Plan Review Details - Permit 02102206
Plan Review Stops For Permit 02102206
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2006-06-11 Cont ID  
Sent By rbrown Date 2006-06-11 Time 16:29 Rev Time 0.00
Received By rbrown Date 2006-06-11 Time 16:29 Sent To  
Notes
2006-06-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 4/24/06
  
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1004.1.2 AND 1004.1.4 EXCEPTION 2
 SHEET A5-2.1, MEETING SPACE (RM 113/115)
 FORMED BY UNITING ROOMS 113 AND 115 NOW
 HAS AN OCCUPANCY OF 65 PERSONS.EVERY
 ROOM WITH AN OCCUPANCY OF 50 OR MORE
 PERSONS SHALL HAVE NOT LESS THAN TWO
 EXIT ACCESS DOORS.AS THIS IS A
 SPRINKLERED BUILDING, THE EXIT ACCESS
 DOORS MUST BE AT A DISTANCE APART NOT
 LESS THAN 1/3 THE MAXIMUM DIAGONAL
 DIMENSION OF THE ROOM (THE REQUIRED
 SEPARATION WOULD BE 1/2 THE DIAGONAL IF
 THE BUILDING WERE NOT SPRINKLERED).
 RELOCATE DOOR 113.A AND/OR 115.A TO
 COMPLY.PLEASE NOTE THAT DOOR 109.B IS
 NOT CONSIDERED AS AN EXIT ACCESS DOOR.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2006-02-19 Cont ID  
Sent By rbrown Date 2006-02-19 Time 15:35 Rev Time 0.00
Received By rbrown Date 2006-02-19 Time 15:35 Sent To  
Notes
2006-02-19 00:00:00STRUCTURAL AND ARCHITECTURAL REVISION
 SUBMITTED 1/27/06 FOR ADDITION OF TWO
 COLUMNS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-01-05 Cont ID  
Sent By rbrown Date 2006-01-05 Time 07:47 Rev Time 0.00
Received By rbrown Date 2006-01-05 Time 07:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-11-21 Cont ID  
Sent By rbrown Date 2005-11-21 Time 12:21 Rev Time 0.00
Received By rbrown Date 2005-11-21 Time 12:21 Sent To  
Notes
2005-11-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 9/15/05 FOR NEW
 DESIGN FOR THE EDUCATION BUILDING.
  
 A) SUBMIT A PRODUCT APPROVAL LOUVER
 DOORS (DOORS 105A, 106A AND 116A).ON
 SHEET A5-10.1, THESE DOORS ARE CALLED UP
 AS HOLLOW METAL ON THE DOOR SCHEDULE BUT
 THE DOOR TYPE ELEVATION HAS A TITLE
 'HOLLOW METAL DOOR WITH LOUVER'.EITHER
 SUBMIT A LOUVER DOOR PRODUCT APPROVAL OR
 CLARIFY THAT THESE DOORS ARE NOT
 LOUVERED
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-08-17 Cont ID  
Sent By rbrown Date 2005-08-17 Time 18:25 Rev Time 0.00
Received By rbrown Date 2005-08-17 Time 14:55 Sent To  
Notes
2005-08-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 REVISION SUBMITTED ON 7/6/05 FOR NEW
 DESIGN FOR THE EDUCATION BUILDING.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC TABLE 704.2.4(FOOT NOTE 2) EXIT
 ACCESS CORRIDORS IN EDUCATIONAL
 OCCUPANCY.SHEET A5-2.1 THE INSTRUCTION
 ROOMS DO NOT HAVE AT LEAST ONE EXIT DOOR
 DIRECTLY TO THE OUTSIDE SO THE EXIT
 ACCESS CORRIDOR (102) IS REQUIRED TO BE
 ONE-HOUR FIRE-RATED.ALSO, THE ROOM
 DOORS LEADING TO THE CORRIDOR ARE
 REQUIRED TO BE 20-MINUTE FIRE-RATED.
 AMEND THE PLANS AND DOOR SCHEDULE.
  
 2) FBC 11-4.16.4WATER CLOSET GRAB BARS
 SHEET A5-4.1.INTERIOR ELEVATIONS 3B,
 4B, 5B AND 6B SHOW THE LENGTH OF THE
 SIDE GRAB BAR AS 3'-0".THIS SHOULD BE
 3'-6".AMEND THE PLANS.
  
 3) FBC 1606.1.3UPLIFT AT HIP TRUSSES.
 SHEET S-5.02 THE FOUR HIP TRUSSES ARE
 MARKED WITH THE SAME TYPE 1 'TRUSS TO
 WALL CONNECTION' THAT IS USED FOR THE
 TYPICAL TRUSS.THE TRIBUTARY AREA FOR
 THE HIP TRUSSES EXCEEDS THAT OF THE
 TYPICAL TRUSS AND AND RESULTS IN AN
 UPLIFT THAT EXCEEDS THE CAPACITY OF THE
 PROPOSED USP HTA12 TRUSS ANCHOR.AMEND
 THE PLAN OR SUBMIT CALCULATIONS TO
 JUSTIFY THE PROPOSED TRUSS ANCHOR FOR
 THIS APPLICATION.
  
 4) FBC* 104.2 SHEET S-5.03, SECTION G.
 THE PROPOSED USE OF 'THREADED ROD WITH
 4" EMBEDMENT' TO ATTACH THE 3X6'S @ 16"
 O.C. TO THE 3X10 AND TO THE 3X6 LEDGER
 IS NOT A RECOGNISED WOOD-TO-WOOD
 CONNECTION DETAIL.AMEND/CLARIFY THIS
 DETAIL.
  
 5) SHEET A5-10.1, DOOR SCHEDULE.DOOR
 113A IS SHOWN AS BEING 5 FEET WIDE.
 SHEET A5-2.1 DOES NOT INDICATE A 5 FOOT
 WIDE DOOR.AMEND/CLARIFY THE PLANS.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE
 GLASS BLOCK WINDOWS, THE SECTIONAL
 OVERHEAD DOORS (DOORS 117B AND 118B)AND
 THELOUVER DOORS (DOORS 105A, 106A AND
 116A).
  
