FBC* 104.2NO FOUNDATIONS ARE SHOWN
 FOR THE COURTYARD ALUMINUM RAILING AND
 GATE.A SEPARATE PERMIT APPLICATION
 WILL BE REQUIRED.
  
 9) FOUNDATION PLAN SHEET S-7.01 HAS
 'MF-16' ANNOTATION AT THE MONOLITHIC
 FOOTING.THIS SHOULD BE 'WF-16' TO
 CORRELATE WITH THE FOOTING SCHEDULE.
  
 10) FBC* TABLE 2306.1STRUCTURAL NOTES,
 SHEET STR-GN, PLYWOOD ROOF DECKING.THE
 PERIMETER ZONE AT THE GABLE ENDS SHALL
 HAVE NAILS SPACED AT 4"O.C. MAXIMUM, TO
 A DISTANCE OF 5 FEET (NOT 24") FROM THE
 EDGE OF THE ROOF.
  
 11) STRUCTURAL NOTES, SHEET STR-GN, WOOD
 TRUSS NOTE 6.IT IS NOTED THAT THE
 TRUSS DESIGN ENGINEER IS TO PROVIDE THE
 WIND UPLIFT REACTIONS.THE PERMIT
 CANNOT BE ISSUED UNTIL THE REACTIONS ARE
 SPECIFIED ON THE PLANS FOR CROSS
 REFERENCE AGAINST THE PROPOSED TRUSS
 ANCHORS AND STRAPS.
  
 12) FBC 410.2.2 FIRE SEPARATION.THE
 LAUNDRY ROOM SHALL BE SEPARATED FROM
 OTHER ROOMS BY 1-HOUR RATED WALLS AND
 3/4-HOUR DOORS.SHEET A7-2.1 SHOWS
 PARTITION TYPES C AND I WHICH ARE NON-
 RATED.
  
 13) FBC 2309.6ATTIC ACCESS.THE ATTIC
 ACCESS PANELS SHOWN ON SHEET A7-11.1 ARE
 NOT DIMENSIONED.ATTIC ACCESS OPENINGS
 SHALL BE NOT LESS THAN 20X36 INCHES.
  
 14) FBC 2405.2THE GLAZED PANEL
 ADJACENT TO THE STAFF OFFICE DOOR IS
 MARKED AS REF *H.NO DETAILS ARE GIVEN
 IN THE SCHEDULE ON SHEET A7-10.1, WHICH
 ONLY GOES UP TO REF F.THE GLAZED PANEL
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2003-10-03 Cont ID  
Sent By dpalmer Date 2003-10-03 Time 07:18 Rev Time 0.75
Received By dpalmer Date 2003-10-03 Time 07:18 Sent To  
Notes
2003-10-03 00:00:00PLEASE SEE COMMENTS UNDER EACH INDIVID-
 -UAL COTTAGE PERMITS.
 03050050-51,52,53,54,55,57

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-05-15 Cont ID  
Sent By dpalmer Date 2003-05-15 Time 12:07 Rev Time 1.50
Received By dpalmer Date 2003-05-15 Time 12:07 Sent To  
Notes
2003-05-15 00:00:00************ UNSAT **************
  
 PLEASE SEE COMMENTS FROM PREVIOUS REVIEW
  
 1)NOTE: PLEASE SEE RISER DIAGRAM,THE
 COTTAGE UNIT #`S DO NOT CORRELATE WITH
 UNIT #`S SHOWN ON UPPER LEFT HAND
 CORNER OF PANEL SCHEDULE?
 PLEASE ALSO CLARIFY WHY THERE ARE TWO-
 -SETS OF 250 MCM FOR A 200A MCB PANEL
 AND CLARIFY HOW TWO 250MCM WILL FIT INTO
 A MCB? IF MAC ADAPTERS ARE TO BE USED
 PLEASE ADD NOTE. 215-5
  