 7) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-02-25 Cont ID  
Sent By rbrown Date 2005-02-25 Time 09:19 Rev Time 0.00
Received By rbrown Date 2005-02-25 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-03-04 Cont ID  
Sent By rbrown Date 2004-03-04 Time 11:32 Rev Time 0.00
Received By rbrown Date 2004-03-04 Time 11:32 Sent To  
Notes
2004-03-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 61G1-16.004FL. ADMIN. CODE.ADD, TO
 EACH ARCHITECTURAL SHEET, THE PRINTED
 NAME AND LICENSE NUMBER OF JORGE GARCIA
 AS THE ARCHITECT WHO SEALED THE PLANS.
 THIS MAY BE DONE BY STAMP OR HANDWRITTEN
  
 THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2003-10-14 Cont ID  
Sent By rbrown Date 2003-10-14 Time 14:42 Rev Time 0.00
Received By rbrown Date 2003-10-14 Time 14:42 Sent To  
Notes
2003-10-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 6/5/03:
  
 3) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 4) IMPACT FEES. THE PLANS SHALL BE TAKEN
 TO PALM BEACH COUNTY BUILDING DEPARTMENT
 FOR IMPACT FEE ASSESSMENT. THEY SHALL BE
 STAMPED AT THAT OFFICE AND A COPY OF THE
 PAID RECEIPT SUBMITTED TO THE CITY OF
 WEST PALM BEACH DEPT OF CONSTRUCTION
 SERVICES BEFORE A PERMIT CAN BE ISSUED.
  
 6) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO, ON SHEET 1, COMPLETE THE
 PROJECT DETAILS INCLUDING NAME OF OWNER,
 PROJECT ADDRESS (4888 N. HAVERHILL RD),
 ZIP (33417) AND PERMIT NUMBER (02102206)
  
 --PROVISO--
 THE SUBMITTED PGT INDUSTRIES ALUMINUM
 FIXED WINDOW (PRODUCT APPROVAL
 NOA# 01-0102.01) DOES NOT HAVE
 SUFFICIENT DESIGN PRESSURE RATING FOR
 WINDOW MARK 'A' (-64.4 PSF REQ'D) OR
 WINDOW MARK 'C' TO OFFICE 120 (-65.3 PSF
 REQ'D).THE SUBMITTED ARCH ALUMINUM
 WINDOW WALL SYSTEM PRODUCT APPROVAL
 NOA# 01-0329.02 CAN BE USED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-06-06 Cont ID  
Sent By rbrown Date 2003-06-05 Time 16:25 Rev Time 0.00
Received By rbrown Date 2003-06-05 Time 16:25 Sent To  
Notes
2003-06-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/10/03 AND 4/18/03:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.4SITE SURVEY.A SIGNED AND
 SEALED SURVEY DRAWING PREPARED BY A
 QUALIFIED SURVEYOR IS REQUIRED (REF:
 472.025(1) FL. STATUTES.). THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???)
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PLANS STAMPED BY THEM
 AND A COPY OF THE RECEIPT SUBMITTED TO
 THE CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING AND THE BUS
 STOP.ACCEPTABILITY OF THIS PERMIT
 APPLICATION IS CONTINGENT UPON THE
 CIVIL/SITE PLANS, UNDER PERMIT 02102208,
 BEING PERMITTED.
  
 6) FBC 13-103.1.1.1 AND 103.1.2SHEET 2
 OF THE SUBMITTED ENERGY CODE COMPLIANCE
 FORMS SHALL BE SIGNED BY THE OWNER (OR
 THE PROJECT ARCHITECT, OR OTHER
 AUTHORIZED AGENT DESIGNATED BY THE
 OWNER) TO CERTIFY COMPLIANCE WITH THE
 CODE.ALSO, THE ARCHITECT'S NAME AND
 REGISTRATION NUMBER SHALL BE ADDED ABOVE
 THOSE OF THE OTHER SYSTEM DESIGNERS.ON
 SHEET 1, COMPLETE THE PROJECT DETAILS
 INCLUDING NAME OF OWNER, PROJECT ADDRESS
 (4888 N. HAVERHILL RD), ZIP (33417)
 AND PERMIT NUMBER (02102206).
  
 7) PRODUCT APPROVALS.THE PRODUCT
 APPROVAL SHEETS SHALL BE MARKED, AS
 APPROPRIATE TO IDENTIFY WHICH PRODUCT
 OPTIONS/MATERIALS ARE TO BE USED, ALSO:
 (A) THE SUBMITTED COPIES OF TIMBERLINE
 SELECT 40 ASPHALT SHINGLE PRODUCT
 APPROVAL NOA# 03-0219.08 IS MISSING
 SHEET 3 OF 3.ALSO, SHEET 2 IS A POOR
 COPY.SUBMIT TWO COPIES OF A COMPLETE
 AND LEGIBLE PRODUCT APPROVAL.
 (G) THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM NARROW STILE
 DOOR PRODUCT APPROVAL NOA# 01-0910.09
 ARE POORLY REPRODUCED.SUBMIT LEGIBLE
 COPIES.NOTE THAT THESE DOORS ARE NOT
 IMPACT RESISTANT, AND WILL REQUIRE THE
 INSTALLATION OF HURRICANE SHUTTERS.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (H) THE SUBMITTED ARCH ALUMINUM SERIES
 4500 STOREFRONT PRODUCT APPROVAL NOA#
 00-1220.05 IS FOR A NON-IMPACT RATED
 SYSTEM.THE INSTALLATION OF HURRICANE
 MISSILE IMPACT PROTECTION SHUTTERS WILL
 BE REQUIRED.THE PLANS SHALL IDENTIFY
 WHERE THIS SYSTEM IS TO BE USED AND A
 HURRICANE MISSILE IMPACT PROTECTION
 SHUTTER PRODUCT APPROVAL SHALL BE
 SUBMITTED.
  
 13) NOTED:
 SHEET A5-1.1, BUILDING CODE ANALYSIS
 TABLE, STATES MINIMUM ALLOWABLE
 CONSTRUCTION TYPE VI.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-04-23 Cont ID  
Sent By shernand Date 2003-05-05 Time 08:57 Rev Time 0.00
Received By rbrown Date 2003-04-18 Time 14:21 Sent To  
Notes
2003-04-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 1/10/03:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC* 104.2.4A SIGNED AND SEALED SURVEY
 DRAWING IS REQUIRED.THE SUBMITTED
 SURVEY SHEET IS FOR A DELRAY BEACH
 LOCATION (???)
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING AND BUS STOP
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) PRODUCT APPROVALS: DOOR, WINDOW, ROOF
 (A) ASPHALT SHINGLE PRODUCT APPROVAL
 NOA# 00-0105.02 WILL EXPIRE ON 4/22/03.
 IF THIS OCCURS BEFORE THE A PERMIT
 APPLICATION IS MADE, THEN THE PRODUCT
 APPROVAL IS NOT VALID AND NEW ONE SHALL
 BE SUBMITTED.
 (B) THE SUBMITTED COPY OF STEELCRAFT
 MANUF. 98/99 RIM EXIT STEEL DOOR PRODUCT
 APPROVAL NOA# 01-1203.11 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (C) THE SUBMITTED COPY OF STEELCRAFT
 MANUF. F,M FRAME STEEL DOOR PRODUCT
 APPROVAL NOA# 01-0129.12 IS MISSING TEXT
 SHEETS 2 AND 3 (SPECIFIC AND GENERAL
 CONDITIONS), AND SOME OF THE DRAWING
 SHEETS.SUBMIT A COMPLETE PRODUCT
 APPROVAL.
 (D) SHEET A5-10.1, WNDOW SCHEDULE.
 THE WIDTH OF WINDOW TYPE B, AT 7 FEET,
 IS OUTSIDE THE SCOPE OF THE SUBMITTED
 ARCH ALUMINUM WINDOW WALL PRODUCT
 APPROVAL NOA# 01-0329.02 AND THE
 SUBMITTED PGT INDUSTRIES FIXED WINDOW
 PRODUCT APPROVAL NOA# 02-0716.03. SUBMIT
 A PRODUCT APPROVAL WHICH COVERS THE
 SPECIFIED WINDOW DIMENSIONS.
 (E) THE DRAWING SHEETS OF THE SUBMITTED
 COPIES OF ARCH ALUMINUM STOREFRONT DOOR
 PRODUCT APPR. NOA# 01-0919.02 ARE POORLY
 REPRODUCED. SUBMIT LEGIBLE COPIES.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
 (F) THE SUBMITTED 2 PAGE COPY EXTRACT OF
 THE 48 PAGE GAF MODIFIED BITUMEN ROOF
 PRODUCT APPROVAL NOA# 00-0331.09 DOES
 NOT INCLUDE A STATEMENT OF THE MAXIMUM
 DESIGN PRESSURE AND STATES THAT "ALL
 GENERAL AND SYSTEM LIMITATIONS SHALL
 APPLY".SUBMIT COPIES OF THE SHEETS
 WHICH STATE THE GENERAL AND SYSTEM
 LIMITATIONS AND THE MAX DESIGN PRESSURE.
 COPIES OF MIAMI-DADE PRODUCT APPROVALS
 CAN BE PRINTED FROM THEIR WEBSITE,WWW.
 MIAMIDADE.GOV/BUILDINGCODE/PC-SEARCH.HTM
  
 8) FBC* TABLE 2306.1STRUCTURAL NOTES,
 SHEET STR-GN, PLYWOOD ROOF DECKING
 NOTE 3B.THE REVISION MADE, PER THE
 G.D. KLIEGER COMMENT RESPONSE LETTER, IS
 NOTED.THE * FOLLOWING THE REFERENCE TO
 FBC MEANS CITY OF WPB AMENDMENTS TO THE
 FLORIDA BUILDING CODE (SEE KEY ABOVE).
 THE AMENDED TABLE REQUIRES THE PERIMETER
 ZONE AT THE GABLE END TO HAVE NAILS
 SPACED AT 4"O.C. MAXIMUM, FOR A DISTANCE
 OF 5 FT (NOT 4 FT) FROM THE EDGE OF THE
 ROOF.
  
 9) SHEET S-5.02, ROOF TRUSS ANCHORS.
 THE ADDITION OF TYPICAL TRUSS ANCHOR
 SPECIFICATION, PER THE K.D. KLIEGER
 COMMENT RESPONSE LETTER OF 2/5/03, IS
 NOTED.THE PLAN SHALL STILL BE AMENDED
 TO STATE THE WORST CASE UPLIFT TO BE
 RESISTED BY THESE ANCHORS.NOTE THE
 IMPLICATIONS OF COMMENT 14 BELOW.
  
 13) SHEET A5-1.1, BUILDING CODE ANALYSIS
 TABLE.THE STATED CONSTRUCTION TYPE HAS
 REVISED FROM TYPE V TO TYPE VI.THIS IS
 NOT CONSISTENT WITH THE CONSTRUCTION
 SHOWN ON SHEETS S-5.O1, S-5.03 AND
 A5-6.1 THRO' A5-7.2.AMEND SHEET AS
 REQUIRED.
  
 14) COLD FORM METAL TRUSSES.SHEETS
 A5-2.2, A5-5.1 THRO' A5-7.2 HAVE ALL
 BEEN REVISED TO SHOW COLD FORM METAL
 TRUSSES.THE REVISION DOES NOT
 CORRELATE WITH SHEETS S-5.02, S-5.03 OR
 STR-GN WHICH ALL STILL REFER TO WOOD
 TRUSSES.AMEND THE PLANS.
  
 15) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-01-10 Cont ID  
Sent By rbrown Date 2003-01-10 Time 16:18 Rev Time 0.00
Received By rbrown Date 2003-01-10 Time 16:18 Sent To  
Notes
2003-01-10 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC* 104.2.4A SIGNED AND SEALED
 SURVEY DRAWING IS REQUIRED.
  