 2)NOTE: PLEASE SEE LOAD CALCULATIONS,
 ON PANEL SCHEDULE. LOADS ARE INCOMPLETE
 FOR PANEL. SHOWN MOSTLY AS BLANK.
 THE LOAD CALCULATIONS ON BOTTOM RIGHT
 HAND CORNER OF SHEET E7-4.01 ARE FOR
 SFR/DWELLING. PLEASE NOTE, CALCS NEED
 TO BE DONE UNDER COMM USE AND SHOW ALL
 CONTINUOUS LOADS AT 125%, WHICH WAS
 STARTED ON PANEL SCHEDULE?
 215-5,215-3, 230-42,220-10,11,13,03,,
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE REMOVE OLD/VOIDED SHEETS
 AND INSERT NEW INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SEE LETTER ATTACHED FOR DESIGN
 OF RECORD. FS 553.80(2)(B)
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-03-28 Cont ID  
Sent By dpalmer Date 2003-03-28 Time 04:57 Rev Time 1.00
Received By dpalmer Date 2003-03-28 Time 04:39 Sent To  
Notes
2003-03-28 00:00:00************* NOTES/UNSAT **********
 #6,8,11,13
 1)NOTE: PLEASE SEE RISER DIAGRAM/PANEL
 SCHEDULE AND LOAD CALCUALTIONS.
 LOAD CALCS SHOW PANEL TO BE 250 MLO W/
 250A MCB, PANEL SCHEDULE SHOWS 200A MCB,
 PLEASE CLARIFY AND CORRELATE.
  
 2)NOTE: PLEASE CLARFIY LOAD CALCAULTIONS
 LOAD CALCS ON PANEL SCHEDULE ARE SHOWN
 AS COMM AND OTHER LOAD CALCS SHOWN AS
 RESIDENTIAL??
 MIXED USE
  
 3)NOTE: PLEASE NOTE, PLANS UNDER THIS
 PERMIT # SHOWS PANEL 6L/A ON RISER AND
 7L/A ON PANEL SCHEDULE AND SHOWS TYP FOR
 9,10 AND 11. TITLE BLOCK ON RIGHT SHOWS
 TYPICAL FOR #`S 6,8,11,13?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]
 ********NOTES FOR 7,9,10,12 *******
  
 PLEASE SEE OTHER NOTES FOR COTTAGES
 SOME NOTES ARE THE SAME.
  
 1)NOTE: PLEASE CLARFIFY HOW/WHERE
 SERVICE SIZE CHANGES? RISER SHOWS
 SEC`S CHANGING TO TWOS SETS OF 250 MCM
 FOR 8,9,12 &13?
 PLEASE NOTE, TWO SETS OF 250MCM ARE
 RATED FOR 510A`S? PLEASE CLARIFY.
 PANELS ARE SHOWN AT 200A MC AND LOAD
 CALCS AT BOTTOM SHOW 250 OCP FOR 250A
 PANEL??
 PLEASE SEE TITLE BLOCK SHOWS TYPICAL
 AS UNITS/ 7,9,10 &12 AND ABOVE PANEL,
 TYPICAL SHOWS 8,12,13??
  
 PLEASE CORRELATE. PLEASE SUBMIT FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-27 Cont ID  
Sent By dpalmer Date 2002-11-27 Time 05:07 Rev Time 2.00
Received By dpalmer Date 2002-11-27 Time 05:07 Sent To  
Notes
2002-11-27 00:00:00*************** UNSAT *****************
  
 1)NOTE:PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED OANEL
 SCHEDULES.
  
 2)NOTE: PLEASE CLARIFY SD`S SHOWN IN
 A/C CLOSET? ARE THESE DUCT DETECTORS?
  
  
 3)NOTE: PLEASE NOTE, ARC FAULT PROTECT-
 -ION REQ`D FOR BEDROOM CIRCUITS. 210-12
 PLEASE SHOW ON PANEL SCHEDULES.
  