 2) FL. ADMIN. CODE 61G1-16.003EACH
 ARCHITECTURAL PLAN SHEET SHALL BE SIGNED
 PERSONALLY, NOT SIGNATURE STAMPED.
  
 3) INFORMATIVE:
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 4) INFORMATIVE:
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO THE
 CITY OF WEST PALM BEACH CONSTRUCTION
 SERVICES DEPARTMENT BEFORE A BUILDING
 PERMIT CAN BE ISSUED.
  
 5) FBC 11-4.1.2THE BUILDING SHALL BE
 SERVED BY AT LEAST ONE ACCESSIBLE ROUTE
 FROM THE ACCESSIBLE PARKING.
 ACCEPTABILITY OF THESE PLANS IS
 CONTINGENT UPON THE CIVIL/SITE PLANS,
 PERMIT# 02102208, BEING PERMITTED.
  
 6) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING, EXTERIOR DOORS AND WINDOWS.
  
 8) FBC* TABLE 2306.1STRUCTURAL NOTES,
 SHEET STR-GN, PLYWOOD ROOF DECKING.THE
 PERIMETER ZONE AT THE GABLE END SHALL
 HAVE NAILS SPACED AT 4"O.C. MAXIMUM, TO
 A DISTANCE OF 5 FEET (NOT 24") FROM THE
 EDGE OF THE ROOF.
  
 9) STRUCTURAL NOTES, SHEET STR-GN, WOOD
 TRUSS NOTE 6.IT IS NOTED THAT THE
 TRUSS DESIGN ENGINEER IS TO PROVIDE THE
 WIND UPLIFT REACTIONS.THE PERMIT
 CANNOT BE ISSUED UNTIL THE REACTIONS ARE
 SPECIFIED ON THE PLANS FOR CROSS
 REFERENCE AGAINST THE PROPOSED TRUSS
 ANCHORS AND STRAPS.
  
 10) FBC 11-4.16.3SHEET A1-2.41, DETAIL
 8A THRU 10B.THE HEIGHT OF THE W.C.
 SEAT SHOULD BE 17" TO 19", NOT 1'-3".
  
 11) FBC 2405.2THE GLAZED PANELS
 ADJACENT DOORS 101.A, 113.A AND 121.A
 ARE IN A 'HAZARDOUS LOCATION' AND ARE
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 12) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 14 Status P Date 2006-11-16 Cont ID  
Sent By dpalmer Date 2006-11-16 Time 07:58 Rev Time 0.00
Received By dpalmer Date 2006-11-15 Time 16:22 Sent To PC
Notes
2006-11-16 07:59:28REDLINED,
  
 GEN IS UNDER SEPARATE PERMIT FOR THIS BUILDING.

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 17:18 Sent To PC
Notes
2006-08-16 00:00:00REVISED BLDG PLANS, GEN IS UNDER
 06050208
  
 REDLING MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM GEN TO BLDG.
 250.122 #3 MIN AS SHOWN UNDER GEN
 PERMIT.

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2006-08-03 Cont ID  
Sent By dpalmer Date 2006-08-03 Time 19:51 Rev Time 0.00
Received By dpalmer Date 2006-08-03 Time 19:51 Sent To PC
Notes
2006-08-03 00:00:00** UNSAT ***
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEWS WHICH STATES NO FURTHER
 REVISIONS INCLUDING GENERATOR / ATS,
 FUEL TANK ETC SHALL BE REVIEWED OR
 STAMPED UNTIL SUCH TIME THE GENERATOR
 WHICH WAS APPLIED FOR UNDER A SEPARATE
 PERMIT IS ISSUED FOR PERMIT.
  
 CALLED CONTRACTOR AND LEFT MESSGAE ON MR
 MARK FORD'S VM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2006-06-20 Cont ID  
Sent By dpalmer Date 2006-06-20 Time 20:12 Rev Time 0.00
Received By dpalmer Date 2006-06-20 Time 20:12 Sent To  
Notes
2006-06-20 00:00:00*********** UNSAT *****************
  
 1) NOTE: PLEASE SEE THAT EXACT SAME
 NOTES FROM REVIEW DONE ON5/14/06 STILL
 APPLY.
 NO CORRECTIONS OR CHANGES HAVE BEEN
 MADE.
 PLEASE SEE NOTES ARE ATTACHED FROM
 PREVIOUS REVIEW.
  
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 13:42 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 13:33 Sent To  
Notes
2006-05-14 00:00:00*******UNSAT *********
  
 1) NOTE: PLEASE SEE NOTES DATED ON ALL
 PREVIOUS REVIEWS AND NOTES DATED
 7/18/05, 11/15/05,12/20/05.
 GEN, ATSIS NOTE PART OF PERMIT.
 PLANS , PERMIT APPLICATION AND FEES
 SHALL BE SUBMITTED BEFORE ANY ANY OTHER
 ELECTRICAL REVISIONS ARE DONE.
 PLEASE KNOW, THE ELECTRICAL RISER AS
 SHOWN DOES NOT MEET CODE COMPLIANCE AND
 PREVIOUS PLANS WERE REDLINED NOT TO
 INCLUDE ATS AND GEN.
 PLEASE SUBMIT ALL INFORMATION FOR
 GENERATOR PERMIT.
 PLEASE SEE 225.31-225.39, 702.5, SUBMIT
 COMPLETE PACKAGE.
 PLEASE INCLUDE ALL SPECS/MANUAFCTURES
 CUT SHEETS FOR GEN, ATS, AND FUEL SUPPLY
 TANKS IF DIESEL/ PROPANE ETC.
 ** PLEASE KNOW, A ROUGH INSPECTION WILL
 NOT BE GIVEN AND THE PERMIT FOR
 ELECTRICAL MAY BE REVOKED AS NOTES HAVE
 NOT BEEN COMPLIED WITH FOR ALMOST 1
 YEAR.(10 MONTHS)
  
 PLEASE KNOW, ONCE PERMIT FOR GEN IS
 ISSUED, OTHER REVISIONS CAN BE REVIEWED
 AT THAT TIME.
  