 4)NOTE: PLEASE NOTE, REQ`D BATH CIRCUTIT
 (S) MISSING. 210-52D/ PLEASE LIST ON
 PANEL SCHEDULE PER 210-11-C-3
  
 5)NOTE: PLEASE CLARIFY MCB IN PANELS
 STILL MEETING 230-76/230-79 FOR MANUAL
 MEANS OF DISC AND RATED FOR THE LOAD
 SERVED. PLEASE NOTE, A SHUNT TRIP IS
 PERMITTED, HOWEVER, MCB STILL NEEDS TO
 MEET THE ABOVE.
  
 6)NOTE: PLEASE COMPLETE LOAD CALCUALTION
 -S.
  
 PLEASE NOTE, THIS IS A TYPICAL REVIEW
 FOR ALL COTTAGE UNITS, AS PLANS WERE
 SUBMITTED FOR ALL AS TYPICAL.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-06-25 Cont ID  
Sent By mamini Date 2003-06-25 Time 10:36 Rev Time 1.00
Received By mamini Date 2003-06-25 Time 10:35 Sent To  
Notes
2003-06-25 00:00:00PASSED :
 1. SEE PERMIT # 02102208 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-03-17 Cont ID  
Sent By mamini Date 2003-03-17 Time 10:32 Rev Time 1.00
Received By mamini Date 2003-03-17 Time 10:32 Sent To  
Notes
2003-03-17 00:00:00FAILED:
 1. SEE REVIEW COMMENTS, PERMIT #02102208
 DATED 03-17-03.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-11-06 Cont ID  
Sent By mamini Date 2002-11-06 Time 15:23 Rev Time 0.00
Received By mamini Date 2002-11-06 Time 15:23 Sent To  
Notes
2002-11-06 00:00:00FAILED:
 1. SEE REVIEW COMMENTS FOR PLAN REVIEW #
 02102208.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-04-24 Cont ID  
Sent By nmccray Date 2003-04-24 Time 14:42 Rev Time 0.00
Received By nmccray Date 2003-04-24 Time 14:42 Sent To  
Notes
2003-04-24 00:00:001) HOW WILL THE COTTAGES BE LICENSED
 UNDER STATE, COUNTY, AND CITY
 REQUIREMENTS.
  
 2) PLEASE INDICATE HOURS OF OPERATION
 FOR THE COTTAGES. WILL THE COTTAGES BE
 OPERATIONAL FULL TIME OR PART TIME.
  
 3) IS THERE ANY COOKING PLANNED AT THE
 COTTAGES THAT WOULD CREATE SMOKE OR
 GREASE LADEN VAPORS.
  
 4) SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR THE INSTALLATION OF FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 5) A KNOX-BOX ENTRY SYSTEM WILL BE
 REQUIRED.
  
 NATE MCCRAY, CAPTAIN
 659-8096, EXT 8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-01-10 Cont ID  
Sent By mcarsill Date 2003-01-10 Time 13:54 Rev Time 0.00
Received By mcarsill Date 2003-01-10 Time 13:54 Sent To  
Notes
2003-01-10 00:00:001) HOW WILL THE COTTAGES BE LICENSED
 UNDER STATE, COUNTY, AND CITY
 REQUIREMENTS.
  
 2) PLEASE INDICATE THE AGES OF THE
 OCCUPANTS FOR THE COTTAGES AND
 APPROPRIATE STAFF RATIO'S.
  
 3) PLEASE PROVIDE A LIFE SAFETY PLAN
 INDICATING OCCUPANT LOADS AND TRAVEL
 DISTANCES TO EXITS.
  
 4) PLEASE INDICATE HOURS OF OPERATION
 FOR THE COTTAGES. WILL THE COTTAGES
 BE OPERATIONAL FULL TIME OR PART TIME.
  
 5) PLEASE PROVIDE A DATA BOX ON THE
 TITLE PAGE INDICATING APPROPRIATE CODES
 AND CONSTRUCTION TYPES FOR THE COTTAGES.
  
 6) IS THERE ANY COOKING PLANNED AT THE
 COTTAGES THAT WOULD CREATE SMOKE OR
 GREASE LADEN VAPORS.
  
 7) FIRE SPRINKLER HEADS APPEAR TO BE
 MISSING FROM THE MIDDLE OF SOCIAL ROOM.
  
 8) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE INSTALLATION OF FIRE SPRINKLER
 SYSTEM.
  
 9) PROVIDE SEPARATE PLANS AND PERMITS
 FOR THE FIRE ALARM SYSTEMS.
  
 10) A KNOX-BOX ENTRY SYSTEM WILL BE
 REQUIRED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:35 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 09:12 Sent To  
Notes
2003-05-05 00:00:00COMM BOARD #12,PLANS NEXT TO CONF ROOM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 15:03 Rev Time 0.00
Received By sthyng Date 2003-03-13 Time 15:03 Sent To  
Notes
2003-03-13 00:00:00COMM BOARD #46, RACK 1ST & 2ND SHELF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-06-10 Cont ID  
Sent By pkrauss Date 2003-06-10 Time 10:33 Rev Time 0.10
Received By pkrauss Date 2003-06-10 Time 10:32 Sent To  
Notes
2003-06-10 00:00:00PLANS APROVED ON INDIVIDUAL PERMITS
 5-10-03 PHK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-04-11 Cont ID  
Sent By pkrauss Date 2003-04-11 Time 14:34 Rev Time 0.45
Received By pkrauss Date 2003-04-11 Time 14:14 Sent To  
Notes
2003-04-11 00:00:00DENIED:COTTAGES 6 - 13
  
 1.PLAN SHEET A6-2.1 & A7-2.1, LAUNDRY
 ROOM NOW HAS A 1 HR SEPARATION.PLEASE
 PROVIDE FIRE DAMPERS ON THE 14" X 14"
 SUPPLY & RETURN DUCT THAT RUNS THROUGH
 THIS DUCT.
  
 2.DUCTS THAT ARE DO NOT EXCEED 100 SQ
 INCHES ARE NOT REQUIRED TO HAVE FIRE
 DAMPERS IF THE DUCT IS A MINIMUM OF
 .0217" STEEL & HAS NO DUCT OPENINGS FOR
 NOT LESS THAN 5 FT FROM RATED WALL.
 PROVIDE MANUFACTURERS INSTALLATION
 INSTRUCTIONS FOR THE FIRE DAMPER ON THE
 JOBSITE AT TIME OF INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By pkrauss Date 2002-12-02 Time 13:36 Rev Time 3.00
Received By pkrauss Date 2002-12-02 Time 12:32 Sent To  
Notes
2002-12-02 00:00:001ST PLAN CHECK
 DENIED:REVIEW COTTAGES #6,7,10,9,10,
 11,12, & 13.
  
 GAS DRYERS ARE INDICATED ON THE PLUMBING
 PLAN.PROVIDE CALCULATIONS INDICATING
 WHETHER THEY ARE INSTALLED IN A
 "CONFINED" OR "UNCONFINED" SPACE.
  
 PLEASE NOTE AS PER 2001 FBC(M) 504.5,
 DRYER INSTALLATIONS EXHAUSTING MORE THAN
 200 CFMSHALL BE PROVIDED WITH MAKEUP
 AIR.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL COMPLY WITH 2001 FBC(M) 606.4.1,
 DETECTOR SHALL ACTIVATE A VISIBLE AND
 AUDIBLE SUPERVISORY SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION OR SHALL
 ACTIVATEA VISIBLE & AN AUDIBLE SIGNAL
 IN AN APPROVED LOCATION IN NORMALLY
 OCCUPIED AREA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-07 Cont ID  
Sent By kstevens Date 2003-06-07 Time 14:47 Rev Time 0.33
Received By kstevens Date 2003-06-07 Time 14:47 Sent To  
Notes
2003-06-07 00:00:00PASSED/PROVISO
  