 2) NOTE: PLEASE SEE ADDRESS ON PLANS IS
 NOT CORRECT. PLEASE SEE ADDRESS GIVEN
 FOR PERMITTING OF THIS BUILDING WAS
 "4888", PLANS READ 4884 WHICH IS THE
 SITE ADDRESS.
 TITLE BLOCKS FOR ALL SHEETS SHALL BE
 REVISED. FAC 61G1-16.004,61G15-23.002.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2005-12-20 Cont ID  
Sent By dpalmer Date 2005-12-20 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2005-12-20 Time 18:59 Sent To  
Notes
2005-12-20 00:00:00REDLINED:
  
  
 GENERATOR AND ATS IS NOT INCLUDED ON
 THIS PERMIT AND SHALL APPLY FOR SEPARATE
 PERMIT, INCLUDING, PLANS AND FEES.
  

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2005-11-15 Cont ID  
Sent By dpalmer Date 2005-11-15 Time 11:01 Rev Time 0.50
Received By dpalmer Date 2005-11-15 Time 10:57 Sent To  
Notes
2005-11-15 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SEE REVIEW DATED 7/18/05
 WITH RESPECT TO GENERATOR INSTALLATION.
 NO PERMIT APPLICATION TO DATE HAS BEEN
 MADE FOR NEW GENERATOR. THIS MAY NOT BE
 INCLUDED UNDER BASE BLDG.
 PLEASE ALSO KNOW, A REVIEW FOR CODE
 COMPOLIANCE WILL BE DONE AT THAT TIME.
 PLEASE BE SURE TO SEE 2002 NEC,
 225.31-225.39, 445, 700ETC FOR
 REQUIREMENTS.
  
 2)NOTE: PLEASE SEE ALL ELECTRICAL SHEETS
 SHALL CLEARLY SHOW REVISIONS, DATES,
 IDENTIFIED BY CLOUDS AND TRIANGLES.
 PLEASE KNOW: A RESPONSE LETTER TELLING
 OF REV'S MADE ANDSCOPE OF WORK WILL HELP
 GREATLY IN EXPEDITING THE PLAN REVIEW
 PROCESS.
  
  
 ** PLEASE SEE COMMENTS #1, PLEASE DO NOT
 SUBMIT REVISION FOR THIS UNTIL GENERATOR
 PERMIT HAS BEEN ISSUED.
 PLEASE BE SURE WHEN THAT DOES OCCUR THAT
 PLANS REFERENCE GENERATORUNDER
 SEPARATE PERMIT,,#( ? ).
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-07-18 Cont ID  
Sent By dpalmer Date 2005-07-18 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2005-07-15 Time 21:23 Sent To  
Notes
2005-07-18 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 IN WITH A NEW GENERATOR SYSTEM WHICH WAS
 NO PART OF ORIGIANL PLANS. PLEASE SEE
 GEN SHALL BE UNDER A SEPARATE PERMIT.
 PLEASE SUBMIT COMPLETE PACKAGE FOR GEN
 REVIEW.
 PLEASE BE SURE TO SEE 2002 FOR ALL GEN
 REQUIREMENTS.
 450.13,702.5, ETC
 PLEASE SUBMIT ALL SPECS/MANUFACTURE
 SHEETS FOR GEN, ATS, ANY SUB0BASE FUEL
 TANK ?
 GEN'S SHALL BE SIZED FOR LOADS TO BE
 SERVED.
  
 SUBMIT REVISED PLANS WHEN GEN AND ALL
 TRADES RELATING TO GEN HAVE BEEN APPLIED
 FOR AND ISSUED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEYPALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-07-15 00:00:00IN ELECTRIC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-02-28 Cont ID  
Sent By dpalmer Date 2005-02-28 Time 06:15 Rev Time 0.20
Received By dpalmer Date 2005-02-28 Time 06:14 Sent To  
Notes
2005-02-28 00:00:00****** PROVISO *********
  
  
  
 PURSUANT TO DECISION BY THE AHJ AND
 BUILDING OFFICAL, ALL ELECTRICAL WORK TO
 BE PERFORMED UNDER THE 2002 NEC.
 PLANS ARE TO BE REVISED BEFORE ROUGH FOR
 ANY CHANGES AFFECTING DESIGN.
  
  
 PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-03-02 Cont ID  
Sent By dpalmer Date 2004-03-02 Time 07:40 Rev Time 0.50
Received By dpalmer Date 2004-03-02 Time 07:38 Sent To  
Notes
2004-03-02 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE CERTIFICATE OF
 AUTHORIZATION, NAME AND LICENSE # FOR
 ENGINEER IS REQ'D ON ALL PLANS.
 FS 471.023,FAC 61G15-23.002
 THIS WAS NOT A PREVIOUS COMMENT.
 THIS IS REQ'D ON ALL SHEETS AND MAY BE
 HAND WRITTEN.
  
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-10-03 Cont ID  
Sent By dpalmer Date 2003-10-03 Time 06:39 Rev Time 0.33
Received By dpalmer Date 2003-10-03 Time 06:39 Sent To  
Notes
2003-10-03 00:00:00NO CHANGES, PLANS OK. STAMPED ON 3/28/03

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-15 Cont ID  
Sent By dpalmer Date 2003-05-15 Time 09:32 Rev Time 0.50
Received By dpalmer Date 2003-05-15 Time 09:31 Sent To  
Notes
2003-05-15 00:00:00PLANS STILL OK, STAMPED PREVIOUS REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-03-28 Cont ID  
Sent By dpalmer Date 2003-03-28 Time 04:32 Rev Time 0.50
Received By dpalmer Date 2003-03-28 Time 03:59 Sent To  
Notes
2003-03-28 00:00:00PLANS OK, AND STAMPED FOR ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-11-26 Cont ID  
Sent By dpalmer Date 2002-11-26 Time 08:21 Rev Time 1.00
Received By dpalmer Date 2002-11-26 Time 08:21 Sent To  
Notes
2002-11-26 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 NEED TO BE COMPLETED ON THE BOTTOM OF
 5L/A. PLEASE NOTE LOAD SHOWN ON 5MDP
 DOES NOT CORRELATE WITH 5L/A.
  