  
 PLUMBING APPROVAL ONLY.SEPARATE PERMIT
 REQUIRED FOR GAS. MORE INFORMATION WILL
 BE REQUIRED WHEN APPLYING FOR PERMIT.
 - SPECIFICATION SHEET FOR ADA ACCESSIBLE
 SLIDING DOOR HARDWARE FOR DOOR AT ROOM
 #104A REQUIRED AT TIME OF FINAL INSPECT-
 ION. -

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-01 Cont ID  
Sent By kstevens Date 2003-04-01 Time 10:10 Rev Time 1.50
Received By kstevens Date 2003-04-01 Time 10:09 Sent To  
Notes
2003-04-01 00:00:00PASSED/PROVISO
  
 PLUBMING ONLY - INFORMATIONS REQUIRED
 FOR GAS TO BE SUBMITTED WITH APPLICATION
 SPECIFICATION SHEET FOR ADA ACCESIBLE
 SLIDING DOOR HARDWARE FOR DOOR AT RM. #
 104A NOT FOUND.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-01-06 Cont ID  
Sent By kstevens Date 2002-12-16 Time 15:16 Rev Time 3.00
Received By kstevens Date 2002-12-16 Time 15:16 Sent To  
Notes
2002-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11
  
 1) PER SECTION 11-9.1.1, ALL PUBLIC USE
 AND COMMON USE AREAS ARE REQUIRED TO BE
 DESIGNED AND CONSTRUCTED TO COMPLY WITH
 SECTION 11-4 (ACCESSIBLE ELEMENTS AND
 SPACES: SCOPE AND TECHNICAL REQUIREMENTS
 ALL BATHROOM SHALL BE ACCESSIBLE AND
 THE STAFF TOILET ROOM SHALL BE ACCESSI-
 BLE. PLEASE PROVIDE DETAILS.
 2) SHT P6-2.01 DRINKING FOUNTAIN, SHOW
 COMPLIANCE WITH SEC 11-4.1.3(10)(A),
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BEND OR STOOPING.
 3) SEC. 11-4.13.9, DOOR HARDWARE. WHEN
 SLIDING DOORS ARE FULLY OPEN, OPERATING
 HARDWARE SHALL BE EXPOSED AND USABLE
 FROM BOTH SIDES.
 4) SEC 11-4.13.11, DOOR OPENING FORCE.
 THE MAXIMUM FORCE FOR PUSHING OR PULLING
 OPEN A DOOR SHALL BE AS FOLLOWS PER
 (2)(C) SLIDING OR FOLDING DOORS: 5 LBF
 5) SHT P6-3.01 DOMESTIC WATER RISER.
 WATER HAMMER ARRESTORS REQUIRED BY 406.9
 FOR QUICK CLOSING VALVES, (WASH MACHINES
 DISHWASHERS, & ICE MAKERS), SHALL BE LO-
 CATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT AT THE TOP OF THE DROP. PER
 PDI-WH 201 AND MANUF. INSTALLATION IN-
 STRUCTIONS.
 6) FOLLOWING COMMENTS FOR GAS PERMIT
 APPLICATION REQUIREMENTS.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3) LISTED WATER HEATERS SHALL BE IN-
 STALLED IN ACCORDANCE WITH THEIR LISTING
 AND THE MANUFACTURES INTSRUCTIONS. THERE
 SHALL BE CLEARANCE FOR SERVICING HEATER.
 4) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE SEC 402.2.
 5) SHTS P6-2.01 & P6-3.02 GAS PLAN VIEW
 & GAS RISER DIAGRAM, MANUAL SHUT OFF
 VALVE TO BE UPSTREAM OF SOLENOID VALVE,
 AND A UNION IS REQUIRED BETWEEN VALVES.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2003-06-06 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:35 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By sgraham Date 2003-01-13 Time 11:25 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-13 00:00:00DENIED, NEED MINOR AMENDMENT AND THE
 PLAT NEED TO BE RECORDED


Account Summary | Usage Policy | Privacy Policy