 2)NOTE: PLEASE CLARIFY MCB IN 5MDP
 COMPLIES WITH 230-76/230-79. SHOWN AS
 SHUNT TRIP, PLEASE NOTE, MUST HAVE A
 MANUAL MEANS OF OPERATING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-06-25 Cont ID  
Sent By mamini Date 2003-06-25 Time 10:33 Rev Time 1.00
Received By mamini Date 2003-06-25 Time 10:33 Sent To  
Notes
2003-06-25 00:00:00PASSED:
 1. SEE PERMIT # 02102208 FOR UNDERGROUND
 UTILITIES AND SITE WORKS.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-03-17 Cont ID  
Sent By mamini Date 2003-03-17 Time 10:27 Rev Time 1.00
Received By mamini Date 2003-03-17 Time 10:27 Sent To  
Notes
2003-03-17 00:00:00FAILED:
 1. SEE REVIEW COMMENTS, PERMIT #02102208
 DATED 03-17-03.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-11-06 Cont ID  
Sent By mamini Date 2002-11-06 Time 10:36 Rev Time 0.00
Received By mamini Date 2002-11-06 Time 10:36 Sent To  
Notes
2003-01-10 00:00:00FAILED:
 1. SEE REVIEW COMMENTS FOR PLAN REVIEW #
 02102208.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2006-06-16 Cont ID  
Sent By mwennerg Date 2006-06-16 Time 10:41 Rev Time 0.00
Received By mwennerg Date 2006-06-16 Time 10:41 Sent To  
Notes
2006-06-16 00:00:00***DENIED***
  
 PLEASE SEE BUILDING REVIEW COMMENT
 REGARDING ARRANGEMENT OF MEANS OF EGRESS
 REGARDING THE MEETING SPACE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2006-01-03 Cont ID  
Sent By mwennerg Date 2006-01-03 Time 14:42 Rev Time 0.00
Received By mwennerg Date 2006-01-03 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2005-11-17 Cont ID  
Sent By mwennerg Date 2005-11-17 Time 14:37 Rev Time 0.00
Received By mwennerg Date 2005-11-17 Time 14:37 Sent To  
Notes
2005-11-17 00:00:00******DENIED******
 REVISION DATED 9/9/05
 PLANS APPROVED ON 4/24/03
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENTS
 REGARDING THE GENERATOR.
  
 2) DRAWINGS SHOW (2) DRY FIRE SPRINKLER
 HEADS AND NO COVERAGE IN TEL. COMM.
 ROOM. PLEASE EXPLAIN, AS THIS
 ARRANGEMENT WOULD NOT BE ACCEPTABLE.
  
 3) AS A REMINDER, SEPARATE SHOP DRAWINGS
 FOR FIRE SPRINKLER AND FIRE ALARM
 SYSTEMS ARE REQUIRED.
  
  
 MIKE WENNERGREN, CAPTAIN/ WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-08-15 Cont ID  
Sent By mwennerg Date 2005-08-15 Time 14:17 Rev Time 0.00
Received By mwennerg Date 2005-08-15 Time 14:17 Sent To  
Notes
2005-08-15 00:00:00PLANS APPROVED ON 4/24/03
  
 REVISION DATED 7/1/05
  
 SEPARATE SHOP DRAWINGS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-11-03 Cont ID  
Sent By nmccray Date 2003-11-03 Time 10:25 Rev Time 0.00
Received By nmccray Date 2003-11-03 Time 10:25 Sent To  
Notes
2003-11-03 00:00:00PLANS OK APPROVED ON 04-24-03

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By nmccray Date 2003-04-24 Time 15:21 Rev Time 0.00
Received By nmccray Date 2003-04-24 Time 15:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-04 Cont ID  
Sent By mcarsill Date 2002-12-04 Time 18:19 Rev Time 0.00
Received By mcarsill Date 2002-12-04 Time 18:19 Sent To  
Notes
2002-12-04 00:00:001) HOW IS FIRE AND PARAMEDICAL ACCESS
 OBTAINED TO THE EDUCATIONAL BUILDING.
 THE 15' CIRCLE DOES NOT MEET THE
 MINIMUM CODE REQUIREMENTS OF AT LEAST
 20'.
  
 2) BUILDING ADDRESS REQUIRED ON
 BUILDING.
  
 3) PLEASE PROVIDE THIS OFFICE A LIFE
 SAFETY PLAN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 16:01 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 16:01 Sent To FIRE
Notes
2006-11-21 16:02:49TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-11-09 Cont ID  
Sent By adarroug Date 2006-11-09 Time 15:43 Rev Time 0.00
Received By adarroug Date 2006-11-09 Time 15:43 Sent To E
Notes
2006-11-09 15:43:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 19:21 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 19:21 Sent To P
Notes
2006-11-04 19:21:53TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 13:54 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 13:54 Sent To M
Notes
2006-08-14 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 16:27 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 16:27 Sent To E
Notes
2006-07-31 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 08:17 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 08:17 Sent To M
Notes
2006-06-20 00:00:00TO "PKRAUSS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-04-25 Cont ID  
Sent By adarroug Date 2006-04-25 Time 11:42 Rev Time 0.00
Received By adarroug Date 2006-04-25 Time 11:42 Sent To  
Notes
2006-05-11 00:00:00TO "COMM" BD#30-REV
2006-04-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-01-31 Cont ID  
Sent By adarroug Date 2006-01-31 Time 13:50 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 13:50 Sent To B
Notes
2006-01-31 00:00:00TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-12-10 Cont ID  
Sent By adarroug Date 2005-12-10 Time 14:29 Rev Time 0.00
Received By adarroug Date 2005-12-10 Time 14:29 Sent To  
Notes
2006-01-03 00:00:00SENT TO M WENNERGREN DESK WITH NOTE TO
 RETURN TO R BROWN AFTER REVIEW.
2005-12-10 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 17:38 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 17:38 Sent To  
Notes
2005-09-28 00:00:00TO "COMM" BD#43
2005-09-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-07-07 Cont ID  
Sent By adarroug Date 2005-07-07 Time 13:42 Rev Time 0.00
Received By adarroug Date 2005-07-07 Time 13:42 Sent To  
Notes
2005-07-13 00:00:00TO "COMM" BD#37
2005-07-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-02-24 Cont ID  
Sent By rbrown Date 2005-02-03 Time 08:50 Rev Time 0.00
Received By rbrown Date 2005-02-03 Time 08:49 Sent To  
Notes
2005-02-24 00:00:00PLANS ON RACK (COMMERCIAL BOARD #17)

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-06 Cont ID  
Sent By csiegber Date 2004-02-06 Time 15:53 Rev Time 0.00
Received By csiegber Date 2004-02-06 Time 15:53 Sent To  
Notes
2004-02-06 00:00:00TO COMM BD#45

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 11:30 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 11:30 Sent To  
Notes
2003-09-12 00:00:00COMM BD#42/PLANS ON RACK SHELF 4

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 11:25 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 11:25 Sent To  
Notes
2003-09-12 00:00:00COMM BD#42/PLANS ON RACK SHELF 4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-05-05 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:34 Rev Time 0.00
Received By shernand Date 2003-05-05 Time 08:57 Sent To B
Notes
2003-05-05 00:00:00COMM BOARD #12,PLANS NEXT TO CONF ROOM.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-13 Cont ID  
Sent By sthyng Date 2003-03-13 Time 08:52 Rev Time 0.00
Received By sthyng Date 2003-03-14 Time 08:52 Sent To  
Notes
2003-03-14 00:00:00COMM BOARD #46
 ON RACK 1ST & 2ND SHELF

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2006-09-11 Cont ID  
Sent By pkrauss Date 2006-09-11 Time 10:49 Rev Time 0.00
Received By pkrauss Date 2006-09-11 Time 10:49 Sent To  
Notes
2006-09-11 00:00:00PROVISO FROM REVIEW DATED 6/20/06:
  
 REVISION TO PLAN SHEET M5-2.01 INDICATES
 REMOVING AHU-3 FROM THE TEL/COMM ROOM
 #118.PLEASE CLARIFY THE RATING OF THIS
 WALL PENETRATION.DOES THE RATING GO
 BEYOND THE DROP RATED CEILING OR END AT
 THE CEILING?PLEASE REVISE THE WALL
 DETAIL SHOULD THE RATING STOP AT THE
 CEILING.
  
  
 NEW PROVISO:
 GENERAL NOTES: REVISION ADDED NOTE #4
 WHICH INDICATES THE HVAC CLOSET WILL NOW
 SERVE AS A PLENUM AND ALL DEVICES
 LOCATED IN THE SPACE SHALL BE PLENUM
 RATED.PLEASE NOTE, THIS SHALL INCLUDE
 THE DOOR AND DOOR FRAME.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2006-06-20 Cont ID  
Sent By pkrauss Date 2006-06-20 Time 15:22 Rev Time 0.00
Received By pkrauss Date 2006-06-20 Time 10:41 Sent To E
Notes
2006-06-20 00:00:00PROVISO:
  
 REVISION TO PLAN SHEET M5-2.01 INDICATES
 REMOVING AHU-3 FROM THE TEL/COMM ROOM
 #118.PLEASE CLARIFY THE RATING OF THIS
 WALL PENETRATION.DOES THE RATING GO
 BEYOND THE DROP RATED CEILING OR END AT
 THE CEILING?PLEASE REVISE THE WALL
 DETAIL SHOULD THE RATING STOP AT THE
 CEILING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2006-06-12 Cont ID  
Sent By hmoser Date 2006-06-12 Time 14:44 Rev Time 0.00
Received By hmoser Date 2006-06-12 Time 14:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-01-03 Cont ID  
Sent By pkrauss Date 2006-01-03 Time 15:54 Rev Time 0.00
Received By pkrauss Date 2006-01-03 Time 15:54 Sent To  
Notes
2006-01-03 00:00:00PROVISO:
 PRIOR TO ROUGH INSPECTION, PLEASE
 PROVIDE DETAIL THE MOUNTING DETAIL FOR
 THE HORIZONTAL UNIT LOCATED IN THE
 COM/TEL ROOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  
  
  
  
  
  
2005-12-20 00:00:00NEW SHEET ADDED DATED 12/9/05

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-11-16 Cont ID  
Sent By pkrauss Date 2005-11-16 Time 13:20 Rev Time 1.00
Received By pkrauss Date 2005-11-16 Time 12:49 Sent To  
Notes
2005-11-16 00:00:00PLEASE NOTE THE FOLLOWING - REVIEW DOES
 NOT INCLUDE APPROVAL FOR THE GENERATOR,
 (SEE ALSO COMMENTS BY DEWEY PALMER,
 ELECTRICAL PLANS EXAMINER).

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-07-27 Cont ID  
Sent By pkrauss Date 2005-07-27 Time 16:22 Rev Time 0.50
Received By pkrauss Date 2005-07-27 Time 15:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By pkrauss Date 2005-03-08 Time 10:56 Rev Time 0.15
Received By pkrauss Date 2005-03-08 Time 10:37 Sent To  
Notes
2005-03-08 00:00:00EDUCATION BUILDING (5)
 APPROVED 5-10-03 - NO CHANGES ON THE
 RESUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-05-10 Cont ID  
Sent By pkrauss Date 2003-05-10 Time 11:38 Rev Time 0.35
Received By pkrauss Date 2003-05-10 Time 11:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-04-24 Cont ID  
Sent By pkrauss Date 2003-04-24 Time 14:16 Rev Time 0.55
Received By pkrauss Date 2003-04-24 Time 14:16 Sent To  
Notes
2003-04-24 00:00:00PROVISO:
  
 PLAN SHEET M5-2.01 STAFF TOILET ROOM
 #122, INDICATES A RETURN AIR GRILLE IN
 THE TOILET ROOM.AS PER 2001 FBC(M)
 TABLE 403.3 NOTE B, MECHANICAL EXHAUST
 REQUIRED & RECIRCULATION IS PROHIBITED
 FROM PUBLIC RESTROOMS. PLEASE RELOCATE
 RETURN AIR GRILLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-03 Cont ID  
Sent By pkrauss Date 2002-12-03 Time 13:22 Rev Time 1.00
Received By pkrauss Date 2002-12-03 Time 13:11 Sent To  
Notes
2002-12-03 00:00:00EDUCATIONAL BUILDING #5
 DENIED:
  
 PRIOVIDE INFORMATION ON THE CONDENSATE
 DRAIN. INDICATE TERMINATION - AS PER
 2001 FBC(M) 307.2.1 (1) UNITS LARGER
 THAN 6 TON SHALL DISCHARGE INTO STORM
 DRAIN OR AN APPROVED DRYWELL.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS OR A SUPER-
 VISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.NFPA 90A 4-4.4.3 & 4-4.4.2
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 8 Status P Date 2006-11-07 Cont ID  
Sent By pschmitz Date 2006-11-07 Time 14:21 Rev Time 0.00
Received By pschmitz Date 2006-11-07 Time 14:21 Sent To PC
Notes
2006-11-07 14:23:09AS BUILT REVISIION FOR DWVU/G

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-06-20 Cont ID  
Sent By kstevens Date 2006-06-20 Time 08:43 Rev Time 0.00
Received By kstevens Date 2006-06-20 Time 08:42 Sent To  
Notes
2006-06-20 00:00:00REVISION OK SHTS P5-2.01 & P5-3.01 NEW
 BUILDING LAYOUT/RISERS.

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-01-04 Cont ID  
Sent By pschmitz Date 2006-01-04 Time 09:33 Rev Time 0.00
Received By pschmitz Date 2006-01-04 Time 09:10 Sent To B
Notes
2006-01-04 00:00:00REVISION APPROVED

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-10-09 Cont ID  
Sent By pschmitz Date 2005-10-09 Time 11:40 Rev Time 0.00
Received By pschmitz Date 2005-10-09 Time 11:00 Sent To  
Notes
2005-10-09 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE
 PLAN REVIEW, DENIED
 WHEN RE- SUBMITTING PLANS PLEASE SUBMITT
 A TRANSMITTAL LETTER FOR ALL DISCIPLINES
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE. IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PLEASE ADDRESS PREVIOUS COMMENTS,
 DATED 8-05-05 BY KEN STEVENS
  
 2. SHTS P5-2.01 & 5-3.01 THE BACKFLOW
 FOR THE 1/2" WATER LINE TO AHU-3 SHALL
 BE LOCATED A MAXIMUM OF 4' ABOVE FINISH
 FLOOR FOR SERVICE AND CERTIFICATION.
 SHT M5-601,NOTE #4 MOUNT AHU BELOW
 CEILING, PLEASE CLARIFY.
 3. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BUILDING. SECTION
 608.13.2.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-08-05 Cont ID  
Sent By kstevens Date 2005-08-05 Time 11:00 Rev Time 1.36
Received By kstevens Date 2005-08-05 Time 11:00 Sent To  
Notes
2005-08-05 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A. THIS REVISION IS A COMPLETE CHANGE OF
 THE FLOOR PLAN.
 1. SHT A5-4.1 DETAIL #2 WATER CLOSETS
 SHALL BE 1'6" FROM THE SIDE WALL TO THE
 CENTERLINE OF THE FIXTURE. 1'8" SHOWN.
 FIGURE 28.
 2. SHTS P5-2.01 & 5-3.01 THE BACKFLOW
 FOR THE 1/2" WATER LINE TO AHU-3 SHALL
 BE LOCATED A MAXIMUM OF 4' ABOVE THE
 FLOOR FOR SERVICE AND CERTIFICATION. -
 NO CONDENSATE IS SHOWN FOR AHU-3. PLEASE
 CLARIFY IF THERE WILL BE A CONDENSATE
 LINE FOR THE AIR HANDLER.
 3. AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BUILDING. SECTION
 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-06-07 Cont ID  
Sent By kstevens Date 2003-06-07 Time 13:09 Rev Time 0.50
Received By kstevens Date 2003-06-07 Time 13:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-04-01 Cont ID  
Sent By kstevens Date 2003-04-01 Time 11:25 Rev Time 0.50
Received By kstevens Date 2003-04-01 Time 11:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-11 Cont ID  
Sent By kstevens Date 2002-12-11 Time 17:49 Rev Time 1.00
Received By kstevens Date 2002-12-11 Time 17:02 Sent To  
Notes
2002-12-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 5-2.1 MINIMUM FACILITIES REQUIRE
 2 DRINKING FOUNTAINS. A HI/LOW DRINKING
 FOUNTAIN IS CONSIDERED 1 FIXTURE SO ONE
 MORE DRINKING FOUNTAIN IS REQUIED. TABLE
 403.1
 2) SHTS A5-2.1 & A5-4.1, TOILET ROOMS
 #144 & 122, IF TOILET FACILITIES ARE
 PROVIDED ON A SITE, THEN EACH SUCH PUB-
 LIC AND COMMON USE TOILET FACILITY SHALL
 COMPLY WITH 11-4.22 PER SECTION 11-4.1.2
 (6).
 3) SHT P5-3.01 WATER RISER DIAGRAM, A
 BACKFLOW IS REQUIRED, AND WATER HAMMER
 ARRESTORS REQUIRED BY 406.9 SHALL BE
 LOCATED NEAR THE FIXTURE IN AN "EFFECT-
 IVE RANGE" NOT AT THE TOP OF THE DROPS.
 PER PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 3 Status P Date 2006-01-04 Cont ID  
Sent By eschneid Date 2006-01-04 Time 17:44 Rev Time 0.00
Received By eschneid Date 2006-01-04 Time 17:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2003-06-06 Cont ID  
Sent By sgraham Date 2003-06-06 Time 16:34 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-01-13 Cont ID  
Sent By sgraham Date 2003-01-13 Time 11:17 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2003-01-13 00:00:00DENIED, NEED MINOR AMENDMENT AND THE
 PLAT TO BE RECORDED


Account Summary | Usage Policy | Privacy Policy